5 Commissioning

Installation manual

12

RXF50+60A2V1B

R32 split series

3P512025-3 – 2017.11

WARNING

If the supply cord is damaged, it MUST be replaced by the

manufacturer,  its  service  agent  or  similarly  qualified

persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This

could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do NOT branch the power supply for the drain pump,

etc.  from  the  terminal  block.  This  could  result  in

electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes

without thermal insulation as such pipes will be very hot.

4.6.1

Guidelines when connecting the electrical
wiring

▪ If single-core wires are used, be sure to curl the end of the lead.

Improper work may cause heat or fire.

▪ The  earth  wire  between  the  pull  relief  and  the  terminal  must  be

longer than the other wires.

4.6.2

Specifications of standard wiring
components

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with

applicable legislation

Interconnection cable

(indoor↔outdoor)

4-core cable ≥1.5 mm² and

applicable for 220~240 V

Recommended field fuse

15 A

Earth leakage circuit breaker

MUST comply with

applicable legislation

4.6.3

To connect the electrical wiring on the
outdoor unit

1

Remove  the  service  cover.  See 

"4.1.1 

To  open  the  outdoor

unit" on page 

7

.

2

Remove the switch box cover.

3

Open the wire clamp.

4

Connect the interconnection cable and power supply as follows:

5

Tighten the terminal screws securely. We recommend using a

Phillips screwdriver.

6

Install the switch box cover.

7

Install the service cover.

4.7

Finishing the outdoor unit
installation

4.7.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable

as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.7.2

To close the outdoor unit

NOTICE

When  closing  the  outdoor  unit  cover,  make  sure  that  the

tightening torque does NOT exceed 4.1 N•m.

2

1

1

5

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or

pressure  sensors/switches.  Burning  of  the  compressor

might result.

5.1

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

Summary of Contents for RXF50A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50A2V1B RXF60A2V1B...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...vat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direkti...

Page 4: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 5: ...the electrical wiring 12 4 6 2 Specifications of standard wiring components 12 4 6 3 To connect the electrical wiring on the outdoor unit 12 4 7 Finishing the outdoor unit installation 12 4 7 1 To fin...

Page 6: ...ient place for carrying the unit in and out of the site Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Provide sufficient space around...

Page 7: ...3 2 Preparing refrigerant piping 3 2 1 Refrigerant piping requirements Piping material Phosphoric acid deoxidised seamless copper Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 12 7 mm 1 2 Piping...

Page 8: ...ee space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow In this case it is recommended to construct a pedestal 330 5 8 0 2 4 0 2...

Page 9: ...unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten those ends 4 3 Connecting the refrigerant piping DANGER RISK OF BURNING 4 3 1 About connecting the re...

Page 10: ...old pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the following Chec...

Page 11: ...NFORMATION Piping length is the one way length of liquid piping 4 5 4 To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the fact...

Page 12: ...lation Interconnection cable indoor outdoor 4 core cable 1 5 mm and applicable for 220 240 V Recommended field fuse 15 A Earth leakage circuit breaker MUST comply with applicable legislation 4 6 3 To...

Page 13: ...F INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 5 4 Starting up the outdoor unit See...

Page 14: ...t ON OFF switch if present on the indoor unit using the indoor unit user interface Method 1 Using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result Operation will s...

Page 15: ...REAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC...

Page 16: ...3 2017 11 7 2 Piping diagram 7 2 1 Piping diagram Outdoor unit RXF60A2V1B PED categories of equipment High pressure switches category IV Compressor category II Other art 4 3 equipment Note When the hi...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 3 2017 11 Copyright 2017 Daikin...

Reviews: