3

English

Outdoor Unit Installation Drawings

(Foot bolt-hole 

 centres)

330mm

Allow space for piping 
and electrical servicing.

250mm from wall

CAUTION

**Set the piping length 

from 1.5m to 30m.

Wrap the insulation 
pipe with the finishing
tape from bottom to top.

Stop valve cover

Service lid

Where there is a danger of 
the unit falling, use foot bolts, 
or wires.

In sites with poor drainage, 
use block bases for outdoor 
unit.  
Adjust foot height until the 
unit is leveled.  Otherwise, 
water leakage or pooling of 
water may occur.

(Foot bolt-hole centres)

580mm

120mm

(From unit’s side)

Max. allowable height

Min. allowable length

Max. allowable length

30m

1.5m

20m

Liquid pipe

Gas pipe

O.D.  6.4mm

O.D. 12.7mm

20g/m

Additional refrigerant 
required for refrigerant 
pipe exceeding 10m 
in length.

**

*

*

 Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.

**

 The suggested shortest pipe length is 1.5m, in order to avoid 

noise from the outdoor unit and vibration. 

(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.)

When connecting the FVXS indoor unit, the shortest piping 

length should be no less than around 2.5m.

01_EN_3P254362-2C.fm  Page 3  Friday, November 12, 2010  2:28 PM

Summary of Contents for RXS50J2V1B

Page 1: ...ds Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R...

Page 2: ...EC 3SB64564 9D RXS60F3V1B RKS60F3V1B RXS50G2V1B RKS50G2V1B ARXS50G2V1B ARXS50E3V1B RXS60F2V1B RKS60F2V1B RYN50E3V1B RYN60E3V1B RN50E3V1B RN60E3V1B RX50G2V1B RX60G2V1B Shinri Sada Manager Quality Contr...

Page 3: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 14E RXS50J2V1B RKS50J2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 KEMA Quality B...

Page 4: ...ls If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrige...

Page 5: ...8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit a...

Page 6: ...ntres 580mm 120mm From unit s side Max allowable height Min allowable length Max allowable length 30m 1 5m 20m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm 20g m Additional refrigerant required for refri...

Page 7: ...door Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necess...

Page 8: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 9: ...p valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping an...

Page 10: ...ensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 12 7mm O D 6 4mm I D 14...

Page 11: ...tart Forced cooling operation will stop automatically after around 15 minutes To force a trial operation to stop press the forced operation switch SW1 Facility Setting Switch cooling only model coolin...

Page 12: ...e limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power s...

Page 13: ...protection the system disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts s...

Page 14: ...1101 HT 3P254362 2C M09B391 Two dimensional bar code is a code for manufacturing 00_CV_3P254362 2C fm Page 2 Thursday November 11 2010 1 09 PM...

Reviews: