English

Wiring

WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN61000-3-12

(1)

• Do not turn on the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).

2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead 
screwdriver be used to tighten the screws. 

NOTE

(1)

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public 
low-voltage systems with input current >16 A and 

75 A per phase.

Observe the notes mentioned following when wiring to the power supply 
terminal board.
Precautions to be taken for power supply wiring. 
Use a round crimp-style terminal for connection to the power supply  terminal 
board. In case it cannot be used due to unavoidable reasons, be sure to 
observe the following instruction. 
Place the round crimp-style terminals on the wires up to the covered part and 
secure in place. 

• Ground terminal installation 

Use the following method when installing the round 
crimp-style terminal. 

1
2
3

1 2 3

L N

Safety 
breaker 
20A

Earth leakage 
circuit breaker

Earth

When wire length exceeds 
10m, use 2.0mm diameter wires.

H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power
supply
50Hz 220-240V 

Firmly fix the wires with 
the terminal screws.

Use 2.0mm diameter wires.

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer 
so wire terminations will not 
receive external stress.

Power supply 
terminal block

L

N

1

2

3

Shape wires so that the 
service lid and stop 
valve cover fit securely.

Stranded wire

Round crimp-style
terminal

Round crimp-
style terminal

Flat washer

Screw

Flat washer

Round crimp-
style terminal

Screw

Good

Wrong

01_EN_3P254362-2C.fm  Page 9  Friday, November 12, 2010  2:28 PM

Summary of Contents for RXS50J2V1B

Page 1: ...ds Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R...

Page 2: ...EC 3SB64564 9D RXS60F3V1B RKS60F3V1B RXS50G2V1B RKS50G2V1B ARXS50G2V1B ARXS50E3V1B RXS60F2V1B RKS60F2V1B RYN50E3V1B RYN60E3V1B RN50E3V1B RN60E3V1B RX50G2V1B RX60G2V1B Shinri Sada Manager Quality Contr...

Page 3: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 14E RXS50J2V1B RKS50J2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 KEMA Quality B...

Page 4: ...ls If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrige...

Page 5: ...8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit a...

Page 6: ...ntres 580mm 120mm From unit s side Max allowable height Min allowable length Max allowable length 30m 1 5m 20m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm 20g m Additional refrigerant required for refri...

Page 7: ...door Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necess...

Page 8: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 9: ...p valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping an...

Page 10: ...ensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 12 7mm O D 6 4mm I D 14...

Page 11: ...tart Forced cooling operation will stop automatically after around 15 minutes To force a trial operation to stop press the forced operation switch SW1 Facility Setting Switch cooling only model coolin...

Page 12: ...e limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power s...

Page 13: ...protection the system disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts s...

Page 14: ...1101 HT 3P254362 2C M09B391 Two dimensional bar code is a code for manufacturing 00_CV_3P254362 2C fm Page 2 Thursday November 11 2010 1 09 PM...

Reviews: