5 Preparation

Installer reference guide

8

RZASG71~Y1

Sky Air Advance-series

4P486047-1 – 2017.04

NOTICE

The  equipment  described  in  this  manual  may  cause
electronic  noise  generated  from  radio-frequency  energy.
The  equipment  complies  to  specifications  that  are
designed  to  provide  reasonable  protection  against  such
interference.  However,  there  is  no  guarantee  that
interference will not occur in a particular installation.

It  is  therefore  recommended  to  install  the  equipment  and
electric  wires  keeping  proper  distances  away  from  stereo
equipment, personal computers, etc.

b

a

c

d

f e

(mm)

1500

1500

1000

1000

1000

1000

a

Earth leakage protector

b

Fuse

c

Outdoor unit

d

Indoor unit

e

User interface

f

Personal computer or radio

In  places  with  weak  reception,  keep  distances  of  3  m  or  more  to
avoid  electromagnetic  disturbance  of  other  equipment  and  use
conduit tubes for power and transmission lines.

▪ Select a place where rain can be avoided as much as possible.

▪ Take  care  that  in  the  event  of  a  water  leak,  water  cannot  cause

any damage to the installation space and surroundings.

▪ Choose a location where the hot/cold air discharged from the unit

or the operation noise, will NOT disturb anyone.

▪ Heat  exchanger  fins  are  sharp  and  injury  is  possible.  Choose  an

installation  location  where  there  is  no  risk  for  injury  (especially  in
areas where children play).

Do NOT install the unit in the following places:

▪ Sound  sensitive  areas  (e.g.  near  a  bedroom),  so  that  the

operation noise will cause no trouble.
Note:  If  the  sound  is  measured  under  actual  installation
conditions,  the  measured  value  might  be  higher  than  the  sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

It  is  NOT  recommended  to  install  the  unit  in  the  following  places
because it may shorten the life of the unit:

▪ Where the voltage fluctuates a lot

▪ In vehicles or vessels

▪ Where acidic or alkaline vapour is present

Seaside  installation.

  Make  sure  the  outdoor  unit  is  NOT  directly

exposed  to  sea  winds.  This  is  to  prevent  corrosion  caused  by  high
levels of salt in the air, which might shorten the life of the unit.

Install the outdoor unit away from direct sea winds.

Example: 

Behind the building.

b

c

a

If the outdoor unit is exposed to direct sea winds, install a
windbreaker.

▪ Height of windbreaker≥1.5×height of outdoor unit

▪ Mind  the  service  space  requirements  when  installing  the

windbreaker.

a

b

c

d

c

d

a

Sea wind

b

Building

c

Outdoor unit

d

Windbreaker

Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet
causes short circuit (suction of discharge air). This may result in:

▪ deterioration of the operational capacity;

▪ frequent frost acceleration in heating operation;

▪ disruption  of  operation  due  to  decrease  of  low  pressure  or

increase of high pressure;

▪ a  broken  fan  (if  a  strong  wind  blows  continuously  on  the  fan,  it

may start rotating very fast, until it breaks).

It  is  recommended  to  install  a  baffle  plate  when  the  air  outlet  is
exposed to wind.

It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.

a

b

c

b

a

Baffle plate

b

Prevailing wind direction

c

Air outlet

Summary of Contents for RZASG100M7V1B

Page 1: ...nstaller reference guide Sky Air Advance series English Installer reference guide Sky Air Advance series RZASG71M2V1B RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B RZASG100M7Y1B RZASG125M7Y1B RZASG140M7Y1...

Page 2: ...recautions when checking the refrigerant piping 16 6 5 3 Checking refrigerant piping Setup 16 6 5 4 To check for leaks 16 6 5 5 To perform vacuum drying 17 6 6 Charging refrigerant 17 6 6 1 About char...

Page 3: ...OT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it...

Page 4: ...ake sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It state...

Page 5: ...earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when layi...

Page 6: ...do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenance and service Ho...

Page 7: ...n manual of the refrigerant branch kit Demand adaptor kit SB KRP58M52 Includes the additional mounting plate EKMKSA2 Can be used for the following Low noise To lower the operation sound of the outdoor...

Page 8: ...ght be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA In pl...

Page 9: ...rresponds with the actual highest unit L1 Main piping L2 L7 Branch piping H1 Height difference between the highest indoor unit and the outdoor unit H2 Height difference between the highest and the low...

Page 10: ...win L2 L3 Limit L4 L5 Limit L6 L7 Limit L2 L4 L3 L7 Limit 10 m 6 Maximum height between indoor and outdoor Pair twin triple and double twin H1 Limit 30 m 7 Maximum height between indoors Pair N A Twin...

Page 11: ...ing Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFORMATION For installation of the indoor unit mounting the indoor unit...

Page 12: ...e unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration INFORMATION If necessary you can use a drain plug kit field supply to...

Page 13: ...thing but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used f...

Page 14: ...d film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough...

Page 15: ...oor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Do the following Remove the service cover a with screw b Remove the p...

Page 16: ...ists of the following stages 1 Checking for leaks in the refrigerant piping 2 Performing vacuum drying to remove all moisture air or nitrogen from the refrigerant piping If there is a possibility of m...

Page 17: ...it is factory charged with refrigerant but in some cases the following might be necessary What When Charging additional refrigerant When the total liquid piping length is more than specified see later...

Page 18: ...ak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating dev...

Page 19: ...ins fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant always use protective gloves and safety glasses CAU...

Page 20: ...frigerant charge in the system expressed as tonnes CO2 equivalent is used to determine the maintenance intervals Follow the applicable legislation Formula to calculate the greenhouse gas emissions GWP...

Page 21: ...ble legislation Interconnection cables Minimum cable section of 2 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 32 A 16 A 20 A Earth leakage circuit breaker Must comply with applicabl...

Page 22: ...e frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tub...

Page 23: ...eat up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor mig...

Page 24: ...vice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start th...

Page 25: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 26: ...y for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically consists of the following stages 1 Pumping down the system 2 Bringing the system to a speci...

Page 27: ...row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 250 100 100 B E 100 1000 500 A B C E 250 150 150 1000 500 D 500 D E 500 1000 500 B D 100 500 B D E 1 2 1 HB HD HB HU 25...

Page 28: ...e upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units...

Page 29: ...ctive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Lege...

Page 30: ...licable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cer...

Page 31: ......

Page 32: ...4P486047 1 2017 04 Copyright 2017 Daikin...

Reviews: