Components
Service manual
47
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Compressor motor winding
measurements are correct?
Action
Yes
Continue with the next step.
No
Replace the compressor, see
49].
5
Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see
6
Connect the Faston connectors to the compressor wire terminals U, V and W
V
U
W
U
Wire terminal U
V
Wire terminal V
W
Wire terminal W
7
Install the compressor insulation.
8
Turn ON the power using the respective circuit breaker.
9
Start the unit operation via the user interface.
10
Wait for – or create condition to operate the compressor.
11
Once the compressor operates, measure the U-V-W inverter voltages. All
measurements MUST be the same.
Inverter voltage measurements are
correct?
Action
Yes
Continue with the next step.
No
Perform a check of the appropriate PCB,
see
37].
12
Measure the current in each phase U, V and W while compressor is operating.
All measurements MUST be the same.
Compressor motor winding current
measurements are correct?
Action
Yes
Perform an insulation check of the
compressor, see
No
Preventively replace the compressor,
see