background image

9

English

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes.

To stop the operation, press the indoor unit ON/OFF switch.

Using the indoor unit’s remote controller

• Please read about the procedure in “Trial operation from remote controller” in the installation manual attached to the

indoor unit. Please set the operation mode to “cooling”.

 CAUTION

• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced cooling operation.

Liquid 

stop valve

Gas 

stop valve

Service port

Valve cap

Close

Hexagonal 

wrench

 WARNING

The unit is accompanied with the label below. Please read the following instructions carefully.

WARNING

1)

2)

3)

4)

5)

• When the refrigeration circuit has a leak, do not execute pump down with the compressor.
• Use recovery system into separate cylinder.
• Warning, explosive hazard exists when executing pump down.
• Pump down with compressor can lead to self-combustion due to air entering during pump

down.

Used symbols:

1)

Warning sign (ISO 7010 – W001)

2)

Warning, Explosive material (ISO 7010 – W002)

3)

Read Operator’s manual (ISO 7000 – 0790)

4)

Operator’s manual; operating instructions (ISO 7000 – 1641)

5)

Service indicator; read technical manual (ISO 7000 – 1659)

3PEN386697-4L.book  Page 9  Monday, July 31, 2017  2:37 PM

Summary of Contents for RXTM30N2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXTM30N2V1B RXTM40N2V1B RXTP25N2V1B RXTP35N2V1B ARXTP25N2V1B ARXTP35N2V1B 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM DAIKIN...

Page 2: ...ul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjo...

Page 3: ...stunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas sl...

Page 4: ...the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the pow...

Page 5: ...mperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users i...

Page 6: ...radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty...

Page 7: ...e foot bolts or wires 250mm from wall unit mm How to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach the stop valve cover Inser...

Page 8: ...ter installed In accordance with the foundation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on...

Page 9: ...surface of the flare Use refrigeration oil for R32 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage After the piping work is finished after check...

Page 10: ...on cycle When refrigerant gas leaks occur ventilate the room as soon and as much as possible R32 as well as other refrigerants should always be recovered and never be released directly into the enviro...

Page 11: ...1000 GWP kg kg kg GWP 675 675 R32 R32 NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the uni...

Page 12: ...set the operation mode to cooling CAUTION When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close...

Page 13: ...or unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on an...

Page 14: ...mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core w...

Page 15: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 16: ...ts standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the po...

Page 17: ...iping Discharge pipe thermistor Propeller fan Heating Cooling Refrigerant flow ON heating Muffler with filter Muffler Muffler 6x7 0 CuT 7 9 CuT 6 4 CuT 6 4 CuT 9 5 CuT 7 9 CuT 9 5 CuT 9 5 CuT 12 7 CuT...

Page 18: ...3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM...

Page 19: ...3PEN386697 4L book Page 2 Monday July 31 2017 2 37 PM...

Page 20: ...3P386697 4L 2017 06 Copyright 2017 Daikin 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM...

Reviews: