background image

4 Installation

Installation manual

10

RXF50+60A2V1B

R32 split series

3P512025-3 – 2017.11

4.3.3

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

1

Connect the liquid refrigerant connection from the indoor unit to

the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect the gas refrigerant connection from the indoor unit to

the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between

indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the

refrigerant piping is wrapped with finishing tape.

4.4

Checking the refrigerant piping

4.4.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see

"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution

from your wholesaler. Do not use soap water, which may

cause cracking of flare nuts (soap water may contain salt,

which  absorbs  moisture  that  will  freeze  when  the  piping

gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap

water  may  contain  ammonia  which  causes  a  corrosive

effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of

at  least 

200 

kPa 

(2 

bar).  It  is  recommended  to  pressurize  to

3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all

connections.

3

Discharge all nitrogen gas.

4.4.2

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates

−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the

system. This procedure is

finished.

Increases

There is moisture in the

system. Go to the next step.

3

Vacuum the system for at least 

hours to a manifold pressure

of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least

1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain

the vacuum for 1 hour, do the following:

▪ Check for leaks again.

▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the

refrigerant piping and performing vacuum drying. Running

the  system  with  the  stop  valves  closed  may  break  the

compressor.

4.5

Charging refrigerant

4.5.1

About charging refrigerant

The  outdoor  unit  is  factory  charged  with  refrigerant,  but  in  some

cases the following might be necessary:

What

When

Charging additional refrigerant

When the total liquid piping

length is more than specified

(see later).

Completely recharging refrigerant

Example: 

▪ When relocating the system.
▪ After a leak.

Charging additional refrigerant

Before charging additional refrigerant, make sure the outdoor unit's

external

 refrigerant piping is checked (leak test, vacuum drying).

INFORMATION

Depending on the units and/or the installation conditions, it

might be necessary to connect electrical wiring before you

can charge refrigerant.

Typical workflow – Charging additional refrigerant typically consists

of the following stages:

1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

Completely recharging refrigerant

Before completely recharging refrigerant, make sure the following is

done:

1 All refrigerant is recovered from the system.
2 The outdoor unit's 

external

 refrigerant piping is checked (leak

test, vacuum drying).

3 Vacuum drying on the outdoor unit's 

internal

 refrigerant piping is

performed.

NOTICE

Before  completely  recharging,  perform  vacuum  drying  on

the outdoor unit's 

internal

 refrigerant piping as well.

Typical  workflow  –  Completely  recharging  refrigerant  typically

consists of the following stages:

1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

Summary of Contents for RXF50A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50A2V1B RXF60A2V1B...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...vat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direkti...

Page 4: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 5: ...the electrical wiring 12 4 6 2 Specifications of standard wiring components 12 4 6 3 To connect the electrical wiring on the outdoor unit 12 4 7 Finishing the outdoor unit installation 12 4 7 1 To fin...

Page 6: ...ient place for carrying the unit in and out of the site Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Provide sufficient space around...

Page 7: ...3 2 Preparing refrigerant piping 3 2 1 Refrigerant piping requirements Piping material Phosphoric acid deoxidised seamless copper Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 12 7 mm 1 2 Piping...

Page 8: ...ee space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow In this case it is recommended to construct a pedestal 330 5 8 0 2 4 0 2...

Page 9: ...unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten those ends 4 3 Connecting the refrigerant piping DANGER RISK OF BURNING 4 3 1 About connecting the re...

Page 10: ...old pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the following Chec...

Page 11: ...NFORMATION Piping length is the one way length of liquid piping 4 5 4 To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the fact...

Page 12: ...lation Interconnection cable indoor outdoor 4 core cable 1 5 mm and applicable for 220 240 V Recommended field fuse 15 A Earth leakage circuit breaker MUST comply with applicable legislation 4 6 3 To...

Page 13: ...F INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 5 4 Starting up the outdoor unit See...

Page 14: ...t ON OFF switch if present on the indoor unit using the indoor unit user interface Method 1 Using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result Operation will s...

Page 15: ...REAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC...

Page 16: ...3 2017 11 7 2 Piping diagram 7 2 1 Piping diagram Outdoor unit RXF60A2V1B PED categories of equipment High pressure switches category IV Compressor category II Other art 4 3 equipment Note When the hi...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 3 2017 11 Copyright 2017 Daikin...

Reviews: