background image

4

English

Precautions on Installation

•  Check the strength and level of the installation surface so that the unit does not cause 

any operating vibrations or noise after installation.

• 

Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4 

sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all sold 
separately.)

•  It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the 

foundation surface.

3/4” (20mm)

Outdoor Unit Installation Diagram

Refrigerant piping must be protected 

from physical damage.

Install a plastic cover or equivalent.

In sites with poor drainage, 

use block bases for the 

outdoor unit.  

Adjust foot height until the unit 

is level. Otherwise, water 

leakage or pooling of water 

may occur.

unit: inch (mm)

Refrigerant piping must be kept to a minimum.

   *Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.  

**The suggested shortest pipe length is 10ft (3m), in order to avoid 

noise from the outdoor unit and vibration.

(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.)

(Foot bolt-hole centers)

18-1/2 (470)

(From unit’s side)

3-13/16 (97)

(Foot bolt-hole 

centers)

12-1/8 (308)

O.D. 3/8 inch (9.5mm)

Gas pipe

Liquid pipe

O.D. 1/4 inch (6.4mm)

0.21oz/ft (20g/m)

Max. allowable piping length

49-1/4ft (15m)

65-5/8ft (20m)

Max. allowable piping height
Additional refrigerant required for refrigerant 

pipe exceeding 32-3/4ft (10m) in length.

10ft (3m)

Min. allowable piping length

**

*

Allow 11-13/16 (300) 

of work space below the 

ceiling surface.

CAUTION

Keep the piping length between 

10ft (3m) and 65-5/8ft (20m) 

9-13/16 (250) from wall

How to remove the stop 

valve cover

1) Remove the screw on the 

stop valve cover.

2) Slide the stop valve cover 

downward to remove it.

1) Insert the upper part of 

the stop valve cover into  

the outdoor unit.

2) Tighten the screw.

How to attach the stop 

valve cover

Stop valve cover

Allow space for piping 

and electrical servicing.

Wrap the insulation pipe with 

finishing tape from bottom to top.

If strong wind blows into the air discharge 

side from the front and there is a danger 

that the fan may be damaged, change the 

orientation of the air discharge side of the 

outdoor unit or use an air direction 

adjustment grille (sold separately).

If there is a danger of the unit falling or 

overturning, fix the unit with foundation bolts, 

or with wire or other means.

English

01_EN_3P658798-1.indd   4

2021/07/14   12:51:30

Summary of Contents for RX09RMVJU9A

Page 1: ...sh Français Español MODELS RX09RMVJU9A RX12RMVJU9A RXL09QMVJUA RXL12QMVJU9A DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel d installation Manual de instalación ...

Page 2: ...ounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant gas leaks during installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes into contact with fire Exposure to this gas could cause severe injury or death After...

Page 3: ...t be kept clean dry and tight a Clean and Dry Foreign materials including mineral oils such as SUNISO oil or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore tak...

Page 4: ...ll flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m from propane gas cylinders NOTE Cannot be installed suspended from a ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions des...

Page 5: ...led and the environment in which it is used Foot bolt hole centers 18 1 2 470 From unit s side 3 13 16 97 Footbolt hole centers 12 1 8 308 O D 3 8 inch 9 5mm Gas pipe Liquid pipe O D 1 4 inch 6 4mm 0 21oz ft 20g m Max allowable piping length 49 1 4ft 15m 65 5 8ft 20m Max allowable piping height Additional refrigerant required for refrigerant pipe exceeding 32 3 4ft 10m in length 10ft 3m Min allowa...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 150 Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to Precautions for Selecting a Location and the Outdoor Unit Installation Diagram If drain work is necessary follow the procedures in 2 Drain work excluding RX...

Page 7: ...1 0 1 5mm Clutch type Rigid type 0 059 0 079 inch 1 5 2 0mm Wing nut type Imperial type Conventional flare tool Cut exactly at right angles Remove burrs 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a result of deterioration over time To prevent gas leakage apply refrigeration oil only to the inner surface of the flare Use re...

Page 8: ... 32 inch 12 15mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid side Use separate thermal insulation pipes for gas and liquid refrigerant pipes Using finishing tape bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other piping Gas pipe Liquid pipe Gas p...

Page 9: ...valve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s flare and outdoor unit s flare and valve rods After the check is complete wipe all soapy water off 8 Disconnect the charging hoses from the service port for the gas stop valve ...

Page 10: ...e Round crimp style terminal Arrow view Flat washer Screw Round crimp style terminal Good Round crimp style terminal Flat washer Screw Wrong Flat washer Round crimp style terminal Screw A A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and fire Strip wire end to this point Excessive strip length ...

Page 11: ...exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation from the indoor unit outlet vent Cutting the jumper 6 J6 sets the...

Page 12: ...peration press For FTXR and FVX models 1 Press and at the same time 2 Press select and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press For FFQ and FDMQ models For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold t...

Page 13: ...s leaks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System is properly grounded Electrical leakage Only specified wires are used for all wiring and all wires are connected correctly No operation or burn damage Indoor or outdoor unit s air inlet or air out...

Page 14: ...Two dimensional bar code is a manufacturing code 3P658798 1 M21B105 2108 HT ...

Reviews: