HARGING

 

REFRIGERANT

The cooling only unit does not require any additional charging of
refrigerant.

The heatpump unit however, requires additional charging of
refrigerant according to the length of pipe connected at the site.

Take the following steps for proper charging.

A

DDITIONAL

 

CHARGING

 

OF

 

REFRIGERANT

Find the correct amount of additional refrigerant to charge (G)
(unit of measurement = kg) using one of the following formulas.

Pair system

 (Refer to figure 5A)

(One way length of liquid pipe = L (unit of measurement = m))

RY200

G = (L-7.5) x 0.03

RY250

G = (L-7.5) x 0.05

Simultaneous operation system 

(Twin, triple, double twin)

(Refer to figure 5B, C and D)

RY200

Ø9.5

RY250

Ø6.4

A = 0.015 kg/m

A = 0.005 kg/m

G = (L1-7.5) x 0.03 + L2xA + L3xA + L4xA + L5xA + L6xA + L7xA

G = (L1-7.5) x 0.05 + L2xA + L3xA + L4xA + L5xA + L6xA + L7xA

• L1: one way length of main liquid pipe.

(Unit of measurement = m).

• L2, L3, L4, L5, L6, L7: branched pipes.

(Unit of measurement = m).

C

OMPLETE

 

CHARGING

 

OF

 

THE

 

REFRIGERANT

- When the entire refrigerant pipe length is 7.5 meters, charge the

refrigerant in accordance with the amount mentioned in the
nameplate.

- When the pipe length exceeds 7.5 meters, the charging amount

mentioned in the nameplate and that required for additional
charging are to be totalled as the net charging amount.

- When the entire refrigerant pipe length is below 7.5 meters

reduce the refrigerant amount charge mentioned in the
nameplate as specified in the table.

R200

50 g/m

R250

90 g/m

RY200

100 g/m

RY250

170 g/m

Caution

Recuperate overcharged refrigerant according to local and
national regulations.

F

IELD

 

WIRING

All field wiring and components must be installed by a licensed
electrician and must comply with relevant local and national
regulations.

The field wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.

Be sure to use a dedicated power circuit.
Never use a power supply shared by another appliance.

Fix cables as shown in the figure below and make sure they do not
make contact with the pipes (Especially on high pressure side).

1

2

3

N

L

1

L

2

L

3

1

3

2

Branched

pipe

1. Power supply intake
2. Switch block
3. Terminal block

Make sure to connect power supply cables in normal phase.
If connected in reverse phase, the remote controller of indoor unit
indicates “U1” and the equipment cannot operate. Change any two
of the three power supply cables (L1, L2, L3) to correct phase.

If the contact in the magnetic switch should be forcibly turned on
while the equipment is inoperative, the compressor will be damaged
by a fire. Never try to forcibly turn on the contact.

• Never squeeze bundled cables into a unit.
• Follow the electric wiring diagram and the nameplate for

electrical wiring works.

• Grounding resistance should be 500 

 or less.

Summary of Contents for RY200F7W1

Page 1: ...Split System air conditioners INSTALLATION MANUAL R200F7W1 R250F7W1 RY200F7W1 RY250F7W1...

Page 2: ...overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning r utf rd i verensst mmelse med och f ljer...

Page 3: ...50 B2 A 50 50 h H A B1 B2 100 100 20 20 mm R22 1 3 4 2 80 80 726 4x 15 1000 1 2 3 1 2 3 1 2 3 N L1 L2 L3 N L1 L2 L3 1 50 Hz 220 240V 3N 50 Hz 380 415V 1 50 Hz 220 240V 6 2 3 1 4 5 1 2 3 1 2 3 N N 1 5...

Page 4: ...g conditions are satisfied and that meets with your customer s approval 1 Places which are well ventilated 2 Places where the indoor and outdoor units piping and wiring lengths come within the allowab...

Page 5: ...tops oil will return to the discharge side of the compressor When starting the unit this can cause liquid oil hammer The oil circulation will decrease To solve these phenomena provide oil traps in the...

Page 6: ...kwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of the body 3 Tighten the cap firmly Note For tightening torques and dimensions of the flares refer to the table in the chapter Flar...

Page 7: ...ntire refrigerant pipe length is below 7 5 meters reduce the refrigerant amount charge mentioned in the nameplate as specified in the table R200 50 g m R250 90 g m RY200 100 g m RY250 170 g m Caution...

Page 8: ...PAIR SYSTEM REFER TO FIGURE 6 1 Outdoor unit 2 Indoor unit 3 Earth leak detector 4 Fuse 5 Remote controller SIMULTANEOUS OPERATION SYSTEM REFER TO FIGURE 7 1 Outdoor unit 2 Indoor unit Master 3 Indoor...

Page 9: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE05807 1C...

Reviews: