5

English

Outdoor Unit Installation

3.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

4.

Refrigerant piping

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches. 

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Torque wrench

Piping union

Flare nut

Flare nut

Spanner

Flare nut tightening torque

Liquid side

1/4 inch

14.2-17.2N • m

(144-175kgf • cm)

Gas side

1/2 inch

49.5-60.3N • m

(505-615kgf • cm)

Valve cap tightening torque

Liquid side

1/4 inch

21.6-27.4N • m

(220-280kgf • cm)

Gas side

1/2 inch

48.1-59.7N • m

(490-610kgf • cm)

Service port cap tightening torque

10.8-14.7N • m (110-150kgf • cm)

Do not apply refrigeration 
oil to the outer surface.

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

[Tighten]

3PEN395501-1A.book  Page 5  Friday, July 24, 2015  1:53 PM

Summary of Contents for RX50KV1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RX50KV1B RX60KV1B RX71KV1B 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Page 2: ...positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...ado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer posi...

Page 4: ...When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control...

Page 5: ...operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing...

Page 6: ...m Allow 300mm of work space below the ceiling surface O D 12 7mm Gas pipe Liquid pipe O D 6 4mm 20g m 20m 30m Max allowable piping length Max allowable piping height Additional refrigerant required fo...

Page 7: ...o Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work only for heat pump models If the drain port is...

Page 8: ...the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A...

Page 9: ...ifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do v...

Page 10: ...nd to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D...

Page 11: ...n 3 minutes then stop the forced operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such as equipment or computer rooms It is never to be used in a...

Page 12: ...insulation from the wire 20mm 2 Connect the inter unit wire between the indoor and outdoor units so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwd...

Page 13: ...OR UNIT To indoor unit POWER SUPPLY Power supply IN CASE OF COOLING ONLY TYPE In case of cooling only type OUTDOOR Outdoor CONDENSER Condenser DISCHARGE Discharge Good Stripping wire at terminal block...

Page 14: ...30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to b...

Page 15: ...3P395501 1A 2015 05 Copyright 2014 Daikin 3PEN395501 1A book Page 1 Friday July 24 2015 1 53 PM...

Reviews: