background image

9

n

English

Facility Setting 
(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in 
a residence or office (the space where there is a human).

n

Cutting jumper 4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 
temperature drops below –20°C and start back up once the temperature rises again.

1) Remove the two screws on the side and remove the top plate of the outdoor unit. 

2) Remove one screw from the upper electric box cover.  

3) Remove the upper electric box cover by sliding it, being careful not to bend the electric box hook.

4) Remove the lower electric box cover. 

5) Cut the jumper (J4) of the PCB inside. 

6) Go back through step 4) 

 3) 

 2) 

 1). Make sure all components are well secured when doing this. 

 CAUTION

1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifier might cause dew jumping from the indoor unit outlet vent.

4) Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.
5) When removing the upper electric box cover, be careful not to bend the hook. 
6) When returning the lower electric box cover, return the notch to the stop valve side. 
7) When returning the upper electric box cover, be careful not to pinch the fan motor lead wire.

Top plate

Upper electric 
box cover

Notch

PCB

Lower electric 
box cover

1) Remove the 

two screws.

2) Remove the 

one screw.

4) Remove the lower 

electric box cover.

3) Remove the upper 

electric box cover 
from the hook.

J3

J4

J5

PCB

5) Cut jumper J4.

Hook

Fan motor lead wire

Electric box

Summary of Contents for RXL42J3V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series MODEL RXL42K2V1B RXL42J3V1B...

Page 2: ...n A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com...

Page 3: ...se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelec...

Page 4: ...es so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during install...

Page 5: ...aces with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away...

Page 6: ...top valve cover into the outdoor unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Additional refrige...

Page 7: ...g fix the unit securely by means of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation b...

Page 8: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them f...

Page 9: ...s from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no...

Page 10: ...piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal i...

Page 11: ...To force a test run to stop press the indoor unit operation stop button n Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button...

Page 12: ...outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall 2 Intermittent noises may be produced by the indoor unit due to the outdoor fan turnin...

Page 13: ...rve the notes mentioned below when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply termina...

Page 14: ...C75 C94 C95 Capacitor DB1 DB2 DB3 Diode bridge FU1 FU2 FU3 FU4 FU5 Fuse FU6 Field fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor S1T Thermostat M1F Fan motor MRCW...

Page 15: ...ioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If t...

Page 16: ...3P327449 4F 2013 06 Copyright 2013 Daikin...

Reviews: