background image

English

8

Outdoor Unit Installation

*1. Pipe length vs. vacuum pump run time.

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.

Check all pipe joints and re-tighten nuts as needed, then repeat steps 2) through 4).

5.

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Fill from the gas pipe in liquid form.

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).

(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

6

5

Please fill in with indelible ink, 

  the factory refrigerant charge of the product, 

tCO

2

eq calculation according to the formula (rounded up 

to 2 decimal places)

  the additional refrigerant amount charged in the field and

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases. 
Do not vent gases into the atmosphere.

Refrigerant type:
GWP

 value:

factory refrigerant charge of the 
product: 
see unit name plate 

additional refrigerant amount 
charged in the field 

total refrigerant charge 

greenhouse gas emissions

 of the 

total refrigerant charge expressed 
as tonnes CO

2

-equivalent 

outdoor unit

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port 
(e.g. onto the inside of the stop valve cover).

GWP = global warming potential 

(1)

(1)

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

1000

GWP × kg

=

=

+

kg

=

kg

=

GWP: 675

675

R32

R32

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. 
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.

NOTICE

In Europe, the 

greenhouse gas emissions 

of the total refrigerant charge in the system (expressed as tonnes CO

-equivalent) 

is  used  to  determine  the  maintenance intervals. Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000

Use the GWP value mentioned on the refrigerant charge label. This GWP value is based on the 4th IPCC 

Assessment 

Report.  The  GWP  value  mentioned  in  the manual might be outdated (i.e., based on the 3rd IPCC Assessment Report).

6

5

Please fill in with indelible ink, 

  the factory refrigerant charge of the product, 

tCO

2

eq calculation according to the formula (rounded up 

to 2 decimal places)

  the additional refrigerant amount charged in the field and

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases. 
Do not vent gases into the atmosphere.

Refrigerant type:
GWP

 value:

factory refrigerant charge of the 
product: 
see unit name plate 

additional refrigerant amount 
charged in the field 

total refrigerant charge 

greenhouse gas emissions

 of the 

total refrigerant charge expressed 
as tonnes CO

2

-equivalent 

outdoor unit

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port 
(e.g. onto the inside of the stop valve cover).

GWP = global warming potential 

(1)

(1)

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

1000

GWP × kg

=

=

+

kg

=

kg

=

GWP: 675

675

R32

R32

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. 
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.

NOTICE

In Europe, the 

greenhouse gas emissions 

of the total refrigerant charge in the system (expressed as tonnes CO

-equivalent) 

is  used  to  determine  the  maintenance intervals. Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000

Use the GWP value mentioned on the refrigerant charge label. This GWP value is based on the 4th IPCC 

Assessment 

Report.  The  GWP  value  mentioned  in  the manual might be outdated (i.e., based on the 3rd IPCC Assessment Report).

3PEN386697-4L.book  Page 8  Monday, July 31, 2017  2:37 PM

Summary of Contents for RXTM30N2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXTM30N2V1B RXTM40N2V1B RXTP25N2V1B RXTP35N2V1B ARXTP25N2V1B ARXTP35N2V1B 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM DAIKIN...

Page 2: ...ul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjo...

Page 3: ...stunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl...

Page 4: ...the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the pow...

Page 5: ...mperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users i...

Page 6: ...radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty...

Page 7: ...e foot bolts or wires 250mm from wall unit mm How to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach the stop valve cover Inser...

Page 8: ...ter installed In accordance with the foundation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on...

Page 9: ...surface of the flare Use refrigeration oil for R32 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage After the piping work is finished after check...

Page 10: ...on cycle When refrigerant gas leaks occur ventilate the room as soon and as much as possible R32 as well as other refrigerants should always be recovered and never be released directly into the enviro...

Page 11: ...1000 GWP kg kg kg GWP 675 675 R32 R32 NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the uni...

Page 12: ...set the operation mode to cooling CAUTION When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close...

Page 13: ...or unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on an...

Page 14: ...mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core w...

Page 15: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 16: ...ts standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the po...

Page 17: ...iping Discharge pipe thermistor Propeller fan Heating Cooling Refrigerant flow ON heating Muffler with filter Muffler Muffler 6x7 0 CuT 7 9 CuT 6 4 CuT 6 4 CuT 9 5 CuT 7 9 CuT 9 5 CuT 9 5 CuT 12 7 CuT...

Page 18: ...3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM...

Page 19: ...3PEN386697 4L book Page 2 Monday July 31 2017 2 37 PM...

Page 20: ...3P386697 4L 2017 06 Copyright 2017 Daikin 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM...

Reviews: