6 Charging refrigerant

Installation manual

12

RXM-A, ARXM-A

R32 split series

3P645642-6L – 2023.07

5.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT open the stop valves before the vacuum drying is
finished.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

6

Charging refrigerant

6.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

Periodical  inspections  for  refrigerant  leaks  may  be  required
depending  on  the  applicable  legislation.  Contact  your  installer  for
more information.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

6.2

To determine the additional
refrigerant amount

If the total liquid

piping length is…

Then…

≤10 m

Do NOT add additional refrigerant.

>10 m

R=(total length (m) of liquid
piping⁠–⁠10 m)×0.020

R=Additional charge (kg) (rounded in units
of 0.01 kg)

INFORMATION

Piping length is the one-way length of liquid piping.

6.3

To determine the complete
recharge amount

INFORMATION

If  a  complete  recharge  is  necessary,  the  total  refrigerant
charge  is:  the  factory  refrigerant  charge  (see  unit  name
plate) + the determined additional amount.

6.4

To charge additional refrigerant

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

Prerequisite: 

Before charging refrigerant, make sure the refrigerant

piping is connected and checked (leak test and vacuum drying).

1

Connect the refrigerant cylinder to the service port.

2

Charge the additional refrigerant amount.

3

Open the gas stop valve.

6.5

To check refrigerant piping joints
for leaks after charging refrigerant

1

Perform  the  leak  tests  see 

"5.3  Checking  the  refrigerant

piping"

 [

4

 11].

Summary of Contents for RXM50A5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXM50A5V1B ARXM50A5V1B ...

Page 2: ...in A and judged positively by B according to the Certificate C as set out in the Technical Construction File D and judged positively by E Applied module F according to the Certificate G Risk category H Also refer to next page wie in A aufgeführt und von B positiv beurteilt gemäß Zertifikat C wie in der Technischen Konstruktionsakte D aufgeführt und von E Angewandtes Modul F positiv ausgezeichnet p...

Page 3: ...tilling av sikkerhetsanordning for trykk P bar Produksjonsnummer og produksjonsår se modellens merkeplate Suurin sallittu paine PS K bar Pienin suurin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximáln...

Page 4: ... I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032F3 10 2023 D DAIKIN TCF PED 0304A E HPi VS Ltd NB1521 F D1 G II H as set out in A and judged positively by B according to the Certificate C as set out in the Technical Construction File D and judged positively by E A...

Page 5: ... C TSmax Saturated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q HPi Verification Services Ltd The Manor House Howbery Business Park Wallingford OX10 8BA United Kingdom Name and address of the Notified body that judged positively on compliance with the...

Page 6: ...nd service 16 12 Troubleshooting 16 12 1 Fault diagnosis using LED on outdoor unit PCB 16 13 Disposal 16 14 Technical data 16 14 1 Wiring diagram 16 14 1 1 Unified wiring diagram legend 16 14 2 Piping diagram 18 14 2 1 Piping diagram Outdoor unit 18 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instruc...

Page 7: ...se new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished Charging refrigerant see 6 Charging refrigerant 412 WA...

Page 8: ...e air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 416 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Dis...

Page 9: ... sound is measured under actual installation conditions the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA The outdoor unit is designed for outdoor installation only and for ambient temperatures specified in the table below unless othe...

Page 10: ...es so that the evacuated condensate CANNOT freeze 1 Install drain caps 1 and 2 accessory Make sure the edges of the drain caps close off the holes completely a b a Bottom frame b Drain cap 2 Install the drain socket a c b b b a a a Drain hole Install a drain cap 2 b Drain hole Install a drain cap 1 c Drain hole for drain socket 5 Piping installation 5 1 Preparing refrigerant piping 5 1 1 Refrigera...

Page 11: ... type 5 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage WARNING Connect the refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause a...

Page 12: ...e unit until a service person confirms that the part from which the refrigerant leaked has been repaired WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources e g open flames an operating gas appliance or an operating electric heater The room size shall be as specified in the General safety precaution ...

Page 13: ...ctrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qu...

Page 14: ...ties such as equipment of computer rooms NEVER use in a residence or office where people occupy the space 9 1 1 To set the facility mode When cutting jumper J6 on the PCB the operation range will expand to 15 C The facility mode will stop if the outdoor temperature drops below 20 C and resume when the temperature rises again To cut jumper J6 1 Remove the top plate of the outdoor unit 2 Remove the ...

Page 15: ...of the indoor and outdoor units There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open The following field wiring has been carried out according to this document and the applicable legislation between the outdoor unit and the...

Page 16: ...Measure the voltage at the terminals of main circuit capacitors or electrical components before servicing 12 Troubleshooting 12 1 Fault diagnosis using LED on outdoor unit PCB LED is Diagnosis flashing Normal Check the indoor unit ON Turn the power OFF and back ON and check the LED within approximately 3 minutes If the LED is ON again the outdoor unit PCB is faulty OFF 1 Supply voltage for power s...

Page 17: ...lligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor Symbol Meaning MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated g...

Page 18: ...egory II Other equipment art 4 3 A B Piping diagram legend Liquid stop valve Gas stop valve Muffler Muffler with filter Electronic expansion valve Filter Propeller fan High pressure switch automatic reset Thermistor Capillary tube 4 way valve Accumulator Compressor Heat exchanger Distributor Piping diagram legend Refrigerant flow Cooling Refrigerant flow Heating A Field piping liquid 6 4 CuT B Fie...

Page 19: ......

Page 20: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P645642 6L 2023 07 Copyright 2023 Daikin Verantwortung für Energie und Umwelt ...

Reviews: