background image

15

English

8-2 Test run

Caution

After completing installation, be sure to open the valve. (Operat-
ing the unit with the valve shut will break the compressor.)

Power supply connection

When running the unit for the first time after installation, be sure to
perform a test run following these steps for test run. (Not performing
a test run when the unit is first installed may prevent the unit from
operating properly.)

During the operation, monitor the outdoor unit operation status
and check for any incorrect wiring.

(Refer to figure 22)

1.

Electric box lid

2.

Service lid

3.

[Service precautions] Label location

〈〈〈〈

Cautions for check operation

〉〉〉〉

If the system is started within about 12 minutes after the outdoor/
indoor units are turned ON, the compressor will not run and H2P
lights up. Before starting an operation, always verify that the LED
display shows the contents of the table in “8-2 Test run 2.”.

The system may require up to 10 minutes until it can start the
compressor after an operation start. This is a normal operation to
equalize the refrigerant distribution.

The check operation does not provide any means of checking the
indoor units individually. For that purpose, perform normal opera-
tion using the remote controller after the check operation.

Remote controller displays an error:

Temperature adjustment operation confirmation

After the test run is over, operate the unit normally. (Heating is not
possible if the outdoor temperature is 24°C or higher.)

Make sure the indoor and outdoor units are operating normally
(If a knocking sound can be heard in the liquid compression of the
compressor, stop the unit immediately and then energize the heater
for a sufficient length of time before restarting the operation.)

Run each indoor unit one at a time and make sure the corre-
sponding outdoor unit is also running.

Check to see if cold (or hot) air is coming out of the indoor unit.

Press the fan direction and fan strength buttons on the indoor
unit to see if they operate properly.

Caution

〈〈〈〈

Cautions for normal operation check

〉〉〉〉

Once stopping, the compressor will not restart in about 5 minutes
even if the

Run/Stop

button of an indoor unit in the same system

is pressed.

When the system operation is stopped by the remote controller,
the outdoor units may continue operating for further 5 minutes at
maximum.

If the system has not undergone any check operation by the test
operation button since it was first installed, an error code “U3” is
displayed. In this case, perform check operation referring to

8-2 Test run

”.

After the test run, when handing the unit over to the customer,
make sure the electric box lid, the service lid, and the unit casing
are all attached.

1. Turn ON the power to the outdoor

units and indoor units.

3.

.

As necessary, configure the system
settings onsite by using the dipswitch
(DS1) on the outdoor unit P-board
(A1P) and push button switches
(BS1 to 5).

Always perform configuration after turning ON the
power. To learn the setting method, refer to the
[Service Precautions] label attached at the
position shown in the figure on the right
(Electric box lid in outdoor unit).
(Remember, the actual settings you have made
must be recorded on the [Service Precautions]
label.)

.

When the system is in the multiple-

outdoor unit configuration (Out Multi),
perform the configuration on the parent
unit. (Any settings made on a child unit
will be ignored.)

2. Check the LED on the P-board (A1P) in the outdoor unit to see if the data transmission

is performed normally.

Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm
the crankcase preliminarily by the electric heater.

LED display
(Default status
before delivery)

One outdoor unit installed

When multiple
outdoor unit
installed (

)

Master station
Sub station 1

Sub station 2

Microcomputer
operation
monitor

Page

HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

Ready/
Error

Cooler/heater changeover

Individual

Bulk
(parent)

Bulk
(child)

Low
noise

Demand

Multi

LED display:

OFF

ON

Blinking

(

) The base (parent) unit is the outdoor unit to which the interconnecting wiring for the

indoor units is connected. The other outdoor units are child units.

4. Check if the shutoff valves are in

appropriate status and correct any
wrong status. (Refer to the table in

6-6 Additional Refrigerant Charge

”.)

5. Perform the check operation

following the instructions printed
on the [Service Precaution] label.

Do not leave any shutoff valve closed.
Otherwise the compressor will fail.

The system operates for about 15 minutes
(30 minutes at maximum) and automatically
stops the test operation. The system can start a
normal operation about 15 minutes after the test
operation, only if the remote controller displays
no error codes.

Caution

Malfunction

code

Installation error

Remedial action

E3
E4
F3

UF

The shutoff valve
of an indoor unit
is left closed.

Check referring to the table in

6-6 Additional Refrigeran

Charge

”.

U1

The phases of
the power to the
outdoor units are
reversed.

Exchange two of the three phases
(L1, L2, L3) to make a positive phase
connection.

U1
U4

No power is
supplied to an
outdoor or
indoor unit
(including phase
interruption).

Check if the power wiring for the out-
door units are connected correctly.
(If the power wire is not connected to
L2 phase, no malfunction display will
appear and the compressor will not
work.)

UF

Incorrect inter-
connections
between units

Check if the refrigerant line piping
and the unit wiring are consistent
with each other.

E3
F6

UF

Refrigerant
overcharge

Recalculate the required amount of
refrigerant from the piping length and
correct the refrigerant charge level by
recovering any excessive refrigerant
with a refrigerant recovery machine.

E4
F3

Insufficient
refrigerant

• Check if the additional refrigerant

charge has been finished correctly.

• Recalculate the required amount

of refrigerant from the piping
length and add an adequate
amount of refrigerant.

U7
UF

If an outdoor
multi terminal is
connected when
there is one
outdoor unit
installed

Remove the line from the outdoor
multi terminals (Q1 and Q2).

01_3P114261-9L-EN.fm Page 15 Thursday, August 28, 2003 3:33 PM

Summary of Contents for RX5MY1

Page 1: ...conditioner Chinese RX5MY1 E RX8MY1 E RX10MY1 E RX12MY1 E RX14MY1 E RX16MY1 E RX18MY1 E RX20MY1 E RX22MY1 E RX24MY1 E RX26MY1 E RX28MY1 E RX30MY1 E RX32MY1 E RX34MY1 E RX36MY1 E RX38MY1 E RX40MY1 E R...

Page 2: ...B4 fm 1...

Page 3: ...type RX12 14 16 type RX5 type RX12 14 16 type RX8 10 type 6 3 2 8 4 7 4 4 6 1 1 6 3 4 2 5 3 4 1 figure 4 722 737 80 80 765 A B 1 2 3 1 2 1 RX18 48 type RX5 16 type 2 6 7 3 4 5 1 4 2 3 10 15 8 9 17 1...

Page 4: ...Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P 3 figure 16 figure 18 A B C F1 X1M F2 F1 F2 1 2 3 4...

Page 5: ...5 6 RX12 14 16 type RX5 8 10 type 7 8 9 8 14 15 16 17 18 19 20 21 22 10 11 1 4 In the case RX5 type In the case RX8 10 type figure 24 1 1 2 2 RX5 8 10 type RX12 14 16 type figure 25 A B C A B C 1 DS1...

Page 6: ...unit is for R22 See the catalog for indoor unit models which can be connected Normal operation is not possible when connected to other units Caution Do not allow children to mount on the outdoor unit...

Page 7: ...45 15 14 10 20 25 27 30 30 B 43 A Small Large RX5 type RX8 16 type RX 12 16 type RX 8 16 type RX12 16 type Number of outdoor units 2 3 Kit name BHF22M90 BHF22M135 Kit name KHRJ26K40TP KHRJ26K40HP KHRJ...

Page 8: ...9 1 6 Crankcase heater W 33 33 33 Refrigerant type R22 Refrigerant charge Kg 8 5 13 1 13 9 15 6 Condenser Nominal air flow m3 min 75 175 180 210 Fan motor output W 0 35 0 75 Model RX14MY1 E RX16MY1 E...

Page 9: ...r supply Phase 3N Frequency Hz 50Hz Voltage V 380 415 Voltage torerance 10 Recommended fuses A 90 100 100 100 Compressor Phase 3 Frequency Hz 50Hz Voltage V 380 415 Nominal running current A 8 3 7 6 8...

Page 10: ...t operation of the unit 3 The refrigerant R22 itself is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size...

Page 11: ...nstalled by a licensed refrigeration techni cian and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to...

Page 12: ...manual delivered with the kit Mount the REFNET joint so that it branches either horizontally or vertically Refer to figure 8 1 Horizontal wires 2 Up to 30 or vertically Mount the REFNET header so tha...

Page 13: ...Piping between outdoor units to indoor unit to indoor unit to indoor unit to indoor unit to indoor unit Downward inclination Downward inclination Oil remains in piping A B A B Prohibited pattern to i...

Page 14: ...er than the first branch select the proper branch kit model based on the total capacity index 100 100 x 160 160 x 330 KHRJ26K11T KHRJ26K18T KHRJ26K37T KHRJ26K40T KHRJ26K40TP KHRJ26K75T KHRJ26K75TP KHR...

Page 15: ...Closing shutoff valve 1 Remove the cap and turn the valve clockwise with the hexagon wrench JISB4648 2 Securely tighten the valve until the shaft contacts the main body seal 3 Make sure to tighten th...

Page 16: ...ear side of the front cover Note refer to the example of connection for the amount to be added After the vacuum drying is finished charge the additional refriger ant in its liquid state through the li...

Page 17: ...s 4 of the supply rating Follow the electrical wiring diagram when carrying out any elec trical wiring Only proceed with wiring work after blocking off all power Always ground wires In accordance with...

Page 18: ...re it so that it comes through the cut out section of the cup washer An improper ground con nection may prevent a good ground from being achieved Field line connection transmission wiring and cool hea...

Page 19: ...g between the outdoor units in the same pipe line must be connected to the Q1 Q2 Out Multi terminals Connecting the wires to the Out Out terminals results in system malfunction The wiring for the othe...

Page 20: ...learn the setting method refer to the Service Precautions label attached at the position shown in the figure on the right Electric box lid in outdoor unit Remember the actual settings you have made m...

Page 21: ...ever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility is divided into 2 entirely inde pendent refrigera...

Page 22: ...3P114261 9L EM03A074A 0310 HT COVER fm Page 5 Thursday August 28 2003 11 22 AM...

Reviews: