10 Commissioning

Installation manual

15

RXM-A, ARXM-A
R32 split series
3P645642-6L – 2023.07

WARNING

Before  connecting  or  disconnecting  the  connector,  make
sure the power supply is turned OFF.

INFORMATION

Selective  connector  for  standby  electricity  saving  is
required if other than applicable indoor unit is connected.

9.2.2

To turn ON standby electricity saving
function

Prerequisite: 

The main power supply MUST be turned OFF.

1

Remove the service cover.

2

Disconnect the selective standby electricity saving connector.

3

Turn ON the main power supply.

10

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

10.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

3

Power up the unit.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between
the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The indoor unit receives the signals of the 

user interface

.

The  specified  wires  are  used  for  the 

interconnection

cable

.

The 

fuses, circuit breakers,

 or locally installed protection

devices  are  installed  according  to  this  document,  and
have NOT been bypassed.

10.2

Checklist during commissioning

To perform an 

air purge

.

To perform a 

test run

.

10.3

To perform a test run

INFORMATION

If the unit runs into an error during commissioning, see the
service manual for the detailed troubleshooting guidelines.

Prerequisite: 

The power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Refer  to  the  operation  manual  of  the  indoor  unit  for

setting temperature, operation mode….

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
The test run can be disabled if necessary.

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

Make sure that all functions and parts are working properly.

4

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

Summary of Contents for RXM50A5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXM50A5V1B ARXM50A5V1B ...

Page 2: ...in A and judged positively by B according to the Certificate C as set out in the Technical Construction File D and judged positively by E Applied module F according to the Certificate G Risk category H Also refer to next page wie in A aufgeführt und von B positiv beurteilt gemäß Zertifikat C wie in der Technischen Konstruktionsakte D aufgeführt und von E Angewandtes Modul F positiv ausgezeichnet p...

Page 3: ...tilling av sikkerhetsanordning for trykk P bar Produksjonsnummer og produksjonsår se modellens merkeplate Suurin sallittu paine PS K bar Pienin suurin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximáln...

Page 4: ... I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032F3 10 2023 D DAIKIN TCF PED 0304A E HPi VS Ltd NB1521 F D1 G II H as set out in A and judged positively by B according to the Certificate C as set out in the Technical Construction File D and judged positively by E A...

Page 5: ... C TSmax Saturated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q HPi Verification Services Ltd The Manor House Howbery Business Park Wallingford OX10 8BA United Kingdom Name and address of the Notified body that judged positively on compliance with the...

Page 6: ...nd service 16 12 Troubleshooting 16 12 1 Fault diagnosis using LED on outdoor unit PCB 16 13 Disposal 16 14 Technical data 16 14 1 Wiring diagram 16 14 1 1 Unified wiring diagram legend 16 14 2 Piping diagram 18 14 2 1 Piping diagram Outdoor unit 18 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instruc...

Page 7: ...se new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished Charging refrigerant see 6 Charging refrigerant 412 WA...

Page 8: ...e air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 416 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Dis...

Page 9: ... sound is measured under actual installation conditions the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA The outdoor unit is designed for outdoor installation only and for ambient temperatures specified in the table below unless othe...

Page 10: ...es so that the evacuated condensate CANNOT freeze 1 Install drain caps 1 and 2 accessory Make sure the edges of the drain caps close off the holes completely a b a Bottom frame b Drain cap 2 Install the drain socket a c b b b a a a Drain hole Install a drain cap 2 b Drain hole Install a drain cap 1 c Drain hole for drain socket 5 Piping installation 5 1 Preparing refrigerant piping 5 1 1 Refrigera...

Page 11: ... type 5 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage WARNING Connect the refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause a...

Page 12: ...e unit until a service person confirms that the part from which the refrigerant leaked has been repaired WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources e g open flames an operating gas appliance or an operating electric heater The room size shall be as specified in the General safety precaution ...

Page 13: ...ctrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qu...

Page 14: ...ties such as equipment of computer rooms NEVER use in a residence or office where people occupy the space 9 1 1 To set the facility mode When cutting jumper J6 on the PCB the operation range will expand to 15 C The facility mode will stop if the outdoor temperature drops below 20 C and resume when the temperature rises again To cut jumper J6 1 Remove the top plate of the outdoor unit 2 Remove the ...

Page 15: ...of the indoor and outdoor units There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open The following field wiring has been carried out according to this document and the applicable legislation between the outdoor unit and the...

Page 16: ...Measure the voltage at the terminals of main circuit capacitors or electrical components before servicing 12 Troubleshooting 12 1 Fault diagnosis using LED on outdoor unit PCB LED is Diagnosis flashing Normal Check the indoor unit ON Turn the power OFF and back ON and check the LED within approximately 3 minutes If the LED is ON again the outdoor unit PCB is faulty OFF 1 Supply voltage for power s...

Page 17: ...lligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor Symbol Meaning MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated g...

Page 18: ...egory II Other equipment art 4 3 A B Piping diagram legend Liquid stop valve Gas stop valve Muffler Muffler with filter Electronic expansion valve Filter Propeller fan High pressure switch automatic reset Thermistor Capillary tube 4 way valve Accumulator Compressor Heat exchanger Distributor Piping diagram legend Refrigerant flow Cooling Refrigerant flow Heating A Field piping liquid 6 4 CuT B Fie...

Page 19: ......

Page 20: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P645642 6L 2023 07 Copyright 2023 Daikin Verantwortung für Energie und Umwelt ...

Reviews: