background image

Installation manual

4

RXYSQ6TAV1B

VRV IV-S System air conditioner

4P482260-1 – 2017.03

3.

B

EFORE

 

INSTALLATION

3.1.

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read 

"8. Precautions on refrigerant piping" on page 7

 carefully

and follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).

The connected indoor units must be indoor units designed
exclusively for R410A.

3.2.

Installation

For Sky Air or room air conditioner indoor units only:
For installation of the indoor unit(s) and BP unit(s), refer to the
indoor unit and BP unit's installation manual.

For VRV indoor units only:
For installation of the indoor unit(s), refer to the indoor unit
installation manual.

Never operate the air conditioner with the discharge pipe
thermistor (R2T), suction pipe thermistor (R3T) and pressure
sensors (S1NPH, S1NPL) removed. Such operation may burn
out the compressor.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

3.3.

Handling

As shown in the figure, bring the unit slowly by grabbing the left and
right grips.

Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.

4.

S

ELECTING

 

INSTALLATION

 

SITE

Only for Y1: This is a class A product. In a domestic environment this
product may cause radio interference in which case the user may be
required to take adequate measures.

1

Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.

-

Places which are well-ventilated.

-

Places where the unit does not bother next-door neighbours.

-

Safe places which can withstand the unit's weight and 
vibration and where the unit can be installed level.

-

Places where there is no possibility of flammable gas or 
product leak.

-

Places where servicing space can be well ensured.

-

Places where lengths of piping and wiring for indoor units, BP 
units (for Sky Air or room air conditioner indoor units only) 
and outdoor units are within the allowable ranges.

-

Places where water leaking from the unit cannot cause 
damage to the location (e.g. in case of a blocked drain pipe).

-

Places where the rain can be avoided as much as possible.

2

When installing the unit in a place exposed to strong wind, pay
special attention to the following.

Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-

Deterioration of the operational capacity.

-

Frequent frost acceleration in heating operation.

-

Disruption of operation due to rise of high pressure.

-

When a strong wind blows continuously on the face of the 
unit, the fan can start rotating very fast until it breaks.

Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.

Turn the air outlet side toward the building's wall, fence or
screen.

Set the outlet side at a right angle to the direction of the wind.

Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph

"7.1. Selection of piping material" on page 7

.

Take care not to let hands or objects come in contact with
rear fins.

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

Strong wind

Blown air

Strong wind

Make sure there is enough room to do the installation

4PEN482260-1.book  Page 4  Monday, March 20, 2017  8:54 PM

Summary of Contents for RXYSQ-TAV

Page 1: ...INSTALLATION MANUAL RXYSQ6TAV1B VRV IV S System air conditioner 4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Page 2: ...L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1...

Page 3: ...2 3 4 1 2 3 4 380 415 V V1 Y1 10 16 V 230 V 230 V 16 V 16 V 16 V 1 2 3 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V V1 Y1 11 2 1 1 1 2 3 4 4 V1 1 50 Hz Y1 3N 50 Hz 1 50 Hz 1 8 11 9 8 10 4PEN482260 1 book Page 1...

Page 4: ...B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information...

Page 5: ...The English text is the original instruction Other languages are translations of the original instructions 1 SAFETY CONSIDERATIONS The precautions listed here are divided into the following two types...

Page 6: ...tubes are not effective grounds Lightning conductor or telephone ground wire Electric potential may rise abnormally if struck by a lightning bolt Be sure to install an earth leakage breaker Failure to...

Page 7: ...an optimum refrigerant branching kit refer to Refrigerant branch kit selection on page 11 2 5 Technical and electrical specifications Refer to the Engineering Data Book for the complete list of specif...

Page 8: ...e satisfied and that meets with your customer s approval Places which are well ventilated Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight a...

Page 9: ...evention of falling over If it is necessary to prevent the unit from falling over install as shown in the figure prepare all 4 wires as indicated in the drawing unscrew the top plate at the 4 location...

Page 10: ...H A and L is shown in the table below NOTE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order to provide a free space of more than 100 mm und...

Page 11: ...reat caution is needed when passing copper tubes through walls For handling of stop valves refer to 9 3 How to use the stop valve on page 9 Only use the flare nuts included with the unit Using differe...

Page 12: ...material field supply to stop up all gaps as shown in the figure Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box Pipe size Tightening torque N m A m...

Page 13: ...ul not to let the BP unit and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown...

Page 14: ...al cover 3 For Sky Air or room air conditioner indoor units only BP unit and outdoor field piping 3 For VRV indoor units only Indoor and outdoor field piping 4 Corking etc 5 Insulation material field...

Page 15: ...Difference in height Difference in height between outdoor and indoor units H1 30 m Between outdoor and BP units Difference in height Difference in height between outdoor and BP units H2 30 m Between...

Page 16: ...c d e Total indoor capacity Q Gas pipe Liquid pipe Qc Qd Qe 5 0 kW 12 7x0 8 6 4x0 8 Qc Qd Qe 5 0 kW 15 9x1 0 9 5x0 8 NOTE Qc Qd Qe is total connected indoor capacity c d e indicates the symbols in th...

Page 17: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor un...

Page 18: ...tory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See How to calculate the additional refrigerant to be charged on page...

Page 19: ...ollows 1 Turn on the power of the outdoor unit 2 Press at least 5 seconds 3 Press 51 times on 4 Press once 5 Press once 6 Press 2 times on The setting for changing from VRV applications to Sky Air or...

Page 20: ...eration stops The operation automatically stops within 30 minutes If the refrigerant charge cannot be finished within 30 minutes repeat step 5 If the operation stops immediately after restart there is...

Page 21: ...in switch has a contact separation of at least 3 mm in all poles Never squeeze bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side...

Page 22: ...urely clamp the cable as shown in figure 12 1 Power 2 Earth leakage breaker 3 Branch switch overcurrent breaker fuse 4 Ground 5 BP unit 1 Power 2 Earth leakage breaker 3 Branch switch overcurrent brea...

Page 23: ...vent outside pressure being exerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and make proper tighteni...

Page 24: ...nd transmission wiring Use a designated power supply and transmission wiring and make sure that it has been carried out according to the instructions described in this manual according to the wiring d...

Page 25: ...BS1 BS5 3 DIP switches 2 DS1 1 DS1 2 x OFF w ON c blinking For changing the set mode For field setting For field setting For test operation For resetting the address when the wiring is changed or whe...

Page 26: ...ic judgement of piping length 4 After the test operation maximum 30 minutes the unit automatically stops Check the operation results by the outdoor unit led indication H1P H2P H3P H4P H5P H6P H7P OFF...

Page 27: ...mmediately and then energize the heater for a sufficient length of time before restarting the operation Run each indoor unit one at a time and make sure the corresponding outdoor unit is also running...

Page 28: ...y against leakage according to local regulations or standards The following standards may be applicable if local regulations are not available This unit like other air conditioning systems uses R410A...

Page 29: ...tional legislation amount of refrigerant in a single unit system amount of refrigerant with which the system is charged before leaving the factory additional charging amount amount of refrigerant adde...

Page 30: ...4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Page 31: ...E E E E E 12 A B C 2 2 3 2 4 7 2 9 3 2 3 5 6 1 4 8 3 2 4 3 2 1 6 8 9 7 2 V1 Y1 3 14 A1P A2P A4P X2M X2M F1 F1 F2 F2 TO IN D UNIT C H SELECTOR X2M A C B A4P TO OUT D UNIT F1 F1 F2 A C B F2 TO IN D UNIT...

Page 32: ...4P482260 1 2017 03 Copyright 2017 Daikin 4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Reviews: