Installation manual

13

Test run

1

Be sure to turn power on at least 6 hours before starting
operation in order to protect the compressor.

2

Make sure the liquid and gas stop valves are open.

3

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.

4

Be sure to set the unit to cooling operation mode.

5

Press the inspection/test operation button of the remote
controller 4 times (2 times in case of a wireless remote
controller) to go into the test run mode.

6

Press the ON/OFF button within 10 seconds to start the test run
and check the operation status for about 6 minutes. The
refrigerant pressure may not rise immediately, even if the stop
valve is opened after an air purge is performed using a vacuum
pump. This is because the indoor unit refrigerant piping is closed
off with electric valves inside. This will not create any problems
during operation.

7

Push the air flow direction adjust button and check if the unit is
responding to the new air flow direction position.

8

Press the inspection/test operation button of the remote
controller 2 times to go into check mode and to make sure that
the malfunction code displays 

"

00

"

 (=normal). In case the

malfunction code does not display 

"

00

"

, refer to 

"Failure

diagnosis at the moment of first installation" on page 13

.

9

If the inspection/test operation button is pressed 4 times during a
test run, the unit returns to normal operation.

10

Check all functions according to the operation manual.

Precautions regarding test-runs

1

In order to detect stop valves failing to open, operation of the
unit is compulsorily performed in cooling for 2-3 minutes during
the first test run, even if the remote controller was set to heating
operation. In this case, the remote controller will have kept
displaying the heating symbol all the time and the unit will switch
to heating operation automatically after elapse of that time.

2

In case you cannot operate the unit in test run mode for any
unusual reason, refer to 

"Failure diagnosis at the moment of first

installation" on page 13

.

3

In case you cannot operate the unit in test run mode, the unit
usually returns to its normal state after 30 minutes.

4

In case of a wireless remote controller, execute the test run only
after having installed the indoor unit decoration panel with infra-
red receiver first.

5

In case the panels of indoor units are not yet installed to the
indoor units, make sure to shut off the power supply after
finishing the complete test run.

6

A complete test run surely includes shutting off power after
having performed a normal operation stop on the remote
controller. Do not stop operation by turning circuit breakers off.

Failure diagnosis at the moment of first installation

In case nothing is displayed on the remote controller (the current
set temperature does not display), check for any of the following
abnormalities before you can diagnose possible malfunction
codes.

Disconnection or wiring error (between power supply and
outdoor unit, between outdoor unit and indoor units, between
indoor unit and remote controller).

The fuse on the outdoor unit PCB may have run out.

If the remote controller shows 

"

E3

", "

E4

"

 or 

"

L8

"

 as an error code,

there is a possibility that either the stop valves are closed, or that
air inlet or air outlet are blocked.

If the error code 

"

U2

"

 is displayed on the remote controller,

check for voltage imbalance.

If the error code 

"

U4

"

 or 

"

UF

"

 is displayed on the remote

controller, check the inter-unit branch wiring connection.

If the error code 

"L4"

 is displayed on the remote controller, it is

possible that air inlet or air outlet are blocked.

The reversed phase protection detector of this product only
works during the initialisation stage after a power reset.
The reversed phase protection detector is designed to stop the
product in case of an abnormality when the product is started up.

When the reversed phase protection circuit forces the unit to
stop, check if all phases exist. If this is the case, shut off the
power supply to the unit and replace two of three phases.
Turn on power again and start the unit.

Reversed phase detection is not performed while the product
is operating.

In case of possible reversal of phases after a momentary
black out of power and the power goes on and off while the
product is operating, install a reversed phase protection
circuit on site. Such situation is not unimaginable when using
generators. Running the product in reversed phase can
break the compressor and other parts.

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.

 

Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

4PEN342104-1B.book  Page 13  Tuesday, May 26, 2015  9:07 AM

Summary of Contents for RZQS71D2V1B

Page 1: ...INSTALLATION MANUAL RZQSG71L3V1B RZQS71D7V1B RZQS71D2V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B Split System air conditioners 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 2: ...E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 1 2 3 4 5 7 8 9 6 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 3: ...giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henho...

Page 4: ...e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka...

Page 5: ...lectrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not act on the terminal conn...

Page 6: ...is appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound level is less than 70 dB A Provide a logbook In accordance with the relevant national and international codes it may be necessary to provide a logbook with the equipment containing at least info on maintenance repair work results of tests stand by period...

Page 7: ...en a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the building s wall fence or screen Set the outlet side at a right angle to the direction of the wind 3 Prepare a water drainage channel around the foun...

Page 8: ...ocket optional Make sure the drain works properly Installation servicing space The numerical figures used in here represent the dimensions for the 71 100 125 140 class models Figures between indicate the dimensions for the 100 125 140 class models Unit mm Refer to Precautions on installation on page 4 Precaution A In case of non stacked installation See figure 1 B In case of stacked installation 1...

Page 9: ...ipe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Europe EN378 is ...

Page 10: ...Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal Refrigerant piping Field pipes can be installed in four directions Figure Field pipes in four directions Cutting out the two slits makes it possible to install as shown in the figure Field pipes in four directions Use a metal saw to cut out the slits To install ...

Page 11: ...r handling the valve cover The valve cover is sealed where indicated by the arrow Refer to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service port Always use a flexible charge hose with a push rod and valve to enable recovery of remaining refrigerant in the ...

Page 12: ...iping will create large quantities of oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preventers Residue of such preventers may result in choking of pipes or malfunction of components When brazing while inserting nitrogen into the piping nitrogen must be s...

Page 13: ...e vacuum pump with a non return valve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 100 7 kPa After keeping the system under that condition for more than one hour check if the vacuum gauge rises or not If it rises the system may either contain moisture inside or have leaks The ...

Page 14: ...e pumping down operation make sure to have removed the insulation sheet that was placed in the switch box as a protective measure as in chapter Preliminary measures on page 10 When in need of operation turn off the main power supply and turn it on again Make sure that stop valves both on liquid and gas side are open and be sure to operate the unit in cooling operation during test run Liquid piping...

Page 15: ... stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knock out hole See figure 7 When you do not use a wire conduit ...

Page 16: ...washer RZQSG71 RZQS71 RZQS100 RZQS125 RZQS140 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact values 21 2 18 9 27 6 28 8 Recommended field fuse A 25 20 32 Wire type b b Only in protected pipes use H07RN F when protected pipes are not used H05VV U3G Size Wiring size must comply with the applicable local and national code W...

Page 17: ... receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete test run 6 A complete test run surely includes shutting off power after having performed a normal operation stop on the remote controller Do not stop operation by turning circuit breakers off Failure diagnosis at the moment of first inst...

Page 18: ...stor coil middle R6T Thermistor liquid R10T Thermistor fin RC Signal receiver circuit S1NPH Pressure sensor high S1PH Pressure switch high TC Signal transmission circuit V1R Power module V2R V3R Diode module V1T Insulated gate bipolar transistor X1M Terminal strip X6A Connector option Y1E Expansion valve Y1S 4 way valve Z1C Z3C Noise filter Z1F Z4F Noise filter Wire clamp BLK Black Terminal GRN Gr...

Page 19: ...4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 20: ...4P342104 1B 2015 05 Copyright 2013 Daikin 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Reviews: