Safety Precautions

• The precautions described herein are classified as WARNING and CAUTION. They both contain important 

information regarding safety. Be sure to observe all precautions without fail. 

• Meaning of WARNING and CAUTION notices 

WARNING .... Failure to follow these instructions properly may result in personal injury or loss of life. 

CAUTION ..... Failure to observe these instructions properly may result in property damage or personal injury, which 

may be serious depending on the circumstances. 

• The safety marks shown in this manual have the following meanings: 

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate 

the air conditioner and take care of it with the aid of the operation manual. 

Be sure to follow the instructions. 

Be sure to establish an earth connection. 

Never attempt. 

WARNING

• Ask your dealer or qualified personnel to carry out installation work. 

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire. 

• Install the air conditioner in accordance with the instructions in this installation manual. 

Improper installation may result in water leakage, electric shocks or fire. 

• Be sure to use only the specified accessories and parts for installation work. 

Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. 

A foundation of insufficient strength may result in the equipment falling and causing injury. 

• Electrical work must be performed in accordance with relevant local and national regulations and with instructions 

in this installation manual. Be sure to use a dedicated power supply circuit only. 

Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

• Use a cable of suitable length. 

Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire. 

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires. 

Improper connections or securing of wires may result in abnormal heat build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires 

so that the control box lid can be securely fastened. 

Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks during installation, ventilate the area immediately. 

Toxic gas may be produced if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage. 

Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker. 

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, 

and use only the specified refrigerant (R410A). 

The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even injury. 

• During installation, attach the refrigerant piping securely before running the compressor. 

If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal 
pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• During pump-down, stop the compressor before removing the refrigerant piping. 

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks. 

• Be sure to install an earth leakage breaker. 

Failure to install an earth leakage breaker may result in electric shocks or fire. 

CAUTION

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out. 

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and 

insulate piping to prevent condensation. 

Improper drain piping may result in indoor water leakage and property damage. 

• Tighten the flare nut according to the specified method such as with a torque wrench. 

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. 

• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

• The temperature of refrigerant circuit will be high, please keep the inter-unit wire away from copper pipes that are 

not thermally insulated.

01_EN_3P203824-12L.fm  Page 1  Thursday, October 18, 2012  10:39 AM

Summary of Contents for RXS42K2V1B

Page 1: ...Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie...

Page 2: ...USTRIES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 13E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS42J2V1B RKS42J2V1B KEMA Quality B...

Page 3: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 19F Shinri Sada Manager Quality Control Department RXS42K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 5: ...s If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refriger...

Page 6: ...In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit any...

Page 7: ...itional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested sh...

Page 8: ...oor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessa...

Page 9: ...e nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly...

Page 10: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 11: ...dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D...

Page 12: ...l operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Press bo...

Page 13: ...re the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facilit...

Page 14: ...e systems with input current 16 A and 75 A per phase Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round cr...

Page 15: ...n in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode I...

Page 16: ...1210 HT 3P203824 12L M12B149 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 12L fm Page 2 Thursday October 18 2012 10 38 AM...