• Split - Sky Air • RXS-L3
17
• Outdoor Unit • RXS-L3
4
Capacity tables
4 - 1 Cooling/Heating Capacity Tables
AFR
15,0
BF
0,08
EWB
EDB
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14,0
20,0
3,48
3,13
0,65
3,33
3,06
0,72
3,17
2,99
0,78
3,10
2,96
0,80
3,01
2,92
0,84
2,85
2,85
0,91
16,0
22,0
3,64
3,09
0,66
3,48
3,02
0,72
3,32
2,95
0,78
3,26
2,93
0,81
3,17
2,89
0,85
3,01
2,82
0,91
18,0
25,0
3,80
3,31
0,66
3,64
3,25
0,72
3,48
3,18
0,79
3,42
3,16
0,81
3,32
3,12
0,85
3,16
3,06
0,91
19,0
27,0
3,87
3,56
0,66
3,72
3,50
0,73
3,56
3,44
0,79
3,49
3,41
0,81
3,40
3,38
0,85
3,24
3,32
0,91
22,0
30,0
4,11
3,46
0,67
3,95
3,41
0,73
3,79
3,35
0,79
3,73
3,33
0,82
3,63
3,30
0,86
3,48
3,25
0,92
24,0
32,0
4,27
3,39
0,67
4,11
3,34
0,74
3,95
3,30
0,80
3,89
3,28
0,82
3,79
3,25
0,86
3,63
3,20
0,92
AFR
15,0
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
2,69
0,85
3,14
0,89
3,60
0,93
4,14
0,98
4,50
1,01
2,55
0,87
3,01
0,91
3,46
0,95
4,00
1,00
4,36
1,03
2,50
0,88
2,95
0,92
3,40
0,96
3,94
1,01
4,31
1,04
2,44
0,89
2,90
0,93
3,35
0,97
3,89
1,02
4,25
1,05
2,42
0,89
2,87
0,93
3,32
0,97
3,86
1,02
4,22
1,06
2,36
0,90
2,81
0,94
3,26
0,98
3,81
1,03
4,17
1,06
27,0
°C
15,0
20,0
22,0
24,0
25,0
EDB
Ͳ
10,0
Ͳ
5,0
0,0
6,0
10,0
20,0
25,0
30,0
32,0
35,0
40,0
Symbols
Air
flow
rate
[m³/min]
Bypass
factor
Entering
wet
Ͳ
bulb
temperature
(°C
WB)
Entering
dry
Ͳ
bulb
temperature
(°C
DB)
Total
capacity
[kW]
Sensible
heat
capacity
[kW]
Power
input
[kW]
Indoor
Outdoor
temperature
[°C
DB]
Cooling
50Hz
220
Ͳ
240V
Heating
50Hz
220
Ͳ
240V
Indoor
Outdoor
temperature
[°C
WB]
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
FBQ35D2VEB
+
RXS35L3V1B
Notes
The
ratings
shown
are
net
capacities
which
include
a
deduction
for
indoor
fan
motor
heat.
The
bold
cells
indicate
the
standard
conditions.
The
total
capacity,
power
input
and
sensible
heat
capacity
must
be
calculated
by
interpolation,
using
the
figures
in
the
table
(figures
not
in
the
table
may
not
be
used
in
the
calculation).
In
case
the
sensible
heat
capacity
is
not
mentioned
in
the
table,
please
calculate
it
using
an
approximation
between
two
values
in
direct
proportion.
The
capacities
are
based
on
the
following
conditions:
Corresponding
refrigerant
piping
length:
5
m
Level
difference:
0m
The
air
flow
rate
and
bypass
factor
are
mentioned
in
the
table.
1)
2)
3)
4)
5)
6)
3D095138A