background image

5

I

NTERNAL

 

WIRING

 - 

PARTS

 

TABLE

Refer to the wiring diagram on the unit.

The abbreviations used are listed below.

Note 

Use copper conductors only.
Do not operate the unit by short-circuiting S1LP.

:Field wiring

L

:Live

N

:Neutral
:Terminal
:Connector
:Wire clamp

:Protective earth (Screw)

BLK

:Black

BLU

:Blue

RED

:Red

WHT

:White

YLW

:Yellow

A1P, A2P ........ Printed circuit board

BS1 ................. Push button (Forced defrost - Pump down)

C1R,C2R ......... Capacitor (M1F-M2F)

DS1 ................ Selector switch (Defrost)

F1C ................. Over-current relay

F1U, F2U ......... Fuse (250V, 10A)

F3U ................. Field fuse

HAP ................ Light emitting diode (Service monitor - GREEN)

H1P, H2P ........ Light emitting diode (Service monitor - RED)

J1HC ............... Cranckcase heater

K1M ................ Magnetic contactor (M1C)

L1 ................... Red

L2 ................... White

L3 ................... Black

M1C ................ Motor (Compressor)

M1F, M2F ....... Motor (Fan)

N ..................... Blue

PRC ................ Phase reverse circuit

Q1L, Q2L, Q3L Thermo switch (M1F-M2F-M1C)

Q3E ................. Earth leak detector

R1T ................. Thermistor (Air)

R2T ................. Thermistor (Coil)

RC .................. Signal receiver circuit

RyC ................. Magnetic relay (K1M)

RyF1~2 ........... Magnetic relay (M1F-M2F)

RyS ................. Magnetic relay (Y1R)

S1LP ............... Pressure switch (Low)

S1PH .............. Pressure switch (High)

S2PH .............. Pressure switch (High-control)

SD .................. Safety devices input

SS1 ................. Selector switch (Emergency)

T1R ................. Transformer (220-240V/16V)

TC ................... Signal transmission circuit

X1M ................ Terminal strip

Y1R ................ 4 way valve

W

IRING

 

OF

 

POWER

 

SUPPLY

 

AND

 

THE

 

UNITS

Refer to the installation manual supplied with the indoor unit for
wiring of indoor units.

Install an earth leak detector and fuse in the power supply line.

P

AIR

 

SYSTEM

 

(R

EFER

 

TO

 

FIGURE

 6)

1. Outdoor unit
2. Indoor unit
3. Earth leak detector
4. Fuse
5. Remote controller

S

IMULTANEOUS

 

OPERATION

 

SYSTEM

 

(R

EFER

 

TO

 

FIGURE

 7)

1. Outdoor unit
2. Indoor unit (Master)
3. Indoor unit (Slave)
4. Earth leak detector
5. Fuse
6. Remote controller

T

EST

 

OPERATION

For the test run procedure, refer to the indoor unit installation
manual.

P

UMP

-

DOWN

 

OPERATION

The outdoor unit is equipped with a low-pressure switch to protect
the compressor. Take the following steps to perform the pumping-
down operation.

Caution

Never short-circuit the low-pressure switch in this operation.

1. Start the fan operation with the remote controller.

Confirm that stop valves both on the liquid and gas side are open.

2. Push the pumping-down button on the PC board of the

outdoor unit.
Compressor and outdoor fan will start operation automatically.

3. Continue operation for 1 min. until operation condition stabilizes.
4. Close the stop valve on the liquid side securely.

Insecure closing of the valve may result in burning of the
compressor.

5. When the low-pressure switch is activated, the unit stops

working. At this time, close the stop valve on the gas side.

This is the end of pumping-down operation. After pumping-down
operation, the remote controller shows “U4” even when ON button
on the remote controller is pressed, and it will not operate. Turn off
the main power supply switch and turn it on again in need of
operation.

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local
and national regulations.

Summary of Contents for RY200F7W1

Page 1: ...Split System air conditioners INSTALLATION MANUAL R200F7W1 R250F7W1 RY200F7W1 RY250F7W1...

Page 2: ...overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer...

Page 3: ...50 B2 A 50 50 h H A B1 B2 100 100 20 20 mm R22 1 3 4 2 80 80 726 4x 15 1000 1 2 3 1 2 3 1 2 3 N L1 L2 L3 N L1 L2 L3 1 50 Hz 220 240V 3N 50 Hz 380 415V 1 50 Hz 220 240V 6 2 3 1 4 5 1 2 3 1 2 3 N N 1 5...

Page 4: ...g conditions are satisfied and that meets with your customer s approval 1 Places which are well ventilated 2 Places where the indoor and outdoor units piping and wiring lengths come within the allowab...

Page 5: ...tops oil will return to the discharge side of the compressor When starting the unit this can cause liquid oil hammer The oil circulation will decrease To solve these phenomena provide oil traps in the...

Page 6: ...kwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of the body 3 Tighten the cap firmly Note For tightening torques and dimensions of the flares refer to the table in the chapter Flar...

Page 7: ...ntire refrigerant pipe length is below 7 5 meters reduce the refrigerant amount charge mentioned in the nameplate as specified in the table R200 50 g m R250 90 g m RY200 100 g m RY250 170 g m Caution...

Page 8: ...PAIR SYSTEM REFER TO FIGURE 6 1 Outdoor unit 2 Indoor unit 3 Earth leak detector 4 Fuse 5 Remote controller SIMULTANEOUS OPERATION SYSTEM REFER TO FIGURE 7 1 Outdoor unit 2 Indoor unit Master 3 Indoor...

Page 9: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE05807 1C...

Reviews: