Installation manual

13

RZQ71~12 RZQ100~140B8W1B

Split System air conditioners

4PW23691-1A

Specifications of standard wiring components

T

EST

 

OPERATION

Pre-run checks

Be sure to perform a test run.

Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will
break down.

Be sure to execute the first test run of the installation in cooling
mode operation.

Never leave the unit unattended with an open front panel during
test run.

Test run

1

Be sure to turn power on at least 6 hours before starting
operation in order to protect the compressor.

2

Make sure the liquid and gas shut-off valves are open.

3

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.

4

Be sure to set the unit to cooling operation mode.

5

Press the inspection/test operation button of the remote
controller 4 times (2 times in case of a wireless remote
controller) to go into the test run mode.

6

Press the ON/OFF button within 10 seconds to start the test run
and check the operation status for about 6 minutes. The
refrigerant pressure may not rise immediately, even if the shut-
off valve is opened after an air purge is performed using a
vacuum pump. This is because the indoor unit refrigerant piping
is closed off with electric valves inside. This will not create any
problems during operation.

7

Push the air flow direction adjust button and check if the unit is
responding to the new air flow direction position.

8

Press the inspection/test operation button of the remote
controller 2 times to go into check mode and to make sure that
the malfunction code displays 

00

  (=normal). In case the

malfunction code does not display 

00

, refer to 

"Failure

diagnosis at the moment of first installation" on page 14

.

9

If the inspection/test operation button is pressed 4 times during
a test run, the unit returns to normal operation.

10

Check all functions according to the operation manual.

Precautions regarding test-runs

1

In order to detect stop valves failing to open, operation of the
unit is compulsorily performed in cooling for 2-3 minutes during
the first test run, even if the remote controller was set to heating
operation. In this case, the remote controller will have kept
displaying the heating symbol all the time and the unit will switch
to heating operation automatically after elapse of that time.

2

In case you cannot operate the unit in test run mode for any
unusual reason, refer to 

"Failure diagnosis at the moment of first

installation" on page 14

.

3

In case you cannot operate the unit in test run mode, the unit
usually returns to its normal state after 30 minutes.

4

In case of a wireless remote controller, execute the test run only after
having installed the indoor unit decoration panel with infra-red
receiver first.

5

In case the panels of indoor units are not yet installed to the
indoor units, make sure to shut off the power supply after
finishing the complete test run.

6

A complete test run surely includes shutting off power after
having performed a normal operation stop on the remote
controller. Do not stop operation by turning circuit breakers off.

RZQ71

125V3

RZQ100~140W1

Minimum circuit 
amps (MCA)

(a)

(a) Stated values are maximum values (see electrical data of combination with 

indoor units for exact values).

17.7

28.2

17.7

Recommended 
field fuse

20 A

32

 

A

20

 

A

Wire type

(b)

(b) Only in protected pipes, use H07RN-F when protected pipes are not used.

H05VV-U3G

H05VV-U5G

Size

Wiring size must comply with the applicable local 

and national code

Wire type of 
wiring between 
the units

H05VV-U4G2.5

NOTE

The earth leakage breaker must be a high-speed type
breaker of 30 mA (<0.1 s).

WARNING

Live parts can be easily touched by accident.

Never leave the unit unattended during installation or
servicing when the service panel is removed.

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly grounded?

Is the wiring between units connected in series
correct?

Are any of the wiring attachment screws loose?

Is the insulation resistance at least 1 M

?

-

Use a 500 V mega-tester when measuring 
insulation.

-

Do not use a mega-tester for low-voltage 
circuits.

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the shut-off valves for both the liquid side and
the gas side open?

Extra refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

 Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Summary of Contents for RZQ100B9V3B

Page 1: ...INSTALLATION MANUAL RZQ71B9V3B RZQ100B9V3B RZQ125B9V3B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B...

Page 3: ...ea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...be according to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition o...

Page 6: ...ation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...f piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidden to discharge refrige...

Page 9: ...y refrigerant gas leaks while working on the unit ventilate the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold...

Page 10: ...If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be re used but...

Page 11: ...areful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as sh...

Page 12: ...sed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increase fo...

Page 13: ...kg Example 1 1 G1 L1 35 m G2 L2 L3 7 5 12 2 Over 30 m a G1 30 5 m 9 5 R1 0 5 kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54...

Page 14: ...h clamping material as shown in the figure below so that it does not come in contact with the piping particulary on the high pressure side Make sure no external pressure is applied to the terminal con...

Page 15: ...overheating When connecting wires of the same gauge connect them according to the below figure Use the correct screwdriver to tighten the terminal screws Small screwdrivers can damage the screw head...

Page 16: ...bol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unusual reason refer to Failure di...

Page 17: ...he product in case of an abnormality when the product is started up When the reversed phase protection circuit forced the unit to stop check if all phases are existing If this is the case shut off the...

Page 18: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23691 1A...

Reviews: