FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Is the measured insulation resistance
correct?
Action
Yes
Continue with the next step.
No
Replace the reactor, see
4
Measure the resistance of the reactor.
Result:
The measured resistance MUST be 105.3~128.7 mΩ.
Is the resistance measurement correct? Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
Replace the reactor, see
Class 50~71 units
1
Check that the reactors are firmly installed on the main PCB.
a
b
a
Reactor L803
b
Reactor L804
2
Remove the main PCB, see
89]. The reactor measuring
points are ONLY reachable on the back side of the main PCB.
3
Measure the resistance of the reactor using a low ohm multi meter.
Result:
The resistance MUST be as follows:
Measuring points
Resistance
c‑d
15~25 mΩ
e
152~228 mΩ