background image

9

Stopping the system

Press the on/off button once again.
The operation lamp goes off and the system 
stops operation.

NOTE

• Do not turn off power immediately after the 

unit stops.

• The system needs at least 5 minutes for the 

residual operation of drain pump.
Turning the power off immediately will cause 
water leak or trouble.

EXPLANATION OF HEATING OPERATION

• For general heating operation, it may take longer 

to reach the set temperature than in cooling oper-
ation.
We recommend starting the operation which was 
used before using timer operation.

• The following operation is performed in order to 

prevent the heating capacity from dropping or 
cold air from blowing.

Defrost operation

• In heating operation, freezing of the outdoor 

unit coil increases. Heating capability 
decreases and the system goes into defrost 
operation.

• The indoor unit fan stops and the remote 

controller displays

 

”.

• After maximum 10 minutes of defrost operation, 

the system returns to heating operation again.

Hot start

• In order to prevent cold air from blowing out 

of an indoor unit at the start of heating oper-
ation, the indoor fan is automatically 
stopped. The display of the remote controller 
shows “

”.

NOTE

• The heating capacity drops as the outside 

temperature falls. If this happens, use 
another heating device together with the 
unit. (When using the appliances which pro-
duce open fire together, ventilate a room 
constantly.)
Do not place appliances which produce 
open fire in places exposed to the air flow 
from the unit or under the unit.

• It takes some time for the room to warm up 

from the time the unit is started since the unit 
uses a hot-air circulatory system to warm 
the entire room.

• If the hot air rises to the ceiling, leaving the 

area above the floor cold, we recommend 
using the circulator (the indoor fan for circu-
lating air). Contact your dealer for details.

5-2 PROGRAM DRY OPERATION

• The function of this operation is to decrease 

the humidity in your room with a minimum 
temperature decrease.

• The micro computer automatically deter-

mines temperature and fan speed.

• This function is not available if the room tem-

perature is 68°F or lower.

FOR SYSTEMS WITHOUT COOL/HEAT 
SELECTOR (Refer to figure 5)

Press the operation mode selector button several 
times and select “

” (program dry operation).

Press the on/off button
The operation lamp lights up and the system 
starts operation.

Press the air flow direction adjust button. Refer 
to the chapter “Adjusting the air flow direction” 
for details.

Press the on/off button once again.
The operation lamp goes off and the system 
stops operation.

NOTE

• Do not turn off power immediately after the 

unit stops, but wait for at least 5 minutes.

• The system needs at least 5 minutes for the 

residual operation of drain pump.
Turning the power off immediately will cause 
water leak or trouble.

FOR SYSTEMS WITH COOL/HEAT SELECTOR 
(Refer to figure 8)

Select cooling operation mode with the COOL/
HEAT selector.

Press the operation mode selector button sev-
eral times and select “

” (program dry 

operation).

Press the on/off button
The operation lamp lights up and the system 
starts operation.

Press the air flow direction adjust button. Refer 
to the chapter “Adjusting the air flow direction” 
for details.

Press the on/off button once again.
The operation lamp goes off and the system 
stops operation.

6

1

2

3

4

1

2

3

4

5

01_EN_3P161360-3D.fm  Page 9  Thursday, April 13, 2006  9:46 AM

Summary of Contents for RXYQ72MTJU

Page 1: ...RXYQ192MTJU REYQ72MTJU REYQ96MTJU REYQ144MTJU REYQ168MTJU REYQ192MTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should b...

Page 2: ...Figure 1 RXYQ REYQ F NOT AVAILABLE 23 24 Figure 2 Figure 3 F F Figure 4 Figure 5 Figure 6 Figure 7 1 Figure 7 3 Figure 7 2 F F F 00_CV_3P161360 3D fm Page 2 Wednesday April 12 2006 5 25 PM...

Page 3: ...F Figure 8 Figure 9 F F Figure 10 Figure 11 Figure 12 Wall Mounted Multi flow Ceiling Suspended Figure 13 Figure 14 Figure 15 00_CV_3P161360 3D fm Page 3 Wednesday April 12 2006 5 25 PM...

Page 4: ...in the unit or property damage only accidents Keep these warning sheets handy so that you can refer to them if needed Also if this unit is transferred to a new user make sure to hand over this operati...

Page 5: ...er the fins while working around them Do not put a finger or other objects into the air inlet or air outlet The fan is rotating at high speed and will cause injury Do not allow children to play on or...

Page 6: ...r the indoor unit It may cause incomplete combustion or deformation of the unit due to the heat Arrange the drain hose to ensure smooth drainage Incomplete drainage may cause wet ting of the building...

Page 7: ...and or stop time 18 Temperature setting button Use this button for setting the desired tempera ture 19 Filter sign reset button Refer to the operation manual of indoor unit 20 Fan speed control butto...

Page 8: ...tem may control the air flow rate automatically It may take some time to change the air flow rate This is not a malfunction FOR SYSTEMS WITHOUT COOL HEAT SELECTOR Refer to figure 4 Press the operation...

Page 9: ...since the unit uses a hot air circulatory system to warm the entire room If the hot air rises to the ceiling leaving the area above the floor cold we recommend using the circulator the indoor fan for...

Page 10: ...the set time has elapsed Programming the start time The sys tem starts operating after the set time has elapsed The timer can be programmed for a maxi mum of 72 hours The start and the stop time can b...

Page 11: ...CON TROLLER CONTROL SYSTEM This system provides two other control systems beside individual control one remote controller con trols one indoor unit system Confirm which type of your unit is the follo...

Page 12: ...ion See the operation manual included with the indoor unit for details on how to clean it 8 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROU BLES 8 1 THE SYSTEM DOES NOT OPERATE The air conditioner doe...

Page 13: ...r to heating operation after defrost operation Moisture generated by defrost becomes steam and is exhausted 8 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power...

Page 14: ...efer to page 9 9 TROUBLE SHOOTING If one of the following malfunctions occurs take the measures shown below and contact your Daikin dealer WARNING Stop operation and shut off the power if any thing un...

Page 15: ...r unit manual 3 The system operates but cooling or heating is insufficient Check if air inlet or outlet of outdoor or indoor unit is blocked by obstacles Remove any obstacle and make it well ventilate...

Page 16: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0605 HT 3P161360 3D EM03A045D 00_CV_3P161360 3D fm Page 4 Wednesday April 12 2006 5 25 PM...

Reviews: