Outdoor Unit Installation

6.

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A
Fill from the gas pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official 
national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. 
Sticking instructions are illustrated on the backside of that label. 

7.

Refrigerant piping work

7-1 Cautions on pipe handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

7-2 Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh •°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe 

thermal insulation

Liquid pipe 

thermal insulation

O.D. 12.7mm

O.D. 6.4mm

I.D. 14-16mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm min.

40mm or more

30mm or more

Thickness 0.8mm (C1220T-O)

Filling a cylinder with an attached siphon

Stand the cylinder upright when 

filling.

There is a siphon pipe inside, so the 

cylinder need not be upside-down to 

fill with liquid.

Turn the cylinder upside-down 

when filling.

Filling other cylinders

Please fill in with indelible ink, 

  the factory refrigerant charge of the product, 
  the additional refrigerant amount charged in the field and

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered 
by the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:
GWP

 value:

GWP = global warming potential 

factory refrigerant charge of the 
product: 
see unit name plate 

additional refrigerant amount 
charged in the field 

total refrigerant charge 

Contains fluorinated greenhouse 
gases covered by the Kyoto 
Protocol

outdoor unit

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port 
(e.g. onto the inside of the stop valve cover).

2087.5

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt 
or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Inter-unit wire

Liquid pipe

Drain hose

Finishing tape

Gas pipe 

insulation

Liquid pipe 

insulation

3PEN395501-1A.book  Page 7  Friday, July 24, 2015  1:53 PM

Summary of Contents for RX50KV1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RX50KV1B RX60KV1B RX71KV1B 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Page 2: ...positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...ado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer posi...

Page 4: ...When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control...

Page 5: ...operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing...

Page 6: ...m Allow 300mm of work space below the ceiling surface O D 12 7mm Gas pipe Liquid pipe O D 6 4mm 20g m 20m 30m Max allowable piping length Max allowable piping height Additional refrigerant required fo...

Page 7: ...o Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work only for heat pump models If the drain port is...

Page 8: ...the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A...

Page 9: ...ifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do v...

Page 10: ...nd to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D...

Page 11: ...n 3 minutes then stop the forced operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such as equipment or computer rooms It is never to be used in a...

Page 12: ...insulation from the wire 20mm 2 Connect the inter unit wire between the indoor and outdoor units so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwd...

Page 13: ...OR UNIT To indoor unit POWER SUPPLY Power supply IN CASE OF COOLING ONLY TYPE In case of cooling only type OUTDOOR Outdoor CONDENSER Condenser DISCHARGE Discharge Good Stripping wire at terminal block...

Page 14: ...30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to b...

Page 15: ...3P395501 1A 2015 05 Copyright 2014 Daikin 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Reviews: