background image

15 

English

Transmission wiring connection procedure

7-4 

If an excessive force is applied while connecting a cable 

 

to the terminal block on the PC board, the PC board may 
be damaged.

IN/D

OUT/D

F1 F2 F1 F2

L1

L2

F

1

IN/D

OUT/D

F

2

F

1

F

2

F1   F2

Use the conductor 

of sheathed wire 

(2 wire) (no polarity)

Indoor unit

 CAUTION

For low-noise operation, it is necessary to install the optional 

• 

“External control adaptor for outdoor unit”.
For details, see the installation manual attached to the 
adaptor.

Caution on the wiring length between units

Make sure to observe the restrictions below.  If they are 
not observed, transmission error may occur.

Maximum wiring length: 3280 ft.

Cautions on the wiring between units

Never connect 208/230V to the terminal block for the trans-

• 

mission wiring.
Doing so will break the entire system.
The transmission wiring from the indoor unit must be con-

• 

nected to the F1/F2 (TO IN/D UNIT) terminals on the PC 
board in the outdoor unit.

 Make sure to use sheathed two-core cables of AWG18-16 in 

the wiring shown above.

 

All cables used in the wiring between the units should 
be procured on the site.

CHECKS AFTER COMPLETION OF 

8. 

WORK

After completing the work, make sure to confi rm the 
following items:

Connection of drain piping and removal of transport fi ttings:

1. 

Refer to “

5. CAUTIONS ON INSTALLATION

”.

Connection of power supply wiring and tightening of screws:

2. 

Refer to “

7-3 Power supply wiring connection proce-

dure

”.

Connection of transmission wiring and tightening of screws:

3. 

Refer to “

7-4 Transmission wiring connection proce-

dure

”.

Freezing connection of refrigerant piping

4. 

Refer to “

6. REFRIGERANT PIPING WORK

”.

Piping size and heat insulation:

5. 

Refer to “

6-1 Selection of piping material

”, “

6-5 Heat 

insulation of piping

”.

Check of stop valve:

6. 

Confi rm that the stop valve is open on both the liquid line 
and gas line.
Record of amount of additional refrigerant:

7. 

Record the amount on the label stuck on the back of the 
front panel.
Measurement of insulation in main power circuit:

8. 

Use the megatester for 500 V.

• 

Do not use any megatester for low voltage electric circuits 

• 

except 230 V.
(Wiring between the outdoor unit and the indoor unit)

 CAUTION

<To piping technician>

Make sure to open the stop valve after fi nishing the piping 

• 

work.
(Operating the air conditioner with the stop valve shut may 
damage the compressor.)

TEST RUN PROCEDURE

9. 

A crankcase heater is mounted for smooth startup.  Make 
sure to turn on the power 6 hours before starting opera-
tion for supplying the power to the crankcase heater.

 WARNING

Make sure to close the front panel before leaving the 

• 

outdoor unit in the power ON status.
To avoid injury, always make sure that the overcurrent 

• 

protective device on the power supply panel of the installa-
tion is switched off before doing any work.

Cautions before turning on the power

Put the insulating cover securely onto the control box.

 

After turning on the power, check the settings and LED 

 

indicators on the PC board (A1P) in the outdoor unit 
through the opening of the insulating cover.

Power on and check operation

9-1 

Make sure to perform the check operation after installation. 

• 

(If the air conditioner is operated using the indoor remote 
controller without performing the check operation, the mal-
function code “U3” is displayed in the indoor remote control-
ler, and normal operation is disabled.)

01_EN_3P281953-2A.indd   15

01_EN_3P281953-2A.indd   15

1/18/2011   9:27:28 AM

1/18/2011   9:27:28 AM

Summary of Contents for RZQ18PVJU (9)

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...e area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the...

Page 3: ...th s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping...

Page 4: ...JU RZR18PVJU RZQ24PVJU RZR24PVJU RZQ30PVJU RZR30PVJU Precaution Refrigerant R410A Power 208 230V 60Hz FAQ Wall mounted Cooling MBh 18 0 24 0 a Heating MBh RZQ only 20 0 26 0 b FCQ Ceiling mounted Cool...

Page 5: ...If strong wind whose velocity is 11 mph or more blows to the outdoor unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the...

Page 6: ...space for wiring with conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 Whe...

Page 7: ...let side is higher than the outdoor unit There is no restriction in the height of obstruction on the air inlet side When the upward area is open When one outdoor unit is installed individually 1 L 4 o...

Page 8: ...ensional relationship between H L and A is as shown in the table below L A 0 L 1 2H 10 1 2H L H 12 When an obstruction is present also in the upward area When one outdoor unit is installed individuall...

Page 9: ...L 1 2H 10 1 2H L H 12 H L Installation is not allowed CAUTIONS ON INSTALLATION 5 Before installation confirm the strength and levelness of the foundation so that vibrations and noise are not generated...

Page 10: ...Protect the piping to prevent moisture and dusts from com ing into the piping Especially pay attention when passing the piping through a hole or connecting the end of piping to the outdoor Location W...

Page 11: ...er action such as caulking the connection area Measures to prevent invasion of small creatures and litter Block all gaps in the piping penetration areas with putty or heat insulating material arranged...

Page 12: ...refrigerant calculated by the formula below Additional charging amount Liquid piping length 0 036 Additional charging depended on type of indoor unit lb ft 0 036 A lb Indoor unit FAQ FCQ FHQ FTQ Addi...

Page 13: ...When the valve stem cannot be turned any more stop 2 turning Now the valve is open How to close the stop valve Insert a hexagon wrench into the valve stem and turn the 1 valve stem clockwise When the...

Page 14: ...smission wiring with a conduit pass through another knockout hole For protection from uninsulated live parts thread the power supply wiring or the transmission wiring through the included insulating t...

Page 15: ...ss cannot be connected to the power terminal block Slack in the electric wires may generate abnormal heat Use round pressure terminals with insulting sleeve for connection to the power terminal block...

Page 16: ...RANT PIPING WORK Piping size and heat insulation 5 Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping Check of stop valve 6 Confirm that the stop valve is open on both the liquid...

Page 17: ...ation the status under execution is indicated on the remote controller 6 After the check operation make sure to close the front panel of the outdoor unit Cautions on check operation If the air conditi...

Page 18: ...g UH The transmission wiring is not connected correctly Connect correctly the transmission wiring to the F1 and F2 TO IN D UNIT terminals on the PC board A1P in the outdoor unit When nothing is displa...

Page 19: ...al amount of refrigerant lb in the system NOTE Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separat...

Page 20: ...3P281953 2A EM08A096D 1102 HT 00_CV_3P281953 2A indd 2 00_CV_3P281953 2A indd 2 1 20 2011 1 24 16 PM 1 20 2011 1 24 16 PM...

Reviews: