[When multiple outdoor units installed: In case of
RX18-48 type]
To connect the piping between outdoor units, an optional piping
kit (multi connection piping kit) is always required. When install-
ing the piping, follow the instructions in the installation manual
that comes with the kit.

Front connection:
Remove the shutoff valve cover to connect.

(Refer to figure 6)

Side (bottom) connection:
Remove the knock holes on the bottom frame and route the piping
under the bottom frame.

(Refer to figure 6)

1.

Front connection:

2.

Remove the shutoff valve cover to connect.

3.

Flange:

4.

(or flare nut in case of models RX5 type)

5.

Gas side accessory pipe (1) (2) (3) (4)

6.

Oil-equalizing piping shutoff valve (Except RX5)

7.

No piping work is needed.

8.

Flare nut

9.

Brazing

10.

Liquid side piping (field supply)

11.

Side (bottom) connection:

12.

Remove the knock holes on the bottom frame and route
the piping under the bottom frame.

13.

Knockout hole

14.

Punch the knock holes.

15.

Gas side piping (field supply)

16.

Oil-equalizing piping (field supply)

17.

Liquid side accessory pipe (1)(2)

Caution

Be sure to use the attached pipe when carrying out piping work
in the field.

Be sure that the local piping does not touch other pipes,
the bottom panel or side panel. Especially for the bottom
and side connection, be sure to protect the local piping
with the provided insulation, to prevent it from coming into
contact with the casing.

Precautions when knocking out knock holes

Be sure to avoid damaging the casing

After knocking out the holes, we recommend you paint the
edges and areas around the edges using the repair paint to
prevent rusting.

When passing electrical wiring through the knock holes, wrap
the wiring with protective tape to prevent damage.

Open knock holes around the 4 concave knock holes in the
base frame, using a

φ

6mm-bit drill.

(Refer to figure 7)

1.

Knock hole

2.

Drill

3.

Concave section

2.

Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable level difference and
allowable length after branching as indicated in chapter “Example
of connection”

3.

For installation of the refrigerant branching kit, refer to the instal-
lation manual delivered with the kit.

Mount the REFNET joint so that it branches either horizontally
or vertically.

(Refer to figure 8)

1.

(Horizontal wires)

2.

(Up to ±30

°

or vertically.)

Mount the REFNET header so that it branches horizontally.

3.

(Horizontal wires)

4.

Pipe connection

Only use the flare nuts included with the unit.
Using different flare nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing nor-
mal operation.)

Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazing (BCup) which does not require
flux.
(Using a chlorine flux may cause the pipes to corrode, and if it
contains fluoride it may cause the refrigerant lubricant to dete-
riorate, adversely affecting the refrigerant piping system.)

Note

The pressure regulator for the nitrogen released when doing the
brazing should be set to 0.02 MPa(0.2kg/cm

2

) or less.

(Refer to figure 9)

1.

Refrigerant piping

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Manual valve

6.

Regulator

7.

Nitrogen

5.

Protection against contamination when installing pipes

Take measures to prevent foreign materials like moisture and
contamination from mixing into the system.

Great caution is needed when passing copper tubes through
walls.

Precautions when selecting branch piping.

Reducing the size of the main liquid piping

When the equivalent length is 30 m or less and the indoor side is
used in offices, etc.
(I.e. places where even barely audible sounds of refrigerant pass-
ing through the piping might be a problem. This does not include
use in households.)

(Refer to figure 10)

1.

Outdoor unit

2.

Main pipe

3.

Size down

4.

The first refrigerant branching kit.

5.

Indoor unit

[Liquid side]

RX5 type:

.....................................φ

9.5

No need of size down

RX8-10 type:

................................φ

12.7

φ

9.5 (Minmum thickness

φ

0.80mm)

RX12-16 type:

.............................φ

15.9

φ

12.7 (Minmum thickness

φ

0.80mm)

RX18-24 type:

.............................φ

19.1

➔ 

φ

15.9 (Minmum thickness

φ

0.80mm)

RX26-48 type:

.............................φ

22.2

φ

19.1 (Minmum thickness

φ

0.85mm)

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

01_3P114261-9L-EN.fm Page 7 Thursday, August 28, 2003 3:33 PM

Summary of Contents for RX5MY1

Page 1: ...conditioner Chinese RX5MY1 E RX8MY1 E RX10MY1 E RX12MY1 E RX14MY1 E RX16MY1 E RX18MY1 E RX20MY1 E RX22MY1 E RX24MY1 E RX26MY1 E RX28MY1 E RX30MY1 E RX32MY1 E RX34MY1 E RX36MY1 E RX38MY1 E RX40MY1 E R...

Page 2: ...B4 fm 1...

Page 3: ...type RX12 14 16 type RX5 type RX12 14 16 type RX8 10 type 6 3 2 8 4 7 4 4 6 1 1 6 3 4 2 5 3 4 1 figure 4 722 737 80 80 765 A B 1 2 3 1 2 1 RX18 48 type RX5 16 type 2 6 7 3 4 5 1 4 2 3 10 15 8 9 17 1...

Page 4: ...Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P 3 figure 16 figure 18 A B C F1 X1M F2 F1 F2 1 2 3 4...

Page 5: ...5 6 RX12 14 16 type RX5 8 10 type 7 8 9 8 14 15 16 17 18 19 20 21 22 10 11 1 4 In the case RX5 type In the case RX8 10 type figure 24 1 1 2 2 RX5 8 10 type RX12 14 16 type figure 25 A B C A B C 1 DS1...

Page 6: ...unit is for R22 See the catalog for indoor unit models which can be connected Normal operation is not possible when connected to other units Caution Do not allow children to mount on the outdoor unit...

Page 7: ...45 15 14 10 20 25 27 30 30 B 43 A Small Large RX5 type RX8 16 type RX 12 16 type RX 8 16 type RX12 16 type Number of outdoor units 2 3 Kit name BHF22M90 BHF22M135 Kit name KHRJ26K40TP KHRJ26K40HP KHRJ...

Page 8: ...9 1 6 Crankcase heater W 33 33 33 Refrigerant type R22 Refrigerant charge Kg 8 5 13 1 13 9 15 6 Condenser Nominal air flow m3 min 75 175 180 210 Fan motor output W 0 35 0 75 Model RX14MY1 E RX16MY1 E...

Page 9: ...r supply Phase 3N Frequency Hz 50Hz Voltage V 380 415 Voltage torerance 10 Recommended fuses A 90 100 100 100 Compressor Phase 3 Frequency Hz 50Hz Voltage V 380 415 Nominal running current A 8 3 7 6 8...

Page 10: ...t operation of the unit 3 The refrigerant R22 itself is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size...

Page 11: ...nstalled by a licensed refrigeration techni cian and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to...

Page 12: ...manual delivered with the kit Mount the REFNET joint so that it branches either horizontally or vertically Refer to figure 8 1 Horizontal wires 2 Up to 30 or vertically Mount the REFNET header so tha...

Page 13: ...Piping between outdoor units to indoor unit to indoor unit to indoor unit to indoor unit to indoor unit Downward inclination Downward inclination Oil remains in piping A B A B Prohibited pattern to i...

Page 14: ...er than the first branch select the proper branch kit model based on the total capacity index 100 100 x 160 160 x 330 KHRJ26K11T KHRJ26K18T KHRJ26K37T KHRJ26K40T KHRJ26K40TP KHRJ26K75T KHRJ26K75TP KHR...

Page 15: ...Closing shutoff valve 1 Remove the cap and turn the valve clockwise with the hexagon wrench JISB4648 2 Securely tighten the valve until the shaft contacts the main body seal 3 Make sure to tighten th...

Page 16: ...ear side of the front cover Note refer to the example of connection for the amount to be added After the vacuum drying is finished charge the additional refriger ant in its liquid state through the li...

Page 17: ...s 4 of the supply rating Follow the electrical wiring diagram when carrying out any elec trical wiring Only proceed with wiring work after blocking off all power Always ground wires In accordance with...

Page 18: ...re it so that it comes through the cut out section of the cup washer An improper ground con nection may prevent a good ground from being achieved Field line connection transmission wiring and cool hea...

Page 19: ...g between the outdoor units in the same pipe line must be connected to the Q1 Q2 Out Multi terminals Connecting the wires to the Out Out terminals results in system malfunction The wiring for the othe...

Page 20: ...learn the setting method refer to the Service Precautions label attached at the position shown in the figure on the right Electric box lid in outdoor unit Remember the actual settings you have made m...

Page 21: ...ever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately Note Where a single refrigerant facility is divided into 2 entirely inde pendent refrigera...

Page 22: ...3P114261 9L EM03A074A 0310 HT COVER fm Page 5 Thursday August 28 2003 11 22 AM...