SiBE041012
Indoor Unit
Removal Procedure
139
1.10 Removal of lndoor Heat Exchanger
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. Disconnect the refrigerant
piping.
Caution
In pump-down work, be sure
to stop the compressor
before disconnecting the
refrigerant pipe. If the
refrigerant pipe is
disconnected with the
compressor operating and
the stop valve open, air may
be sucked in to generate an
over-pressure in refrigeration
cycle, thus resulting in pipe
rupture or accidental injury.
Place a plastic sheet under
the drain pan to prevent from
wetting the floor with
remaining drain.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
Carry out the removal works
with 2 wrench.
When the pipings are
disconnected, protect the
both openings of pipe side
and unit side from entering
of moisture.
1
Remove the screws
fixed to the installation
plate.
2
Hold the indoor unit up
with a block.
Disconnect the piping
with 2 wrenches.
2. Remove the indoor unit.
1
Detach the indoor unit
from the installation
plate.
(R12140)
(R12141)
Block
Installation
plate
(R12142)