Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN/IEC 61000-3-12

(1)

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wire between the indoor 

and outdoor units 

so that the terminal 

numbers match

. Tighten the terminal screws 

securely. We recommend a flathead 
screwdriver be used to tighten the screws. 

Appearance of outdoor units may differ from some models.

Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.

(1)

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-

voltage systems with input current >16 A and 

75 A per phase.

Safety 
breaker 
20A

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more 
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power 
supply
50Hz 220-240V 

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

1

2

3

1

2

3

Power supply
terminal block

Shape wires so 
that the protection 
plate and conduit 
mounting plate fit 
securely.

Service lid

Screws

L

1

L

2

3PEN395501-1A.book  Page 9  Friday, July 24, 2015  1:53 PM

Summary of Contents for RX50KV1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RX50KV1B RX60KV1B RX71KV1B 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Page 2: ...positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...ado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer posi...

Page 4: ...When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control...

Page 5: ...operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing...

Page 6: ...m Allow 300mm of work space below the ceiling surface O D 12 7mm Gas pipe Liquid pipe O D 6 4mm 20g m 20m 30m Max allowable piping length Max allowable piping height Additional refrigerant required fo...

Page 7: ...o Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work only for heat pump models If the drain port is...

Page 8: ...the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A...

Page 9: ...ifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do v...

Page 10: ...nd to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D...

Page 11: ...n 3 minutes then stop the forced operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such as equipment or computer rooms It is never to be used in a...

Page 12: ...insulation from the wire 20mm 2 Connect the inter unit wire between the indoor and outdoor units so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwd...

Page 13: ...OR UNIT To indoor unit POWER SUPPLY Power supply IN CASE OF COOLING ONLY TYPE In case of cooling only type OUTDOOR Outdoor CONDENSER Condenser DISCHARGE Discharge Good Stripping wire at terminal block...

Page 14: ...30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to b...

Page 15: ...3P395501 1A 2015 05 Copyright 2014 Daikin 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Reviews: