Outdoor Unit Installation

6.

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A
Fill from the liquid pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.

1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering. 

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official 
national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. 
Sticking instructions are illustrated on the backside of that label. 

7.

Refrigerant piping work

7-1 Caution on pipe handling 

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for 

bending.

7-2 Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 12.7mm

O.D. 6.4mm

I.D. 14-16mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

40mm or more

30mm or more

Thickness 0.8mm (C1220T-O)

Filling a cylinder with an attached siphon

Stand the cylinder upright when 
filling.

There is a siphon pipe inside, so the 
cylinder need not be upside-down to 
fill with liquid.

Filling other cylinders

Turn the cylinder upside-down 
when filling.

3

5

6

2

1

4

Please fill in with indelible ink, 

n

1

  the factory refrigerant charge of the product, 

n

2

  the additional refrigerant amount charged in the field and

n

1  +  2

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

 

(1) 

GWP = global warming potential 

1

factory refrigerant charge of the 
product: 
see unit name plate 

2

additional refrigerant amount 
charged in the field 

3

total refrigerant charge 

4

Contains fluorinated greenhouse 
gases covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port (e.g. 
onto the inside of the stop valve cover).

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wire

01_EN_3P254362-2C.fm  Page 7  Friday, November 12, 2010  2:28 PM

Summary of Contents for RXS50J2V1B

Page 1: ...ds Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R...

Page 2: ...EC 3SB64564 9D RXS60F3V1B RKS60F3V1B RXS50G2V1B RKS50G2V1B ARXS50G2V1B ARXS50E3V1B RXS60F2V1B RKS60F2V1B RYN50E3V1B RYN60E3V1B RN50E3V1B RN60E3V1B RX50G2V1B RX60G2V1B Shinri Sada Manager Quality Contr...

Page 3: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 14E RXS50J2V1B RKS50J2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 KEMA Quality B...

Page 4: ...ls If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrige...

Page 5: ...8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit a...

Page 6: ...ntres 580mm 120mm From unit s side Max allowable height Min allowable length Max allowable length 30m 1 5m 20m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm 20g m Additional refrigerant required for refri...

Page 7: ...door Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necess...

Page 8: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 9: ...p valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping an...

Page 10: ...ensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 12 7mm O D 6 4mm I D 14...

Page 11: ...tart Forced cooling operation will stop automatically after around 15 minutes To force a trial operation to stop press the forced operation switch SW1 Facility Setting Switch cooling only model coolin...

Page 12: ...e limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power s...

Page 13: ...protection the system disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts s...

Page 14: ...1101 HT 3P254362 2C M09B391 Two dimensional bar code is a code for manufacturing 00_CV_3P254362 2C fm Page 2 Thursday November 11 2010 1 09 PM...

Reviews: