background image

2

4. The space around the unit is adequate for servicing and the

minimum space for air inlet and air outlet is available.
(Refer to figure 1 and choose one of both possibilities.)

5. There is no danger of fire due to leakage of flammable gas.
6. Ensure that water cannot cause any damage to the location in

case it drips out the unit (e.g. in case of a blocked drain pipe).

7. Select the location of the unit in such a way that neither the

discharged air nor the sound generated by the unit disturb
anyone.

P

RECAUTIONS

Do not install or operate the unit in sites mentioned below.

• Where mineral oil like cutting oil is present;
• Where the air contains high levels of salt;
• Where sulphurous gas exists such as at areas with hot springs;
• Where voltage fluctuates a lot;
• In vehicles or vessels;
• Where high concentrations of oil vapour or spray are present;
• Where machines generating excessive electromagnetic waves

are installed;

• Where acidic or alkaline vapour is present.

Caution

In heavy snowfall areas, select an installation site where snow
will not affect operation of the unit.

R

EFRIGERANT

 

PIPING

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and national
regulations.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

Refrigerant pipe size

1. Pair system (Refer to figure 5A)

2. Simultaneous operation system

Allowable pipe length

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

When the outdoor unit is installed below the indoor unit, the
following can occur:

• When the unit stops, oil will return to the discharge side of the

compressor. When starting the unit, this can cause liquid (oil)
hammer.

• The oil circulation will decrease.

To solve these phenomena, provide oil traps in the gas pipe every
15 m if the level difference (H) is more than 15 m.

H

3

2

5

4

1

Note 

If the outdoor unit is installed above the indoor unit, oil traps
are not necessary.

C

ONNECTING

 

THE

 

REFRIGERANT

 

PIPING

1. Installation of refrigerant piping is possible as front connection,

side connection and bottom connection.

1. Flange
2. Flare nut
3. Gas side attached pipe
4. Liquid side attached pipe
5. Brazing
6. Knock out hole (use a hammer)

• Twin and Triple operation system (Refer to figure 5B and 5C)

Caution

The pipes between the outdoor unit and the branch   should
have the same size as the outdoor connections.

The pipes between the branch   and the indoor units should
have the same size as the indoor connections.

• Double twin operation system (Refer to figure 5D)

1.  Outdoor unit
2.  Indoor unit
3.  Gas pipe
4.  Liquid pipe
5.  Oil trap

R(Y)250

Ø28.6

Ø12.7

Ø15.9

Ø25.4

R(Y)200

Gas

Liquid

Refrigerant pipe size

R(Y)250

Ø28.6

Ø12.7

Ø15.9

Ø25.4

R(Y)200

Gas

Liquid

Refrigerant pipe size

Ø19.1

Ø9.5

Ø9.5

Ø19.1

Gas

Liquid

Ø15.9

Ø6.4

Ø9.5

Ø12.7

Gas

Liquid

L1

L2 - L3

L4 - L5 - L6 - L7

double twin

 twin/triple

pair

50 m

-

-

-

-

-

-

-

-

30 m

-

-

-

50 m

50 m

-

-

20 m

20 m

-

-

10 m

10 m

-

10 m

-

10 m

-

0,5 m

-

-

L1

L1 + L2, L1 + L3, L1 + L4

L1 + L2 + L3

L2, L3, L4

L2 + L4

L1 - L2, L2 - L4, L3 - L4

(L2 + L4) - (L3 + L7)

L2 - L3

L4 - L5, L6 - L7

H1, H2, H3, H4, H5

H

max. allowable piping length

max. branch pipe length

max. difference between

branch lengths

max. difference between each

1st branch

max. difference between each

2nd branch

max. height difference between

indoor and outdoor

-

-

0,5 m

H1, H2, H3

30 m

30 m

max. height difference between

indoors

Summary of Contents for RY200F7W1

Page 1: ...Split System air conditioners INSTALLATION MANUAL R200F7W1 R250F7W1 RY200F7W1 RY250F7W1...

Page 2: ...overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer...

Page 3: ...50 B2 A 50 50 h H A B1 B2 100 100 20 20 mm R22 1 3 4 2 80 80 726 4x 15 1000 1 2 3 1 2 3 1 2 3 N L1 L2 L3 N L1 L2 L3 1 50 Hz 220 240V 3N 50 Hz 380 415V 1 50 Hz 220 240V 6 2 3 1 4 5 1 2 3 1 2 3 N N 1 5...

Page 4: ...g conditions are satisfied and that meets with your customer s approval 1 Places which are well ventilated 2 Places where the indoor and outdoor units piping and wiring lengths come within the allowab...

Page 5: ...tops oil will return to the discharge side of the compressor When starting the unit this can cause liquid oil hammer The oil circulation will decrease To solve these phenomena provide oil traps in the...

Page 6: ...kwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of the body 3 Tighten the cap firmly Note For tightening torques and dimensions of the flares refer to the table in the chapter Flar...

Page 7: ...ntire refrigerant pipe length is below 7 5 meters reduce the refrigerant amount charge mentioned in the nameplate as specified in the table R200 50 g m R250 90 g m RY200 100 g m RY250 170 g m Caution...

Page 8: ...PAIR SYSTEM REFER TO FIGURE 6 1 Outdoor unit 2 Indoor unit 3 Earth leak detector 4 Fuse 5 Remote controller SIMULTANEOUS OPERATION SYSTEM REFER TO FIGURE 7 1 Outdoor unit 2 Indoor unit Master 3 Indoor...

Page 9: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE05807 1C...

Reviews: