background image

English 

16

In the check operation, the status of the outdoor unit is 

• 

checked, and incorrect wiring is checked for.

(1) •  Close the front panel 

of the outdoor unit.

 

•  Turn ON the power to 

the outdoor unit and 
indoor unit.

 

Caution

Make sure to turn on the 
power 6 hours before 
starting operation for 
supplying the power to 
the crankcase heater.

(2) •  Open the front panel of the outdoor unit.

 

•  Check the LED on the PC board (A1P 

and A2P) in the outdoor unit to see if the 
data transmission is performed normally.

Outdoor 

unit installed 

H1P

H5P

H4P

H6P

H7P

H2P

H3P

HAP

Blinking

ON

OFF

LED display:

LED display 
(Default 
status 
before 
delivery)

A1P

A2P

SER

VICE MONIT

OR

MODE

IND

SLA

VE

MASTER

TEST/HWL

L.N.O

.P

.

DEMAND

The power is 
supplied to the 
outdoor unit.
Take due care 
during the work to 
prevent electric 
shock.

(3) •  When performing the 

low-noise operation 
(L.N.O.P.) or demand 
(DEMAND) operation 
upon request from the 
customer, perform the 
setting using the 
pushbutton switches (BS1 
to BS5) on the PC board 
(A2P) in the outdoor unit.

 

•  Press each pushbut-

ton switch from the 
opening of the 
insulation cover. 
(Do not remove the 
insulation cover.)

The power is supplied to the 

 

outdoor unit. Take due care during 
the work to prevent electric shock.
Before using the pushbutton 

 

switches (BS1 to BS5) for setting, 
confi rm that the microcomputer 
(SERVICE) monitor is lit.
For the setting method, refer to the 

 

[Cautions on service] label attached 
on the back of the front panel of the 
outdoor unit. (Make sure to write the 
contents of setting on the [Cautions 
on service] label.)

(4)  Confi rm that the stop 

valves are open on both 
the liquid and gas lines. If 
they are closed, open them.

 

Caution

Do not leave any stop 
valve closed.
Otherwise the 
compressor will fail.

(5)  Press and hold the test 

run button (BS4) for 
5 seconds or more to start 
the check operation.
For the details, refer to the 

Check operation procedure

 

on the [Cautions on 
service] label.

When leaving the outdoor unit 

 

during the check operation for 
unavoidable reasons, ask another 
installation worker to watch the 
outdoor unit, or close the front panel.
The system operates the check 

 

operation for about 15 minutes 
(30 minutes maximum), then stops 
automatically.
The system can start normal operation 
about 5 minutes after the check 
operation if the remote controller does 
not display any malfunction code.
During the check operation, the 

 

status under execution is indicated 
on the remote controller.

(6)  After the check operation, make sure to close the front panel of 

the outdoor unit.

<Cautions on check operation>

If the air conditioner is started within about 12 minutes after 

• 

the power of the indoor/outdoor unit is turned on, the H2P 
indicator lights and the compressor does not run.
Confi rm that the LED status is as shown in the table in (2) in  

9-1 Power on and check operation

” before starting the air 

conditioner.
The air conditioner may require about 10 minutes maximum 

• 

until it can start the compressor after start of operation.
This period of time is required to homogenize the refrigerant 
status, and does not indicate any failure.
The check operation does not provide any means of check-

• 

ing the indoor unit individually.  For that purpose, perform the 
normal operation using the remote controller after fi nishing 
the check operation.
The check operation is not available in any other mode such 

• 

as the recovery mode.
Before running a check on the unit, changing the indoor 

• 

remote controller settings might cause the error code “UF” to 
be displayed and prevent a proper check to be run.

Checks in normal operation

9-2 

After fi nishing the check operation, operate the air condi-

• 

tioner normally.
(Heating is not available if the outside air temperature is 
75 °F or more.  Refer to the operation manual  supplied 
together with the unit.) (Heating is only available for RZQ-P 
models.)
Confi rm that the indoor and outdoor units are operating 

• 

normally.
(If a knocking sound is heard in the liquid compression of 
the compressor, stop the air conditioner immediately and 
energize the crankcase heater for a suffi cient period of time, 
then start the operation again.)
Check to see if cold (or hot) air is coming out of the indoor 

• 

unit.
Press the fan direction button and fan speed control button 

• 

on the remote controller to see if the fan is operating nor-
mally.

<Cautions for normal operation check>

Once stopped, the compressor will not start for about 

• 

5 minutes even if the “

ON/OFF

”  button on the remote con-

troller is pressed.
When the system operation is stopped by the remote con-

• 

trol, the outdoor unit may continue to operate for a further 
3 minutes.
If the system has not undergone the check operation by the 

• 

test run button since it was fi rst installed, a malfunction code 
“U3” is displayed.
In this case, perform the check operation by referring to 

9-1 Power on and check operation

”.

01_EN_3P281953-2A.indd   16

01_EN_3P281953-2A.indd   16

1/18/2011   9:27:29 AM

1/18/2011   9:27:29 AM

Summary of Contents for RZQ18PVJU (9)

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...e area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the...

Page 3: ...th s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping...

Page 4: ...JU RZR18PVJU RZQ24PVJU RZR24PVJU RZQ30PVJU RZR30PVJU Precaution Refrigerant R410A Power 208 230V 60Hz FAQ Wall mounted Cooling MBh 18 0 24 0 a Heating MBh RZQ only 20 0 26 0 b FCQ Ceiling mounted Cool...

Page 5: ...If strong wind whose velocity is 11 mph or more blows to the outdoor unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the...

Page 6: ...space for wiring with conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 Whe...

Page 7: ...let side is higher than the outdoor unit There is no restriction in the height of obstruction on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 L 4 o...

Page 8: ...ensional relationship between H L and A is as shown in the table below L A 0 L 1 2H 10 1 2H L H 12 When an obstruction is present also in the upward area When one outdoor unit is installed individuall...

Page 9: ...L 1 2H 10 1 2H L H 12 H L Installation is not allowed CAUTIONS ON INSTALLATION 5 Before installation confirm the strength and levelness of the foundation so that vibrations and noise are not generated...

Page 10: ...Protect the piping to prevent moisture and dusts from com ing into the piping Especially pay attention when passing the piping through a hole or connecting the end of piping to the outdoor Location W...

Page 11: ...er action such as caulking the connection area Measures to prevent invasion of small creatures and litter Block all gaps in the piping penetration areas with putty or heat insulating material arranged...

Page 12: ...refrigerant calculated by the formula below Additional charging amount Liquid piping length 0 036 Additional charging depended on type of indoor unit lb ft 0 036 A lb Indoor unit FAQ FCQ FHQ FTQ Addi...

Page 13: ...When the valve stem cannot be turned any more stop 2 turning Now the valve is open How to close the stop valve Insert a hexagon wrench into the valve stem and turn the 1 valve stem clockwise When the...

Page 14: ...smission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring or the transmission wiring through the included insulating t...

Page 15: ...ss cannot be connected to the power terminal block Slack in the electric wires may generate abnormal heat Use round pressure terminals with insulting sleeve for connection to the power terminal block...

Page 16: ...RANT PIPING WORK Piping size and heat insulation 5 Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping Check of stop valve 6 Confirm that the stop valve is open on both the liquid...

Page 17: ...ation the status under execution is indicated on the remote controller 6 After the check operation make sure to close the front panel of the outdoor unit Cautions on check operation If the air conditi...

Page 18: ...g UH The transmission wiring is not connected correctly Connect correctly the transmission wiring to the F1 and F2 TO IN D UNIT terminals on the PC board A1P in the outdoor unit When nothing is displa...

Page 19: ...al amount of refrigerant lb in the system NOTE Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separat...

Page 20: ...3P281953 2A EM08A096D 1102 HT 00_CV_3P281953 2A indd 2 00_CV_3P281953 2A indd 2 1 20 2011 1 24 16 PM 1 20 2011 1 24 16 PM...

Reviews: