3
2
• Split - Sky Air • RZAG-LV1
3
• Outdoor Unit • RZAG-LV1
2
Specifications
2-1 Capacity and Power input
FCAHG71F/RZAG71LV1
FCAHG100F/
RZAG100LV1
FCAHG125F/
RZAG125LV1
FCAHG140F/
RZAG140LV1
Cooling capacity
Nom.
kW
6.8
9.5
12.0
13.4
Heating capacity
Nom.
kW
7.5
10.8
13.5
15.5
Power input
Cooling
Nom.
kW
1.66
2.15
3.00
4.00
Heating
Nom.
kW
1.56
2.16
3.07
3.77
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
A++
-
Pdesign
kW
6.80
9.50
12.00
-
SEER
7.35 (1)
6.94 (1)
-
Annual energy
consumption
kWh
324
452
605
-
A
Condition
(35°C -
27/19)
Pdc
kW
6.80
9.50
12.00
-
EERd
4.38
4.61
4.10
-
power
input
kW
1.55
2.06
2.93
-
B
Condition
(30°C -
27/19)
Pdc
kW
5.01
7.00
8.90
-
EERd
6.12
5.95
5.40
-
power
input
kW
0.82
1.18
1.65
-
C
Condition
(25°C -
27/19)
Pdc
kW
3.57
4.70
5.80
-
EERd
9.30
8.25
8.40
-
power
input
kW
0.38
0.57
0.69
-
D
Condition
(20°C -
27/19)
Pdc
kW
3.38
3.60
2.60
-
EERd
12.10
13.15
9.80
-
power
input
kW
0.28
0.27
-
Heating (Average
climate)
Energy label
A+
A++
-
Pdesign
kW
5.65
9.13
9.52
-
SCOP/A
4.54 (1)
4.64 (1)
4.63 (1)
-
SCOPnet/A
4.55
4.67
4.64
-
Pdh Heating capacity at -10°
5
8
9
-
Annual energy
consumption
kWh
1,743
2,753
2,879
-
Required back up
heating cap at design
conditions
kW
0.21
0.86
0.21
-
TOL
Tol
(temperat
ure
operating
limit)
°C
-15
-
Pdh
(declared
heating
cap)
kW
6.19
8.60
10.80
-
COPd (declared
COP)
2.05
2.11
1.87
-
Power
input
kW
3.02
4.07
5.78
-
Summary of Contents for RZAG-LV1
Page 1: ...Air Conditioning Technical Data RZAG LV1...
Page 2: ......
Page 36: ...Outdoor Unit RZAG LV1 12 Split Sky Air RZAG LV1 34 12 Installation 12 1 Installation Method...
Page 37: ...3 12 Split Sky Air RZAG LV1 35 Outdoor Unit RZAG LV1 12 Installation 12 1 Installation Method...
Page 38: ...Outdoor Unit RZAG LV1 13 Split Sky Air RZAG LV1 36 13 Operation range 13 1 Operation Range...