background image

6 Disposal

Installation manual

13

RXF50+60A2V1B

R32 split series

3P512025-3 – 2017.11

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.
The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been

bypassed.
The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.
There are NO 

loose  connections

 or damaged electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.
The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.
The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.
The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between

the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The indoor unit receives the signals of the 

user interface

.

The  specified  wires  are  used  for  the 

interconnection

cable

.

5.2

Checklist during commissioning

To perform an 

air purge

.

To perform a 

test run

.

5.3

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test run may be performed done in cooling or heating

mode.

Prerequisite: 

Test run should be performed in accordance with the

operation manual of the indoor unit to make sure that all functions

and parts are working properly.

1

In cooling mode, select the lowest programmable temperature.

In heating mode, select the highest programmable temperature.

Test run can be disabled if necessary.

2

When the test run is finished, set the temperature to a normal

level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

The  system  stops  operating 

minutes  after  turning  the  unit

OFF.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.
▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

5.4

Starting up the outdoor unit

See  the  indoor  unit  installation  manual  for  configuration  and

commissioning of the system.

6

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  the

dismantling of the system, treatment of the refrigerant, oil

and  other  parts  MUST  comply  with  applicable  legislation.

Units  MUST  be  treated  at  a  specialised  treatment  facility

for reuse, recycling and recovery.

6.1

Overview: Disposal

Typical workflow

Disposing of the system typically consists of the following stages:
1

Pumping down the system.

2

Bringing the system to a specialized treatment facility.

INFORMATION

For more details, see the service manual.

6.2

To pump down

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

 If you want to pump

down the system, and there is a leakage in the refrigerant

circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the

system into the outdoor unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor

because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

NOTICE

During pump down operation, stop the compressor before

removing  the  refrigerant  piping.  If  the  compressor  is  still

running and the stop valve is open during pump down, air

will be sucked into the system. Compressor breakdown or

damage to the system can result due to abnormal pressure

in the refrigerant cycle.

Pump down operation will extract all refrigerant from the system into

the outdoor unit.

1

Remove the valve lid from the liquid stop valve and the gas stop

valve.

2

Carry  out  the  forced  cooling  operation.  See 

"6.3 

To  start  and

stop forced cooling" on page 

14

.

3

After 5 to 

10 

minutes (after only 1 or 

minutes in case of very

low ambient temperatures (<−10°C)), close the liquid stop valve

with a hexagonal wrench.

4

Check on the manifold if the vacuum is reached.

5

After 

2-3 

minutes,  close  the  gas  stop  valve  and  stop  forced

cooling operation.

Summary of Contents for RXF50A2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50A2V1B RXF60A2V1B...

Page 2: ...izate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v...

Page 3: ...vat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direkti...

Page 4: ...ava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TS...

Page 5: ...the electrical wiring 12 4 6 2 Specifications of standard wiring components 12 4 6 3 To connect the electrical wiring on the outdoor unit 12 4 7 Finishing the outdoor unit installation 12 4 7 1 To fin...

Page 6: ...ient place for carrying the unit in and out of the site Choose a location where the hot cold air discharged from the unit or the operation noise will NOT disturb anyone Provide sufficient space around...

Page 7: ...3 2 Preparing refrigerant piping 3 2 1 Refrigerant piping requirements Piping material Phosphoric acid deoxidised seamless copper Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 12 7 mm 1 2 Piping...

Page 8: ...ee space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow In this case it is recommended to construct a pedestal 330 5 8 0 2 4 0 2...

Page 9: ...unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten those ends 4 3 Connecting the refrigerant piping DANGER RISK OF BURNING 4 3 1 About connecting the re...

Page 10: ...old pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the following Chec...

Page 11: ...NFORMATION Piping length is the one way length of liquid piping 4 5 4 To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the fact...

Page 12: ...lation Interconnection cable indoor outdoor 4 core cable 1 5 mm and applicable for 220 240 V Recommended field fuse 15 A Earth leakage circuit breaker MUST comply with applicable legislation 4 6 3 To...

Page 13: ...F INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 5 4 Starting up the outdoor unit See...

Page 14: ...t ON OFF switch if present on the indoor unit using the indoor unit user interface Method 1 Using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result Operation will s...

Page 15: ...REAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC...

Page 16: ...3 2017 11 7 2 Piping diagram 7 2 1 Piping diagram Outdoor unit RXF60A2V1B PED categories of equipment High pressure switches category IV Compressor category II Other art 4 3 equipment Note When the hi...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P512025 3 2017 11 Copyright 2017 Daikin...

Reviews: