background image

Installation manual

2

Caution

Ground the air conditioner.
Grounding resistance should be according to national
regulations.
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire.
Incomplete grounding may cause electric shocks.

Gas pipe.
Ignition or explosion may occur if the gas leaks.

Water pipe.
Hard vinyl tubes are not effective grounds.

Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by lightning.

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may cause electric
shocks and fire.

Install drain piping according to this installation manual to ensure
good drainage, and insulate the pipe to prevent condensation.
Improper drain piping may cause water leakage, and make the
furniture get wet.

Install the indoor and outdoor units, power wire and connecting
wire at least 1 meter away from televisions or radios to prevent
image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)

Do not rinse the outdoor unit. This may cause electric shocks or
fire.

Do not install the air conditioner in places such as the following:

Where there is mist of mineral oil, oil spray or vapour, for
example a kitchen.
Plastic parts may deteriorate, causing them to fall out or
water to leak.

Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.

Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.

Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled.
Such gases may cause fire.

Where the air contains high levels of salt such as that near
the ocean.

Where voltage fluctuates a lot, such as that in factories.

In vehicles or vessels.

Where acidic or alkaline vapour is present.

This appliance is intended to be used by expert or trained users
in shops, in light industry and on farms, or for commercial use by
lay persons.

Sound level is less than 70 dB(A).

Provide a logbook

In accordance with the relevant national and international codes, it
may be necessary to provide a logbook with the equipment
containing at least 

- info on maintenance,
- repair work,
- results of tests,
- stand-by periodes,
- etc...

In Europe, EN378 provides the necessary guidance for this logbook.

Before installation

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
- Clean and dry
Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
- Tight
Read 

"Precautions on refrigerant piping" on page 6

 carefully and

follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in a state of gas, its composition changes and the system will not
work properly).

The connected indoor units must be indoor units designed
exclusively for R410A.

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

Illustrations show class 125 outdoor unit type. Other types also
follow this installation manual.

This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.

Never operate the unit with a damaged or disconnected
discharge thermistor and suction thermistor, burning of the
compressor may result.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

Accessories

Check if the following accessories are included with the unit

Since maximum working pressure is 4.0 MPa or 40 bar,
pipes of larger wall thickness may be required. Refer to
paragraph 

"Selection of piping material" on page 5

.

Installation manual

1

Clamp

2

Fluorinated greenhouse gases 
label

1

Multilingual fluorinated 
greenhouse gases label

1

4PEN342104-1B.book  Page 2  Tuesday, May 26, 2015  9:07 AM

Summary of Contents for RZQS71D2V1B

Page 1: ...INSTALLATION MANUAL RZQSG71L3V1B RZQS71D7V1B RZQS71D2V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B Split System air conditioners 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 2: ...E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 1 2 3 4 5 7 8 9 6 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 3: ...giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henho...

Page 4: ...e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom jotka...

Page 5: ...lectrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not act on the terminal conn...

Page 6: ...is appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound level is less than 70 dB A Provide a logbook In accordance with the relevant national and international codes it may be necessary to provide a logbook with the equipment containing at least info on maintenance repair work results of tests stand by period...

Page 7: ...en a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the building s wall fence or screen Set the outlet side at a right angle to the direction of the wind 3 Prepare a water drainage channel around the foun...

Page 8: ...ocket optional Make sure the drain works properly Installation servicing space The numerical figures used in here represent the dimensions for the 71 100 125 140 class models Figures between indicate the dimensions for the 100 125 140 class models Unit mm Refer to Precautions on installation on page 4 Precaution A In case of non stacked installation See figure 1 B In case of stacked installation 1...

Page 9: ...ipe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Europe EN378 is ...

Page 10: ...Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal Refrigerant piping Field pipes can be installed in four directions Figure Field pipes in four directions Cutting out the two slits makes it possible to install as shown in the figure Field pipes in four directions Use a metal saw to cut out the slits To install ...

Page 11: ...r handling the valve cover The valve cover is sealed where indicated by the arrow Refer to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service port Always use a flexible charge hose with a push rod and valve to enable recovery of remaining refrigerant in the ...

Page 12: ...iping will create large quantities of oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preventers Residue of such preventers may result in choking of pipes or malfunction of components When brazing while inserting nitrogen into the piping nitrogen must be s...

Page 13: ...e vacuum pump with a non return valve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 100 7 kPa After keeping the system under that condition for more than one hour check if the vacuum gauge rises or not If it rises the system may either contain moisture inside or have leaks The ...

Page 14: ...e pumping down operation make sure to have removed the insulation sheet that was placed in the switch box as a protective measure as in chapter Preliminary measures on page 10 When in need of operation turn off the main power supply and turn it on again Make sure that stop valves both on liquid and gas side are open and be sure to operate the unit in cooling operation during test run Liquid piping...

Page 15: ... stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knock out hole See figure 7 When you do not use a wire conduit ...

Page 16: ...washer RZQSG71 RZQS71 RZQS100 RZQS125 RZQS140 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact values 21 2 18 9 27 6 28 8 Recommended field fuse A 25 20 32 Wire type b b Only in protected pipes use H07RN F when protected pipes are not used H05VV U3G Size Wiring size must comply with the applicable local and national code W...

Page 17: ... receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete test run 6 A complete test run surely includes shutting off power after having performed a normal operation stop on the remote controller Do not stop operation by turning circuit breakers off Failure diagnosis at the moment of first inst...

Page 18: ...stor coil middle R6T Thermistor liquid R10T Thermistor fin RC Signal receiver circuit S1NPH Pressure sensor high S1PH Pressure switch high TC Signal transmission circuit V1R Power module V2R V3R Diode module V1T Insulated gate bipolar transistor X1M Terminal strip X6A Connector option Y1E Expansion valve Y1S 4 way valve Z1C Z3C Noise filter Z1F Z4F Noise filter Wire clamp BLK Black Terminal GRN Gr...

Page 19: ...4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Page 20: ...4P342104 1B 2015 05 Copyright 2013 Daikin 4PEN342104 1B book Page 1 Tuesday May 26 2015 9 07 AM ...

Reviews: