background image

11

English

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the unit without
a torque wrench, you may follow the installation method mentioned below.

After the work is finished, make sure to check that there is no gas leak.

When you keep on tightening the flare nut with a spanner, there is a
point where the tightening torque suddenly increases. From that
position, further tighten the flare nut the angle shown below:

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local and
national regulations.

6-5 Pipe insulation

After finishing the leak test and vacuum drying, the piping must be
insulated. Take into account the following points:

Make sure to insulate the connection piping and refrigerant
branch kits entirely.

Be sure to insulate the liquid-side and gas-side piping for the
inter-unit piping and the refrigerant branch kits and always use
RX18-type or better insulation for the oil pressure equalizer.
Not insulating them may cause leaking. (The gas piping can reach
temperatures of 120°C. Be sure the insulation used can withstand
such temperatures.)

If you think the humidity around the cooling piping might exceed
30°C and RH80%, reinforce the insulation on the cooling piping
(at least 20mm thick). Condensation might form on the surface of
the insulation.

If there is a possibility that condensation on the shut-off valve
might drip down into the indoor unit through gaps in the insulation
and piping because the outdoor unit is located higher than the
indoor unit, etc., this must be prevented by corking the connec-
tions, etc.

(Refer to figure 11)

1.

One outdoor unit installed:

2.

Liquid line shutoff valve

3.

Gas line shutoff valve

4.

Outer-to-inner interconnecting piping

5.

Calking treatment, etc.

6.

Heat insulator

7.

Oil-equalizing line shutoff valve

8.

When multiple outdoor units installed:

Caution

Be sure to insulate local pipes, as touching them can cause
burns.

6-6 Additional refrigerant charge

Caution

Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the leak test
and the vacuum drying (see above).
When charging a system, care shall be taken that its maximum
permissible charge is never exceeded, in view of the danger of
liquid hammer.
Charging with an unsuitable substance may cause explosions
and accidents, so always ensure that the appropriate refrigerant
(R22) is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when charg-
ing refrigerant.

TO AVOID COMPRESSOR BREAKDOWN. DO NOT CHARGE THE
REFRIGERANT MORE THAN THE SPECIFED AMOUNT TO RAISE
THE CONDENSING PRESSURE.

This outdoor unit is factory charged with refrigerant and depend-
ing on pipe sizes and pipe lengths some systems require addi-
tional charging of refrigerant.

Determine the amount of refrigerant to be added by referring to
the table, write it down on the included “Added Refrigerant” plate
and attach it to the rear side of the front cover.
Note: refer to the example of connection for the amount to be
added.

After the vacuum drying is finished, charge the additional refriger-
ant in its liquid state through the liquid stop valve service port.
Taking into account following instructions:

1.

Check that gas and liquid stop valves are closed.

2.

Stop the compressor and charge the specified weight of refrig-
erant.

If the outdoor unit is not in operation and the total amount cannot
be charged, follow the procedures for additional refrigerant
charge shown below.

Make sure to use installation tools you exclusively use on R22
installations to withstand the pressure and to prevent foreign
materials from mixing into the system.

Note

Procedures for charging additional refrigerant.

One outdoor unit installed: In case of RX5-16 type

(Refer to figure 12)

1.

Pressure reducing valve

2.

Nitrogen

3.

Tank

4.

Siphon system

5.

Measuring instrument

6.

Vacuum pump

7.

Valve A

8.

Gas side

9.

Outdoor unit

10.

Liquid side

11.

Indoor unit

12.

Shutoff valve service port

13.

Charge hose

14.

To indoor unit

15.

Oil-equalizing line

16.

Valve B

17.

Dotted lines represent onsite piping

[Additional refrigerant charge procedure]
To learn the system settings for additional refrigerant charging, refer
to the [Service Precaution] label attached on the back of the electric
box lid in the outdoor unit.

1.

Fully open the gas line shutoff valve (liquid line shutoff valve
and valve A above must be left fully closed) and start the addi-
tional refrigerant charge operation.

2.

After the system is charged with a specified amount of refrig-
erant, press the confirmation button (BS3) on the P-board
(A1P) in the outdoor unit to stop the additional refrigerant
charge operation.

3.

Immediately restore the shutoff valve to the following status.
(The test run cannot be performed properly if the shut-off valve
is not correct.)

When multiple outdoor units installed: In case of
RX18-48MY1(E)
(Refer to figure 12)

[Additional refrigerant charge procedure]
To learn the system settings for additional refrigerant charging, refer
to the [Service Precaution] label attached on the back of the electric
box lid in the outdoor unit.

1.

Fully open the gas line shutoff valve/oil-equalizing line shutoff
valve (liquid line shutoff valve and valves A and B above must be
left fully closed), start the additional refrigerant charge operation.

2.

After the system is charged with a specified amount of refrig-
erant, press the confirmation button (BS3) on the P-board
(A1P) in the outdoor unit to stop the additional refrigerant
charge operation.

3.

Immediately restore the shutoff valve to the following status.
(The test run cannot be performed properly if the shut-off valve
is not correct.)

Caution

If the refrigerant cylinder is siphonal, set it upright while charging
additional refrigerant.

Pipe size

Further tightening angle

Recommended arm length of tool

9.5 (3/8”)

60 to 90 degrees

Approx. 200 mm

12.7 (1/2”)

30 to 60 degrees

Approx. 250 mm

15.9 (5/8”)

30 to 60 degrees

Approx. 300 mm

Liquid line

shutoff valve

Gas line

shutoff valve

Oil-equalizing line

shutoff valve

Open

Open

Close (Default status

before delivery)

Liquid line

shutoff valve

Gas line

shutoff valve

Oil-equalizing line

shutoff valve

Open

Open

Open

01_3P114261-9L-EN.fm Page 11 Thursday, August 28, 2003 3:33 PM

Summary of Contents for RX5MY1

Page 1: ...conditioner Chinese RX5MY1 E RX8MY1 E RX10MY1 E RX12MY1 E RX14MY1 E RX16MY1 E RX18MY1 E RX20MY1 E RX22MY1 E RX24MY1 E RX26MY1 E RX28MY1 E RX30MY1 E RX32MY1 E RX34MY1 E RX36MY1 E RX38MY1 E RX40MY1 E R...

Page 2: ...B4 fm 1...

Page 3: ...type RX12 14 16 type RX5 type RX12 14 16 type RX8 10 type 6 3 2 8 4 7 4 4 6 1 1 6 3 4 2 5 3 4 1 figure 4 722 737 80 80 765 A B 1 2 3 1 2 1 RX18 48 type RX5 16 type 2 6 7 3 4 5 1 4 2 3 10 15 8 9 17 1...

Page 4: ...Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P 3 figure 16 figure 18 A B C F1 X1M F2 F1 F2 1 2 3 4...

Page 5: ...5 6 RX12 14 16 type RX5 8 10 type 7 8 9 8 14 15 16 17 18 19 20 21 22 10 11 1 4 In the case RX5 type In the case RX8 10 type figure 24 1 1 2 2 RX5 8 10 type RX12 14 16 type figure 25 A B C A B C 1 DS1...

Page 6: ...unit is for R22 See the catalog for indoor unit models which can be connected Normal operation is not possible when connected to other units Caution Do not allow children to mount on the outdoor unit...

Page 7: ...45 15 14 10 20 25 27 30 30 B 43 A Small Large RX5 type RX8 16 type RX 12 16 type RX 8 16 type RX12 16 type Number of outdoor units 2 3 Kit name BHF22M90 BHF22M135 Kit name KHRJ26K40TP KHRJ26K40HP KHRJ...

Page 8: ...9 1 6 Crankcase heater W 33 33 33 Refrigerant type R22 Refrigerant charge Kg 8 5 13 1 13 9 15 6 Condenser Nominal air flow m3 min 75 175 180 210 Fan motor output W 0 35 0 75 Model RX14MY1 E RX16MY1 E...

Page 9: ...r supply Phase 3N Frequency Hz 50Hz Voltage V 380 415 Voltage torerance 10 Recommended fuses A 90 100 100 100 Compressor Phase 3 Frequency Hz 50Hz Voltage V 380 415 Nominal running current A 8 3 7 6 8...

Page 10: ...t operation of the unit 3 The refrigerant R22 itself is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size...

Page 11: ...nstalled by a licensed refrigeration techni cian and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to...

Page 12: ...manual delivered with the kit Mount the REFNET joint so that it branches either horizontally or vertically Refer to figure 8 1 Horizontal wires 2 Up to 30 or vertically Mount the REFNET header so tha...

Page 13: ...Piping between outdoor units to indoor unit to indoor unit to indoor unit to indoor unit to indoor unit Downward inclination Downward inclination Oil remains in piping A B A B Prohibited pattern to i...

Page 14: ...er than the first branch select the proper branch kit model based on the total capacity index 100 100 x 160 160 x 330 KHRJ26K11T KHRJ26K18T KHRJ26K37T KHRJ26K40T KHRJ26K40TP KHRJ26K75T KHRJ26K75TP KHR...

Page 15: ...Closing shutoff valve 1 Remove the cap and turn the valve clockwise with the hexagon wrench JISB4648 2 Securely tighten the valve until the shaft contacts the main body seal 3 Make sure to tighten th...

Page 16: ...ear side of the front cover Note refer to the example of connection for the amount to be added After the vacuum drying is finished charge the additional refriger ant in its liquid state through the li...

Page 17: ...s 4 of the supply rating Follow the electrical wiring diagram when carrying out any elec trical wiring Only proceed with wiring work after blocking off all power Always ground wires In accordance with...

Page 18: ...re it so that it comes through the cut out section of the cup washer An improper ground con nection may prevent a good ground from being achieved Field line connection transmission wiring and cool hea...

Page 19: ...g between the outdoor units in the same pipe line must be connected to the Q1 Q2 Out Multi terminals Connecting the wires to the Out Out terminals results in system malfunction The wiring for the othe...

Page 20: ...learn the setting method refer to the Service Precautions label attached at the position shown in the figure on the right Electric box lid in outdoor unit Remember the actual settings you have made m...

Page 21: ...ever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility is divided into 2 entirely inde pendent refrigera...

Page 22: ...3P114261 9L EM03A074A 0310 HT COVER fm Page 5 Thursday August 28 2003 11 22 AM...

Reviews: