background image

10

NOTE

• Do not turn off power immediately after the 

unit stops, but wait for at least 5 minutes.

• The system needs at least 5 minutes for the 

residual operation of drain pump.
Turning the power off immediately will cause 
water leak or trouble.

5-3 ADJUSTING THE AIR FLOW DIRECTION 

(Refer to figure 6)

Press the air flow direction button to 
select the air direction.
The air flow flap display swings as 
shown on the right and the air flow 
direction continuously varies. (Auto-
matic swing setting)

Press the air flow direction adjust button to 
select the air direction of your choice.

The air flow flap display stops swing-
ing and the air flow direction is fixed. 
(Fixed air flow direction setting)

MOVEMENT OF THE AIR FLOW FLAP 
(Refer to figure 13)

For the following conditions, a micro computer con-
trols the air flow direction which may be different 
from the display.

The air flow direction can be adjusted in one of the 
following ways.

• The air flow flap itself adjusts its position.
• The air flow direction can be fixed by the user.
• Automatic “

” and desired position “

”.

NOTE

• The movable limit of the flap is changeable. 

Contact your Daikin dealer for details.

• Avoid operating in the horizontal direction 

”. It may cause dew or dust to settle on 

the ceiling.

5-4 PROGRAMMING START AND STOP OF 

THE SYSTEM WITH TIMER 
(Refer to figure 9)

• The timer is operated in the following two ways. 

Programming the stop time “

”. The sys-

tem stops operating after the set time has 
elapsed.
Programming the start time “

”. The sys-

tem starts operating after the set time has 
elapsed.

• The timer can be programmed for a maxi-

mum of 72 hours.

• The start and the stop time can be simulta-

neously programmed.

Press the timer mode start/stop button several 
times and select the mode on the display.
The display flashes.

• For setting the timer stop “

• For setting the timer start “

Press the programming time button and set 
the time for stopping or starting the system.

Each time this button is pressed, the 
time advances or goes backward by 1 
hour.

Press the timer on/off button.
The timer setting procedure ends. The display 

” or “

” changes from flashing to 

lighting.

NOTE

• When setting the timer off and on at the 

same time, repeat the above procedure 
(from “

” to “

”) once again.

• After the timer is programmed, the display 

shows the remaining time.

• Press the timer on/off button once again to 

cancel programming. The display vanishes.

For example: (Refer to figure 11)

When the timer is programmed to stop the sys-
tem after 3 hours and start the system after 4 
hours, the system will stop after 3 hours and 
start 1 hour later.

COOLING

HEATING

• When starting operation.
• When the room temperature is 

higher than the set temperature.

• At defrost operation.

• When operating continuously at horizontal air flow direction.
• When continuous operation with downward air flow is performed at the 

time of cooling with a ceiling-suspended or a wall-mounted unit, the 
microcomputer may control the flow direction, and then the remote con-
troller indication also will change.

1

2

1

2

3

1

3

01_EN_3P161360-3D.fm  Page 10  Thursday, April 13, 2006  9:46 AM

Summary of Contents for RXYQ72MTJU

Page 1: ...RXYQ192MTJU REYQ72MTJU REYQ96MTJU REYQ144MTJU REYQ168MTJU REYQ192MTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should b...

Page 2: ...Figure 1 RXYQ REYQ F NOT AVAILABLE 23 24 Figure 2 Figure 3 F F Figure 4 Figure 5 Figure 6 Figure 7 1 Figure 7 3 Figure 7 2 F F F 00_CV_3P161360 3D fm Page 2 Wednesday April 12 2006 5 25 PM...

Page 3: ...F Figure 8 Figure 9 F F Figure 10 Figure 11 Figure 12 Wall Mounted Multi flow Ceiling Suspended Figure 13 Figure 14 Figure 15 00_CV_3P161360 3D fm Page 3 Wednesday April 12 2006 5 25 PM...

Page 4: ...in the unit or property damage only accidents Keep these warning sheets handy so that you can refer to them if needed Also if this unit is transferred to a new user make sure to hand over this operati...

Page 5: ...er the fins while working around them Do not put a finger or other objects into the air inlet or air outlet The fan is rotating at high speed and will cause injury Do not allow children to play on or...

Page 6: ...r the indoor unit It may cause incomplete combustion or deformation of the unit due to the heat Arrange the drain hose to ensure smooth drainage Incomplete drainage may cause wet ting of the building...

Page 7: ...and or stop time 18 Temperature setting button Use this button for setting the desired tempera ture 19 Filter sign reset button Refer to the operation manual of indoor unit 20 Fan speed control butto...

Page 8: ...tem may control the air flow rate automatically It may take some time to change the air flow rate This is not a malfunction FOR SYSTEMS WITHOUT COOL HEAT SELECTOR Refer to figure 4 Press the operation...

Page 9: ...since the unit uses a hot air circulatory system to warm the entire room If the hot air rises to the ceiling leaving the area above the floor cold we recommend using the circulator the indoor fan for...

Page 10: ...the set time has elapsed Programming the start time The sys tem starts operating after the set time has elapsed The timer can be programmed for a maxi mum of 72 hours The start and the stop time can b...

Page 11: ...CON TROLLER CONTROL SYSTEM This system provides two other control systems beside individual control one remote controller con trols one indoor unit system Confirm which type of your unit is the follo...

Page 12: ...ion See the operation manual included with the indoor unit for details on how to clean it 8 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROU BLES 8 1 THE SYSTEM DOES NOT OPERATE The air conditioner doe...

Page 13: ...r to heating operation after defrost operation Moisture generated by defrost becomes steam and is exhausted 8 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power...

Page 14: ...efer to page 9 9 TROUBLE SHOOTING If one of the following malfunctions occurs take the measures shown below and contact your Daikin dealer WARNING Stop operation and shut off the power if any thing un...

Page 15: ...r unit manual 3 The system operates but cooling or heating is insufficient Check if air inlet or outlet of outdoor or indoor unit is blocked by obstacles Remove any obstacle and make it well ventilate...

Page 16: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0605 HT 3P161360 3D EM03A045D 00_CV_3P161360 3D fm Page 4 Wednesday April 12 2006 5 25 PM...

Reviews: