![background image](http://html1.mh-extra.com/html/daikin/rzqsg100l8y1/rzqsg100l8y1_technical-data-manual_2460039018.webp)
• Outdoor Unit • RZQSG-L(8)Y1
6
• Split - Sky Air • RZQSG-L(8)Y1
16
6
Capacity tables
6 - 1 Cooling/Heating Capacity Tables
RZQSG100L9V1
RZQSG100L8Y1
Cooling
Heating
Symbols
AFR: Air
flow
rate
[m³/min]
BF: Bypass
factor
EWB: Entering
wet
Ͳ
bulb
temperature
(°C
WB)
EDB: Entering
dry
Ͳ
bulb
temperature
(°C
DB)
TC: Maximum
total
cooling/heating
capacity
[kW]
SHC: Sensible
heat
capacity
[kW]
CPI: Coefficient
of
the
power
input
PI: Power
input
[kW]
compressor
+
indoor
and
outdoor
fan
motors
Cooling
Heating
Notes
1. The
ratings
shown
are
net
capacities
which
include
a
deduction
for
indoor
fan
motor
heat.
2.
= Maximum
at
standard
conditions
= Rated
capacity
and
rated
coefficient
of
the
power
input
The
maximum
capacity
is
not
guaranteed
except
at
standard
conditions.
3. SHC
is
based
on
indoor
units
EWB
&
EDB.
SHC
for
other
dry
Ͳ
bulb
temperatures
=
SHC
+
SHC*
SHC*
= SHC
correction
for
other
dry
Ͳ
bulb
temperatures
= 0.02
x
AFR
(m³/min)
x
(1
Ͳ
BF)
x
(DB*
Ͳ
EDB)
4. The
capacities
are
based
on
the
following
conditions:
Outdoor
air:
85%
RH
However,
the
outdoor
ambient
condition
of
the
rated
capacity
during
heating
operation
is
7°C
DB
/
6°C
WB.
Corresponding
refrigerant
piping
length:
5.0
m
Level
difference:
0m
5. CPI
is
a
percentage
value
compared
to
the
rated
value
which
is
1.00.
6. The
error
rate
for
this
value
is
less
than
5%
and
depends
on
the
indoor
unit
type.
7. The
heating
performance
takes
into
account
the
drop
that
occurs
during
defrost
operation.
8. The
air
flow
rate
and
bypass
factor
are
mentioned
in
the
table.
9. The
rated
power
input
for
each
model
is
mentioned
in
the
table
below.
Pair
Pair
FCQGH100F
FCQG100F
FBQ100C
FHQG100C
FAQ100C
FVQ100C
FHQ100CA
FBQ100D
FCQGH100F
FCQG100F
FBQ100C
FHQG100C
FAQ100C
FVQ100C
FHQ100CA
FBQ100D
Cooling
2,57
2,88
2,87
2,96
3,16
2,96
2,96
2,84
Heating
2,51
3,05
2,96
2,99
3,17
2,99
2,99
2,94
Twin
Twin
FCQG50F
X
2
FBQ50C
X
2
FHQ50CA
X
2
FFQ50C
X
2
FDXS50F9
X
2
FBQ50D
X
2
FNQ50A
X
2
FCQG50F
X
2
FBQ50C
X
2
FHQ50CA
X
2
FFQ50C
X
2
FDXS50F9
X
2
FBQ50D
X
2
FNQ50A
X
2
Cooling
2,76
2,93
3,35
3,13
3,15
3,10
3,15
Heating
2,61
2,86
3,28
3,34
3,31
3,27
3,31
Triple
Triple
FCQG35F
X
3
FBQ35C
X
3
FHQ35CA
X
3
FFQ35C
X
3
FDXS35F
X
3
FBQ35D
X
3
FNQ35A
X
3
FCQG35F
X
3
FBQ35C
X
3
FHQ35CA
X
3
FFQ35C
X
3
FDXS35F
X
3
FBQ35D
X
3
FNQ35A
X
3
Cooling
2,82
2,93
3,33
2,88
3,71
2,90
3,71
Heating
2,66
2,86
3,26
3,04
4,06
3,24
4,06
8.7
x
3
(0.17
x
3)
15
x
3
(0.08
x
3)
8.7
x
3
(0.17
x
3)
18
x
2
(0.15
x
2)
16
x
2
(0.11
x
2)
AFR
(BF)
12.5
x
3
(0.4
x
3)
16
x3
(0.15
x
3)
14
x
3
(0.17
x
3)
10
x
3
(0.25
x
3)
AFR
(BF)
12.6
x
2
(0.22
x
2)
16
x2
(0.16
x
2)
15
x
2
(0.18
x
2)
12
x
2
(0.16
x
2)
16
x
2
(0.11
x
2)
26.0
(0.10)
28.0
(0.20)
28.0
(0.09)
29.0
(0.03)
AFR
(BF)
32.3
(0.17)
32.0
(0.17)
32.0
(0.13)
20.0
(0.09)
Co
effi
ci
en
t
of
th
e
pow
er
input
Co
effi
ci
en
t
of
th
e
pow
er
input
Cooling
capacity
[kW]
Heating
capacity
[kW]
Capacity
range
Rated
point
Rated
point
Indoor
Indoor
Outdoor
temperature
[°C
DB]
Outdoor
temperature
[°C
WB]
Capacity
range
3D076753E
RZQSG125L9V1
RZQSG125L8Y1
Cooling
Heating
Symbols
AFR: Air
flow
rate
[m³/min]
BF: Bypass
factor
EWB: Entering
wet
Ͳ
bulb
temperature
(°C
WB)
EDB: Entering
dry
Ͳ
bulb
temperature
(°C
DB)
TC: Maximum
total
cooling/heating
capacity
[kW]
SHC: Sensible
heat
capacity
[kW]
CPI: Coefficient
of
the
power
input
PI: Power
input
[kW]
compressor
+
indoor
and
outdoor
fan
motors
Cooling
Heating
Notes
1. The
ratings
shown
are
net
capacities
which
include
a
deduction
for
indoor
fan
motor
heat.
2.
= Maximum
at
standard
conditions
= Rated
capacity
and
rated
coefficient
of
the
power
input
The
maximum
capacity
is
not
guaranteed
except
at
standard
conditions.
3. SHC
is
based
on
indoor
units
EWB
&
EDB.
SHC
for
other
dry
Ͳ
bulb
temperatures
=
SHC
+
SHC*
SHC*
= SHC
correction
for
other
dry
Ͳ
bulb
temperatures
= 0.02
x
AFR
(m³/min)
x
(1
Ͳ
BF)
x
(DB*
Ͳ
EDB)
4. The
capacities
are
based
on
the
following
conditions:
Outdoor
air:
85%
RH
However,
the
outdoor
ambient
condition
of
the
rated
capacity
during
heating
operation
is
7°C
DB
/
6°C
WB.
Corresponding
refrigerant
piping
length:
5.0
m
Level
difference:
0m
5. CPI
is
a
percentage
value
compared
to
the
rated
value
which
is
1.00.
6. The
error
rate
for
this
value
is
less
than
5%
and
depends
on
the
indoor
unit
type.
7. The
heating
performance
takes
into
account
the
drop
that
occurs
during
defrost
operation.
8. The
air
flow
rate
and
bypass
factor
are
mentioned
in
the
table.
9. The
rated
power
input
for
each
model
is
mentioned
in
the
table
below.
Pair
Pair
FCQHG125F
FCQG125F
FBQ125C
FHQG125C
FAQ125C
FVQ125C
FHQ125CA
FBQ125D
FCQHG125F
FCQG125F
FBQ125C
FHQG125C
FAQ125C
FVQ125C
FHQ125CA
FBQ125D
Cooling
3,71
3,74
3,74
4,15
3,74
4,27
4,15
3,72
Heating
3,60
3,96
3,85
3,73
3,85
3,96
3,73
3,72
Twin
Twin
FCQG60F
X
2
FBQ60C
X
2
FHQ60CA
X
2
FFQ60C
X
2
FDXS60F
X
2
FBQ60D
X
2
FNQ60A
X
2
FCQG60F
X
2
FBQ60C
X
2
FHQ60CA
X
2
FFQ60C
X
2
FDXS60F
X
2
FBQ60D
X
2
FNQ60A
X
2
Cooling
3,66
3,95
4,34
4,75
4,88
4,24
4,88
Heating
3,88
4,06
4,43
4,33
4,38
4,14
4,38
Triple
Triple
FCQG50F
X
3
FBQ50C
X
3
FHQ50CA
X
3
FFQ50C
X
3
FDXS50F9
X
3
FBQ50D
X
3
FNQ50A
X
3
FCQG50F
X
3
FBQ50C
X
3
FHQ50CA
X
3
FFQ50C
X
3
FDXS50F9
X
3
FBQ50D
X
3
FNQ50A
X
3
Cooling
3,69
3,95
4,33
4,14
4,07
4,08
4,07
Heating
3,90
4,06
4,42
3,87
3,92
4,09
3,92
Double
twin
Double
twin
FCQG35F
X
4
FBQ35C
X
4
FHQ35CA
X
4
FFQ35C
X
4
FDXS35F
X
4
FBQ35D
X
4
FNQ35A
X
4
FCQG35F
X
4
FBQ35C
X
4
FHQ35CA
X
4
FFQ35C
X
4
FDXS35F
X
4
FBQ35D
X
4
FNQ35A
X
4
Cooling
3,75
3,95
4,31
3,99
4,67
3,95
4,67
Heating
3,96
4,06
4,32
3,59
4,66
4,03
4,66
15
x
4
(0.08
x
4)
8.7
x
4
(0.17
x
4)
AFR
(BF)
12.5
x
4
(0.4
x
4)
16
x4
(0.15
x
4)
14
x
4
(0.17
x
4)
10
x
4
(0.25
x
4)
8.7
x
4
(0.17
x
4)
16
x
3
(0.11
x
3)
15
x
3
(0.13
x
3)
16
x
3
(0.11
x
3)
18
x
2
(0.15
x
2)
16
x
2
(0.12
x
2)
AFR
(BF)
12.6
x
3
(0.22
x
3)
16
x
3
(0.16
x
3)
15
x
3
(0.18
x
3)
12
x
3
(0.16
x
3)
AFR
(BF)
13.6
x
2
(0.2
x
2)
18
x
2
(0.15
x
2)
19.5
x
2
(0.20
x
2)
14.5
x
2
(0.11
x
2)
16
x
2
(0.12
x
2)
39.0
(0.16)
28.0
(0.16)
31.0
(0.14)
34.0
(0.06)
AFR
(BF)
33.5
(0.19)
33.0
(0.21)
39.0
(0.16)
31.0
(0.134)
Co
effic
ie
nt
of
the
powe
r
input
Co
effic
ie
nt
of
the
powe
r
input
Cooling
capacity
[kW]
Heating
capacity
[kW]
Capacity
range
Rated
point
Capacity
range
Rated
point
Indoor
Indoor
Outdoor
temperature
[°C
DB]
Outdoor
temperature
[°C
WB]
3D076754F