Installation manual

8

RXYSQ6TAV1B

VRV IV-S System air conditioner

4P482260-1 – 2017.03

8.2.

Cautions for flare connection

See the following table for flare part machining dimensions.

When connecting the flare nuts, apply refrigerant ether or ester
oil to the inside and outside of the flares and turn them three or
four times at first.

When loosening a flare nut, always use two wrenches in
combination. When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.

See the following table for tightening torque.
(Applying too much torque may cause the flares to crack.)

After all the piping has been connected, use nitrogen to perform
a gas leak check.

9.

R

EFRIGERANT

 

PIPING

Field pipes can be installed in four directions.

Figure - 

Field pipes in four directions 

(See figure 5)

When connecting the piping in the lateral direction (on the rear),
remove the piping cover (rear) in reference to 

figure 8

.

To install the connecting pipe to the unit in a downward direction,
make a knock-out hole by penetrating the center area around
the knock-out hole using a Ø6 mm drill. 

(See figure 5)

.

Cutting out the two slits makes it possible to install as shown in

figure 5

.

(Use a metal saw to cut out the slits.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

The size of the gas side stop valve is Ø15.9 while the inter-unit piping
is Ø19.1. Use the standard supplied accessory piping to make the
connection. See 

figure 19

.

Only for RXYSQ6.

9.1.

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material (field
supply) to stop up all gaps, as shown in the figure.

Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.

Pipe size

Tightening 

torque (N•m)

A (mm)

Flare shape

Ø9.5

33~42

12.8~13.2

Ø15.9

63~77

19.3~19.7

Ø19.1

90~110

12.3~23.7

NOTE

You must use a torque wrench but if you are obliged to
install the unit without a torque wrench, you may follow
the installation method mentioned below.

After the work is finished, make sure to check that
there is no gas leak.

When you keep on tightening the flare nut with a
spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten
the flare nut within the angle shown below:

12 3

4

1

Piping union

2

Spanner

3

Flare nut

4

Torque wrench

R=0.4~0.8

45 

±

2

90 

±

2

A

Pipe size

Further tightening 

angle

Recommended 

arm length of tool

Ø9.5 (3/8")

60~90°

±200 mm

Ø15.9 (5/8")

30~60°

±300 mm

Ø19.1 (5/8")

20~35°

±450 mm

A

Forward

B

Backward

C

Sideways

D

Downward

1

Drill

2

Center area around knock-out hole

3

Knock-out hole

4

Slit

5

Connecting pipe liquid (field supply)

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

11

For Sky Air or room air conditioner indoor units only:
Gas line copper gasket supplied with the unit (1) (make 
sure to always use the copper gasket).

11

For VRV indoor units only:
Connecting pipe gas (field supply, except RXYSQ6)

1

Piping cover (rear)

A

Front connection

B

Rear connection

C

Side connection

D

Bottom connection

1

Gas line copper gasket supplied with the unit (make sure 
to always use the copper gasket).

2

Gas line piping supplied with the unit

3

Gas piping (field supply)

4

Cut to the appropriate length.

5

Gas line piping supplied with the unit

1

1

Putty or insulating material (field 
supply)

4PEN482260-1.book  Page 8  Monday, March 20, 2017  8:54 PM

Summary of Contents for RXYSQ-TAV

Page 1: ...INSTALLATION MANUAL RXYSQ6TAV1B VRV IV S System air conditioner 4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Page 2: ...L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1...

Page 3: ...2 3 4 1 2 3 4 380 415 V V1 Y1 10 16 V 230 V 230 V 16 V 16 V 16 V 1 2 3 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V V1 Y1 11 2 1 1 1 2 3 4 4 V1 1 50 Hz Y1 3N 50 Hz 1 50 Hz 1 8 11 9 8 10 4PEN482260 1 book Page 1...

Page 4: ...B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information...

Page 5: ...The English text is the original instruction Other languages are translations of the original instructions 1 SAFETY CONSIDERATIONS The precautions listed here are divided into the following two types...

Page 6: ...tubes are not effective grounds Lightning conductor or telephone ground wire Electric potential may rise abnormally if struck by a lightning bolt Be sure to install an earth leakage breaker Failure to...

Page 7: ...an optimum refrigerant branching kit refer to Refrigerant branch kit selection on page 11 2 5 Technical and electrical specifications Refer to the Engineering Data Book for the complete list of specif...

Page 8: ...e satisfied and that meets with your customer s approval Places which are well ventilated Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight a...

Page 9: ...evention of falling over If it is necessary to prevent the unit from falling over install as shown in the figure prepare all 4 wires as indicated in the drawing unscrew the top plate at the 4 location...

Page 10: ...H A and L is shown in the table below NOTE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order to provide a free space of more than 100 mm und...

Page 11: ...reat caution is needed when passing copper tubes through walls For handling of stop valves refer to 9 3 How to use the stop valve on page 9 Only use the flare nuts included with the unit Using differe...

Page 12: ...material field supply to stop up all gaps as shown in the figure Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box Pipe size Tightening torque N m A m...

Page 13: ...ul not to let the BP unit and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown...

Page 14: ...al cover 3 For Sky Air or room air conditioner indoor units only BP unit and outdoor field piping 3 For VRV indoor units only Indoor and outdoor field piping 4 Corking etc 5 Insulation material field...

Page 15: ...Difference in height Difference in height between outdoor and indoor units H1 30 m Between outdoor and BP units Difference in height Difference in height between outdoor and BP units H2 30 m Between...

Page 16: ...c d e Total indoor capacity Q Gas pipe Liquid pipe Qc Qd Qe 5 0 kW 12 7x0 8 6 4x0 8 Qc Qd Qe 5 0 kW 15 9x1 0 9 5x0 8 NOTE Qc Qd Qe is total connected indoor capacity c d e indicates the symbols in th...

Page 17: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor un...

Page 18: ...tory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See How to calculate the additional refrigerant to be charged on page...

Page 19: ...ollows 1 Turn on the power of the outdoor unit 2 Press at least 5 seconds 3 Press 51 times on 4 Press once 5 Press once 6 Press 2 times on The setting for changing from VRV applications to Sky Air or...

Page 20: ...eration stops The operation automatically stops within 30 minutes If the refrigerant charge cannot be finished within 30 minutes repeat step 5 If the operation stops immediately after restart there is...

Page 21: ...in switch has a contact separation of at least 3 mm in all poles Never squeeze bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side...

Page 22: ...urely clamp the cable as shown in figure 12 1 Power 2 Earth leakage breaker 3 Branch switch overcurrent breaker fuse 4 Ground 5 BP unit 1 Power 2 Earth leakage breaker 3 Branch switch overcurrent brea...

Page 23: ...vent outside pressure being exerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and make proper tighteni...

Page 24: ...nd transmission wiring Use a designated power supply and transmission wiring and make sure that it has been carried out according to the instructions described in this manual according to the wiring d...

Page 25: ...BS1 BS5 3 DIP switches 2 DS1 1 DS1 2 x OFF w ON c blinking For changing the set mode For field setting For field setting For test operation For resetting the address when the wiring is changed or whe...

Page 26: ...ic judgement of piping length 4 After the test operation maximum 30 minutes the unit automatically stops Check the operation results by the outdoor unit led indication H1P H2P H3P H4P H5P H6P H7P OFF...

Page 27: ...mmediately and then energize the heater for a sufficient length of time before restarting the operation Run each indoor unit one at a time and make sure the corresponding outdoor unit is also running...

Page 28: ...y against leakage according to local regulations or standards The following standards may be applicable if local regulations are not available This unit like other air conditioning systems uses R410A...

Page 29: ...tional legislation amount of refrigerant in a single unit system amount of refrigerant with which the system is charged before leaving the factory additional charging amount amount of refrigerant adde...

Page 30: ...4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Page 31: ...E E E E E 12 A B C 2 2 3 2 4 7 2 9 3 2 3 5 6 1 4 8 3 2 4 3 2 1 6 8 9 7 2 V1 Y1 3 14 A1P A2P A4P X2M X2M F1 F1 F2 F2 TO IN D UNIT C H SELECTOR X2M A C B A4P TO OUT D UNIT F1 F1 F2 A C B F2 TO IN D UNIT...

Page 32: ...4P482260 1 2017 03 Copyright 2017 Daikin 4PEN482260 1 book Page 1 Monday March 20 2017 8 54 PM...

Reviews: