4 Installation

Installation manual

9

RXF50+60A2V1B

R32 split series

3P512025-3 – 2017.11

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate

measures  so  that  the  evacuated  condensate  CANNOT

freeze.

INFORMATION

For  information  on  the  available  options,  contact  your

dealer.

NOTICE

Provide  at  least 

300 

mm  of  free  space  below  the  unit.

Additionally,  make  sure  the  unit  is  positioned  at  least

100 mm above the expected level of snow.

1

Use a drain plug for drainage.

2

Use a Ø16 mm hose (field supply).

b

c

d

a

a

Drain port

b

Bottom frame

c

Drain plug

d

Hose (field supply)

4.2.4

To prevent the outdoor unit from falling
over

In case the unit is installed in places where strong wind can tilt the

unit, take following measure:

1

Prepare 2 cables as indicated in the following illustration (field

supply).

2

Place the 2 cables over the outdoor unit.

3

Insert a rubber sheet between the cables and the outdoor unit

to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

4.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the indoor unit
▪ Connecting the refrigerant piping to the outdoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:

▪ Pipe bending
▪ Flaring pipe ends
▪ Using the stop valves

4.3.2

Precautions when connecting the
refrigerant piping

DANGER: RISK OF BURNING

CAUTION

▪ Use the flare nut fixed to the main unit.
▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

WARNING

Connect the refrigerant piping securely before running the

compressor. If the refrigerant piping is NOT connected and

the stop valve is open when the compressor is run, air will

be  sucked  in.  This  will  cause  abnormal  pressure  in  the

refrigeration cycle, which may result in equipment damage

and even injury.

Summary of Contents for RXF50A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50A2V1B RXF60A2V1B...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...vat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direkti...

Page 4: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 5: ...the electrical wiring 12 4 6 2 Specifications of standard wiring components 12 4 6 3 To connect the electrical wiring on the outdoor unit 12 4 7 Finishing the outdoor unit installation 12 4 7 1 To fin...

Page 6: ...ient place for carrying the unit in and out of the site Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Provide sufficient space around...

Page 7: ...3 2 Preparing refrigerant piping 3 2 1 Refrigerant piping requirements Piping material Phosphoric acid deoxidised seamless copper Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 12 7 mm 1 2 Piping...

Page 8: ...ee space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow In this case it is recommended to construct a pedestal 330 5 8 0 2 4 0 2...

Page 9: ...unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten those ends 4 3 Connecting the refrigerant piping DANGER RISK OF BURNING 4 3 1 About connecting the re...

Page 10: ...old pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the following Chec...

Page 11: ...NFORMATION Piping length is the one way length of liquid piping 4 5 4 To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the fact...

Page 12: ...lation Interconnection cable indoor outdoor 4 core cable 1 5 mm and applicable for 220 240 V Recommended field fuse 15 A Earth leakage circuit breaker MUST comply with applicable legislation 4 6 3 To...

Page 13: ...F INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 5 4 Starting up the outdoor unit See...

Page 14: ...t ON OFF switch if present on the indoor unit using the indoor unit user interface Method 1 Using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result Operation will s...

Page 15: ...REAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC...

Page 16: ...3 2017 11 7 2 Piping diagram 7 2 1 Piping diagram Outdoor unit RXF60A2V1B PED categories of equipment High pressure switches category IV Compressor category II Other art 4 3 equipment Note When the hi...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 3 2017 11 Copyright 2017 Daikin...

Reviews: