Outdoor Unit Installation Drawings

(F

oot bolt-hole 

centres)

311

574

(Foot bolt-hole centres)

(From unit’

s side)

105.5

CAUTION

**Set the piping length 

from 1.5m to 20m.

Wrap the insulation pipe with 
the finishing tape from bottom 
to top.

In sites with poor drainage, use 
block bases for outdoor unit.  
Adjust foot height until the unit 
is leveled.  Otherwise, water 
leakage or pooling of water may 
occur.

Where there is a danger of the unit 
falling, use foot bolts, or wires.

250mm from wall

unit: mm

O.D. 9.5mm

Gas pipe

Liquid pipe

O.D. 6.4mm

20g/m

15m

20m

Max. allowable length

Max. allowable height

Additional refrigerant
required for refrigerant
pipe exceeding
10m in length.

*

 Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.

**

 The suggested shortest pipe length is 1.5m, in order to avoid 

noise from the outdoor unit and vibration. 

(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.)

How to remove the stop 
valve cover

Remove the screw on the 
stop valve cover.
Slide the lid downward 
to remove it.

How to attach the stop 
valve cover

Insert the upper part of 
the stop valve cover into the 
outdoor unit to install.
Tighten the screws.

Stop valve cover

1.5m

Min. allowable length

**

*

Allow space for piping 
and electrical servicing.

01_EN_3P203824-12L.fm  Page 3  Thursday, October 18, 2012  10:39 AM

Summary of Contents for RXS42K2V1B

Page 1: ...Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie...

Page 2: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 13E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS42J2V1B RKS42J2V1B KEMA Quality B...

Page 3: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 19F Shinri Sada Manager Quality Control Department RXS42K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 5: ...s If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refriger...

Page 6: ...In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit any...

Page 7: ...itional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested sh...

Page 8: ...oor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessa...

Page 9: ...e nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly...

Page 10: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 11: ...dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D...

Page 12: ...l operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Press bo...

Page 13: ...re the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facilit...

Page 14: ...e systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round cr...

Page 15: ...n in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode I...

Page 16: ...1210 HT 3P203824 12L M12B149 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 12L fm Page 2 Thursday October 18 2012 10 38 AM...

Reviews: