2
|
Components
Service manual
61
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
b
c
c
d
e
a
a
Expansion valve motor
b
Metal bracket
c
Nipple
d
Notch
e
Expanion valve body
2
Route the expansion valve motor harness towards the appropriate PCB.
3
Connect the expansion valve motor connector to the appropriate PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
4
Fix the expansion valve motor harness using new tie straps.
5
Install the insulation cap on the expansion valve motor (if applicable).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
valve and continue with the next
procedure.
2.4 High pressure switch
2.4.1 Checking procedures
To perform an electrical check of the high pressure switch
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Recuperate the refrigerant from the refrigerant circuit, see
133].
2
Fill the refrigerant circuit with nitrogen until pressurized just below operating
pressure of the high pressure switch.