background image

3

Note 

 

bottom connection

Liquid side

Bend the liquid side accessory pipe and connect it to the stop
valve. Take care not to allow it to touch the gas side pipe.

±

75mm

A

A = bending position

Gas side

Cut the gas side accessory pipe and make connection using
an elbow (field supply).

±

167mm

A

A = cutting position

2. Make sure to perform the piping installation within the range of

the maximum allowable pipe length, allowable level difference
and allowable length after branching.
In case of simultaneous operation system.

• Upward and downward piping should be performed at the

main piping line.

• Use branch piping kit (optional) for branching of refrigerant

pipes. When using this, follow the following precautions.
(For details, refer to the manual attached to branch piping kit.)

a. Install the branch pipes horizontally (Maximum inclination:

20 degrees or less).

b. Length of branch pipe to the unit should be as short as

possible. (Maximum length: 20 meters or less).

c. Try to keep lengths of both branch pipes to the indoor unit

equal. (Maximum allowable length difference: 10 meters
or less).

3. For installation of the refrigerant branching kit, refer to the

installation manual delivered with the kit.

S

ELECTION

 

OF

 

PIPING

 

MATERIAL

1. Use the following material specification for refrigerant piping:

• Construction material: Phosphoric acid deoxidized

seamless copper for refrigerant.

• Size: Refer to chapter “Refrigerant pipe size and allowable

pipe length”.

• The wall thickness of the refrigerant piping should comply with

relevant local and national regulations. For R22 the allowable
pressure is 2.8 MPa.

H

OW

 

TO

 

OPEN

 

STOP

 

VALVES

 

(R

EFER

 

TO

 

FIGURE

 2)

To open

1. Remove the cap (1) and turn the shaft (2) counter-clockwise

with hexagon socket screw keys (JIS B 4648 nominal size 6 mm
and 10 mm).

2. Turn it all the way until the shaft stops.
3. Tighten the cap firmly.

To close

1. Remove the cap and turn the shaft clockwise.
2. Tighten the shaft firmly until it reaches the sealed area (4) of the

body.

3. Tighten the cap firmly.

Note 

- For tightening torques and dimensions of the flares, refer to the

table in the chapter “Flare shape and flarenut tightening torque”.

- Be sure to use both, a spanner and a torque wrench, when

connecting or disconnecting pipes to or from the unit.

- When connecting a flare nut, apply refrigerant oil on the flare

area (both internal and external face), and screw it with your
hand a few times first.

- Use a charging hose with push rod when using the service

port (5).

- Check for refrigerant gas leakage after tightening the cap.
- Make sure to keep stop valve open during operation.

Flare shape and flarenut tightening torque

L

EAK

 

TEST

 

AND

 

VACUUM

 

DRYING

The units were checked for leaks by the manufacturer.

Confirm that the valves are firmly closed before pressure test or
vacuuming.

After connection of the piping, a leak test must be performed and
the air in the refrigerant piping must be evacuated to a value of
4 mbar absolute by means of a vacuum pump.

Do not purge the air with refrigerants. Use a vacuum pump to
vacuum the installation. No additional refrigerant is provided for
air purging.

1. Perform air evacuation of the piping and a vacuum test.

(There may be no pressure increase for 1 minute.)

2. Break the vacuum with a minimum of 2 bar of nitrogen (N2).
3. Check the connections for leakage. Apply soapsuds to the

connections and inspect carefully. After checking, wipe them off
completely.

4. By way of a final air tight test, check if there is no decrease of

pressure after having left the installation under a pressure of
28 bar during 24 hours.

5. Release the nitrogen.
6. Try to reach perfect vacuum (= gauge reading - atmospheric

pressure of 1013 mbar).

7. Open the valves of the outdoor unit. Let refrigerant flow into

indoor units for equalization through pipes.

R = 0.4~0.8

45

° ±

2

90

°±

4

A

Pipe size

Tightening torque (Ncm)

Ø15.9

6180 ~ 7540

18.6 ~ 19.0

15.4 ~ 15.8

4950 ~ 6030

Ø12.7

A (mm)

Flare shape

Note 

 

front connection

Make sure to close the piping intake hole again after installation
work.

Summary of Contents for RY200F7W1

Page 1: ...Split System air conditioners INSTALLATION MANUAL R200F7W1 R250F7W1 RY200F7W1 RY250F7W1...

Page 2: ...overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer...

Page 3: ...50 B2 A 50 50 h H A B1 B2 100 100 20 20 mm R22 1 3 4 2 80 80 726 4x 15 1000 1 2 3 1 2 3 1 2 3 N L1 L2 L3 N L1 L2 L3 1 50 Hz 220 240V 3N 50 Hz 380 415V 1 50 Hz 220 240V 6 2 3 1 4 5 1 2 3 1 2 3 N N 1 5...

Page 4: ...g conditions are satisfied and that meets with your customer s approval 1 Places which are well ventilated 2 Places where the indoor and outdoor units piping and wiring lengths come within the allowab...

Page 5: ...tops oil will return to the discharge side of the compressor When starting the unit this can cause liquid oil hammer The oil circulation will decrease To solve these phenomena provide oil traps in the...

Page 6: ...kwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of the body 3 Tighten the cap firmly Note For tightening torques and dimensions of the flares refer to the table in the chapter Flar...

Page 7: ...ntire refrigerant pipe length is below 7 5 meters reduce the refrigerant amount charge mentioned in the nameplate as specified in the table R200 50 g m R250 90 g m RY200 100 g m RY250 170 g m Caution...

Page 8: ...PAIR SYSTEM REFER TO FIGURE 6 1 Outdoor unit 2 Indoor unit 3 Earth leak detector 4 Fuse 5 Remote controller SIMULTANEOUS OPERATION SYSTEM REFER TO FIGURE 7 1 Outdoor unit 2 Indoor unit Master 3 Indoor...

Page 9: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE05807 1C...

Reviews: