5 Preparation
Installer reference guide
10
RZASG71~Y1
Sky Air Advance-series
4P486047-1 – 2017.04
Refrigerant piping length and height difference
The piping lengths and height differences must comply with the following requirements:
Requirement
Limit
71+100
125+140
1 Minimum total one‑way piping length
Pair: Limit≤L1
Twin: Limit≤L1+L3
Triple: Limit≤L1+L4
Double twin: Limit≤L1+L3+L7
5 m
2 Maximum total one‑way piping length
Pair: L1≤Limit
50 m (70 m)
(a)
Twin and triple: L1+L2≤Limit
Double twin: L1+L2+L4≤Limit
50 m (70 m)
(a)
3 Maximum allowable piping length
Pair: N/A
—
Twin: L1+L2+L3≤Limit
50 m
Triple: L1+L2+L3+L4≤Limit
50 m
Double twin: L1+L2+L3+L4+L5+L6+L7≤Limit
—
50 m
4 Maximum branch piping length
Pair: N/A
Twin and triple: L2≤Limit
Double twin: L2+L4≤Limit
20 m
5 Maximum difference between branch lengths
Pair: N/A
—
Twin: L2–L3≤Limit
10 m
Triple: L2–L4≤Limit
10 m
Double twin:
▪ L2–L3≤Limit
▪ L4–L5≤Limit
▪ L6–L7≤Limit
▪ (L2+L4)–(L3+L7)≤Limit
—
10 m
6 Maximum height between indoor and outdoor
Pair, twin, triple and double twin: H1≤Limit
30 m
7 Maximum height between indoors
Pair: N/A
Twin, triple and double twin: H2≤Limit
0.5 m
(a)
Parenthesised figure represents the equivalent length.
Example
If the system layout is as follows…
Then the requirements are…
▪ RZASG125
▪ Triple:
L2
L3
L4
H1
H2
L1
▪ Ø standard
1
5 m≤L1+L4
2
L1+L2≤50 m (70 m)
3
L1+L2+L3+L4≤50 m
4
L2≤20 m
5
L2–L4≤10 m
6
H1≤30 m
7
H2≤0.5 m
5.3.2
Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Ambient
temperature
Humidity
Minimum thickness
≤30°C
75% to 80% RH
15 mm
>30°C
≥80% RH
20 mm
5.4
Preparing electrical wiring
5.4.1
About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
INFORMATION
Also read
"6.7.5 Specifications of standard wiring
.