background image

7

n

English

Outdoor Unit Installation

5.

Refilling the refrigerant.

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A
Fill from the liquid pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.

1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official 
national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. 
Sticking instructions are illustrated on the backside of that label. 

6.

Refrigerant piping work.

6-1 Cautions on pipe handling.

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

6-2 Selection of copper and heat insulation materials.

When using commercial copper pipes and fittings, observe the following:

1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh •°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe 

thermal insulation

Liquid pipe 

thermal insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

Filling a cylinder with an attached siphon

Stand the cylinder upright when 
filling.

There is a siphon pipe inside, so the 
cylinder need not be upside-down to 
fill with liquid.

Filling other cylinders

Turn the cylinder upside-down 
when filling.

3

5

6

2

1

4

Please fill in with indelible ink, 

n

1

  the factory refrigerant charge of the product, 

n

2

  the additional refrigerant amount charged in the field and

n

1  +  2

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

 

(1) 

GWP = global warming potential 

1

factory refrigerant charge of the 
product: 
see unit name plate 

2

additional refrigerant amount 
charged in the field 

3

total refrigerant charge 

4

Contains fluorinated greenhouse 
gases covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port (e.g. 
onto the inside of the stop valve cover).

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Summary of Contents for RXL42J3V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series MODEL RXL42K2V1B RXL42J3V1B...

Page 2: ...n A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com...

Page 3: ...se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelec...

Page 4: ...es so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during install...

Page 5: ...aces with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away...

Page 6: ...top valve cover into the outdoor unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Additional refrige...

Page 7: ...g fix the unit securely by means of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation b...

Page 8: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them f...

Page 9: ...s from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no...

Page 10: ...piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal i...

Page 11: ...To force a test run to stop press the indoor unit operation stop button n Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button...

Page 12: ...outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall 2 Intermittent noises may be produced by the indoor unit due to the outdoor fan turnin...

Page 13: ...rve the notes mentioned below when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply termina...

Page 14: ...C75 C94 C95 Capacitor DB1 DB2 DB3 Diode bridge FU1 FU2 FU3 FU4 FU5 Fuse FU6 Field fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor S1T Thermostat M1F Fan motor MRCW...

Page 15: ...ioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If t...

Page 16: ...3P327449 4F 2013 06 Copyright 2013 Daikin...

Reviews: