3
2
• Split - Sky Air • RZAG-LV1
5
• Outdoor Unit • RZAG-LV1
2
Specifications
Notes
(1) EER/COP according to Eurovent 2012, for use outside EU only
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Annual energy consumption is according to Energy labeling directive 2002/31/EC
SEER and SCOP are according to EN 14825
Nominal efficiency
EER
4.09
4.42
4.00
3.35
COP
4.80
4.99
4.40
4.12
Annual energy consumption
kWh
830
1,075
1,500
2,000
Energy label
Cooling
A
Heating
A
2-2 Technical Specifications
RZAG71LV1
RZAG100LV1
RZAG125LV1
RZAG140LV1
Capacity control
Method
Inverter controlled
Casing
Colour
Ivory white
Material
Painted galvanized steel plate
Dimensions
Unit
Height
mm
990
1,430
Width
mm
940
Depth
mm
320
Packed unit
Height
mm
1,170
1,610
Width
mm
1,015
Depth
mm
422
Weight
Unit
kg
67
93
Packed unit
kg
79
105
Packing
Weight
kg
12
Heat exchanger
Fin
Type
WF fin
Treatment
Anti-corrosion treatment (PE)
Compressor
Quantity
1
Type
Hermetically sealed swing compressor
Starting method
Inverter driven
Fan
Type
Propeller
Discharge direction
Horizontal
Quantity
1
2
Air flow rate
Cooling Nom.
m³/min
59
70
Super
low
m³/min
-
cfm
-
Heating Nom.
m³/min
49
62
Super
low
m³/min
-
cfm
-
Fan motor
Quantity
1
2
Model
Brushless DC motor
Output
W
94
Drive
Direct drive
Speed
Cooling Super
low
rpm
-
Heating Super
low
rpm
-
Sound power level
Cooling
dBA
64
66
67
Heating
dBA
-
Sound pressure level
Cooling
Nom.
dBA
48
49
51
52
Heating
Nom.
dBA
50
51
52
Night quiet mode
Level 1
dBA
43
45
Operation range
Cooling
Ambien
t
Min.
°CDB
-15
Max.
°CDB
50
Heating
Ambien
t
Min.
°CWB
-20
Max.
°CWB
15.5
2-1 Capacity and Power input
FCAHG71F/RZAG71LV1
FCAHG100F/
RZAG100LV1
FCAHG125F/
RZAG125LV1
FCAHG140F/
RZAG140LV1
Summary of Contents for RZAG-LV1
Page 1: ...Air Conditioning Technical Data RZAG LV1...
Page 2: ......
Page 36: ...Outdoor Unit RZAG LV1 12 Split Sky Air RZAG LV1 34 12 Installation 12 1 Installation Method...
Page 37: ...3 12 Split Sky Air RZAG LV1 35 Outdoor Unit RZAG LV1 12 Installation 12 1 Installation Method...
Page 38: ...Outdoor Unit RZAG LV1 13 Split Sky Air RZAG LV1 36 13 Operation range 13 1 Operation Range...