background image

17 

English

When a malfunction code is displayed in the remote 
controller

(Check a malfunction code in the remote controller connected 
to the indoor unit.)

Malfunction 

code

Cause

Solution

E3

The stop valves in 
the outdoor unit 
remain closed.

Open the stop valve on both the 
gas and liquid lines.

The refrigerant is 
overcharged.

Calculate again the required 
amount of refrigerant to be charged 
based on the piping length, recover 
the refrigerant using the refrigerant 
recovery device, then achieve 
proper amount of refrigerant.

E4
F3

The stop valves in 
the outdoor unit 
remain closed.

Open the stop valve on both the 
gas side and liquid side.

The operation 
mode on the 
remote controller 
was changed 
before the check 
operation.

Set the operation mode on all 
indoor unit remote controllers to 
“cooling.”

The refrigerant is 
insuffi cient.

Check whether additional 

 

refrigerant charge has been 
fi nished correctly.
Calculate again the required 

 

amount of refrigerant to be 
charged based on the piping 
length, then charge additionally 
proper amount of refrigerant.

F6

The refrigerant is 
overcharged.

Calculate again the required 
amount of refrigerant to be charged 
based on the piping length, recover 
the refrigerant using the refrigerant 
recovery device, then achieve 
proper amount of refrigerant.

U3

The check 
operation has not 
performed.

Perform the check operation.

U4

The power is not 
supplied to the 
outdoor unit.

Connect correctly the power supply 
wiring of the outdoor unit.

UA

Improper type of 
indoor unit is 
connected.

Check the type of indoor unit 
currently connected.  If it is not 
proper, replace it with proper one.

UF

The stop valves in 
the outdoor unit 
remain closed.

Open the stop valve on both the 
gas and liquid lines.

The piping and 
wiring of the 
indoor unit are 
not connected 
correctly to the 
outdoor unit.

Confi rm that the piping and wiring 
of the indoor unit are connected 
correctly to the outdoor unit.

The operation 
mode on the 
remote controller 
was changed 
before the check 
operation.

Set the operation mode on indoor 
unit remote controller to “cooling.”

UH

The transmission 
wiring is not 
connected 
correctly.

Connect correctly the transmission 
wiring to the F1 and F2 (TO IN/D 
UNIT) terminals on the PC board 
(A1P) in the outdoor unit.

When nothing is displayed in the remote controller

There might be a problem with the connection or transmis-

• 

sion between the indoor unit and the remote controller.
Check connections, and check for wire breakage.

 CAUTION

<To piping technician>
<To electrician>

After fi nishing the test run and before using the unit by 

 

customer, confi rm that the front panel and screws are 
attached securely to the unit.

CAUTION FOR REFRIGERANT LEAKS

10. 

 DANGER

Refrigerant gas is heavier than air and replaces oxygen. A 

• 

massive leak could lead to oxygen depletion, especially in 
basements, and an asphyxiation hazard could occur leading 
to serious injury or death.

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety 
against leakage according to local regulations or stan-
dards. The following standards may be applicable if local 
regulations are not available.

The Split System, like other air conditioning systems, uses 
R410A as refrigerant. R410A itself is an entirely safe non-toxic, 
non-combustible refrigerant. Nevertheless care must be taken 
to ensure that air conditioning facilities are installed in a room 
which is suffi ciently large. This assures that the maximum 
concentration level of refrigerant gas is not exceeded, in the 
unlikely event of major leak in the system and this in accor-
dance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the 
maximum concentration of refrigerant is directly related to the 
humanly occupied space in to which it could leak.

The unit of measurement of the concentration is lb./ft³ ( the 
weight in lb. of the refrigerant gas in 1ft³ volume of the occu-
pied space).

Compliance to the local applicable regulations and standards 
for the maximum allowable concentration level is required.

Direction of the refrigerant flow

Room where 
refrigerant leak 
has occurred 
(outflow of all the 
refrigerant from 
the system)

01_EN_3P281953-2A.indd   17

01_EN_3P281953-2A.indd   17

1/18/2011   9:27:30 AM

1/18/2011   9:27:30 AM

Summary of Contents for RZQ18PVJU (9)

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...e area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the...

Page 3: ...th s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping...

Page 4: ...JU RZR18PVJU RZQ24PVJU RZR24PVJU RZQ30PVJU RZR30PVJU Precaution Refrigerant R410A Power 208 230V 60Hz FAQ Wall mounted Cooling MBh 18 0 24 0 a Heating MBh RZQ only 20 0 26 0 b FCQ Ceiling mounted Cool...

Page 5: ...If strong wind whose velocity is 11 mph or more blows to the outdoor unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the...

Page 6: ...space for wiring with conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 Whe...

Page 7: ...let side is higher than the outdoor unit There is no restriction in the height of obstruction on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 L 4 o...

Page 8: ...ensional relationship between H L and A is as shown in the table below L A 0 L 1 2H 10 1 2H L H 12 When an obstruction is present also in the upward area When one outdoor unit is installed individuall...

Page 9: ...L 1 2H 10 1 2H L H 12 H L Installation is not allowed CAUTIONS ON INSTALLATION 5 Before installation confirm the strength and levelness of the foundation so that vibrations and noise are not generated...

Page 10: ...Protect the piping to prevent moisture and dusts from com ing into the piping Especially pay attention when passing the piping through a hole or connecting the end of piping to the outdoor Location W...

Page 11: ...er action such as caulking the connection area Measures to prevent invasion of small creatures and litter Block all gaps in the piping penetration areas with putty or heat insulating material arranged...

Page 12: ...refrigerant calculated by the formula below Additional charging amount Liquid piping length 0 036 Additional charging depended on type of indoor unit lb ft 0 036 A lb Indoor unit FAQ FCQ FHQ FTQ Addi...

Page 13: ...When the valve stem cannot be turned any more stop 2 turning Now the valve is open How to close the stop valve Insert a hexagon wrench into the valve stem and turn the 1 valve stem clockwise When the...

Page 14: ...smission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring or the transmission wiring through the included insulating t...

Page 15: ...ss cannot be connected to the power terminal block Slack in the electric wires may generate abnormal heat Use round pressure terminals with insulting sleeve for connection to the power terminal block...

Page 16: ...RANT PIPING WORK Piping size and heat insulation 5 Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping Check of stop valve 6 Confirm that the stop valve is open on both the liquid...

Page 17: ...ation the status under execution is indicated on the remote controller 6 After the check operation make sure to close the front panel of the outdoor unit Cautions on check operation If the air conditi...

Page 18: ...g UH The transmission wiring is not connected correctly Connect correctly the transmission wiring to the F1 and F2 TO IN D UNIT terminals on the PC board A1P in the outdoor unit When nothing is displa...

Page 19: ...al amount of refrigerant lb in the system NOTE Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separat...

Page 20: ...3P281953 2A EM08A096D 1102 HT 00_CV_3P281953 2A indd 2 00_CV_3P281953 2A indd 2 1 20 2011 1 24 16 PM 1 20 2011 1 24 16 PM...

Reviews: