![background image](http://html1.mh-extra.com/html/daikin/rxs-l3/rxs-l3_technical-data-manual_2459939011.webp)
3
2
• Split - Sky Air • RXS-L3
9
• Outdoor Unit • RXS-L3
2
Specifications
Notes
(1) Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
(2) 220V
(3) 230V
(4) 240V
(5) EER/COP according to Eurovent 2012, for use outside EU only
Notes
(1) EER/COP according to Eurovent 2012, for use outside EU only
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
B
Pdesign
kW
3.50
SEER
4.87
Annual energy
consumption
kWh
252
Heating (Average
climate)
Energy label
A
Pdesign
kW
2.90
SCOP/A
3.80
Annual energy
consumption
kWh
1,068
Piping connections
Liquid
OD
mm
6.35
Gas
OD
mm
9.5
Drain
OD
mm
18.0
Heat insulation
Both liquid and gas pipes
Current
Nominal running
current (RLA) - 50Hz
Cooling
A
5.70 (2) / 5.49 (3) / 5.27 (4)
Heating
A
5.60 (2) / 5.30 (3) / 5.10 (4)
Nominal efficiency
EER
2.88 (5)
COP
3.57 (5)
Annual energy consumption
kWh
608
Energy label
Cooling
B
Heating
A
2-8 Capacity and Power input
FNQ25A/RXS25L3
FNQ35A/RXS35L3
Cooling capacity
Nom.
kW
2.6
3.4
Heating capacity
Nom.
kW
3.20
4.00
Power input
Cooling
Nom.
kW
0.69
1.11
Heating
Nom.
kW
0.80
1.15
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
A+
Pdesign
kW
2.60
3.40
SEER
5.63
5.65
Annual energy
consumption
kWh
162
211
Heating (Average
climate)
Energy label
A+
Pdesign
kW
2.80
2.90
SCOP/A
4.24
4.05
Annual energy
consumption
kWh
925
1,002
Nominal efficiency
EER
3.77 (1)
3.06 (1)
COP
4.00 (1)
3.48 (1)
Annual energy consumption
kWh
345
556
Energy label
Cooling
A
B
Heating
A
B
2-7 Capacity and Power input
FLXS35B9/RXS35L3
Summary of Contents for RXS-L3