English

Facility Setting

 

(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in 
a residence or office (the space where there is a human).

Cutting jumper4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 
temperature drops below –20°C and start back up once the temperature rises again.
1) Remove the 2 screws on the side and remove the top plate of the outdoor unit. 
2) Remove 1 screw from the upper electric box cover.  
3) Remove the upper electric box cover by sliding it, being careful not to bend the electric box hook.
4) Remove the lower electric box cover. 
5) Cut the jumper (J4) of the PCB inside. 
6) Go back through step 4)

 →

 3)

 →

 2) 

→ 

1). Make sure all components are well secured when doing this. 

 CAUTION

• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifier might cause dew jumping from the indoor unit outlet vent.

• Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.
• When removing the upper electric box cover, be careful not to bend the hook. 
• When returning the lower electric box cover, return the notch to the stop valve side. 
• When returning the upper electric box cover, be careful not to pinch the fan motor lead wire.

Top plate

Upper electric 
box cover

Notch

PCB

Lower electric 
box cover

1) Remove the 

2 screws.

2) Remove the 

1 screw.

4) Remove the lower 

electric box cover.

3) Remove the upper 

electric box cover 
from the hook.

J3

J4

J5

PCB

5) Cut jumper J4.

Hook

Fan motor lead wire

Electric box

01_EN_3P203824-12L.fm  Page 9  Thursday, October 18, 2012  10:39 AM

Summary of Contents for RXS42K2V1B

Page 1: ...Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie...

Page 2: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 13E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS42J2V1B RKS42J2V1B KEMA Quality B...

Page 3: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 19F Shinri Sada Manager Quality Control Department RXS42K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 5: ...s If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refriger...

Page 6: ...In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit any...

Page 7: ...itional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested sh...

Page 8: ...oor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessa...

Page 9: ...e nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly...

Page 10: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 11: ...dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D...

Page 12: ...l operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Press bo...

Page 13: ...re the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facilit...

Page 14: ...e systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round cr...

Page 15: ...n in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode I...

Page 16: ...1210 HT 3P203824 12L M12B149 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 12L fm Page 2 Thursday October 18 2012 10 38 AM...

Reviews: