[Method of mounting conduit]
•
A protection plate is fixed for protection from the high-voltage section.
1) Dismount the stop valve cover by removing the screw.
2) Dismount the protection plate by removing the 2 screws.
3) Dismount the conduit mounting cover by removing the 2 screws.
4) Pass wires through the conduit and secure them with a lock nut.
5) After completing the work, reattach the conduit mounting cover, the protection plate, and the stop valve cover to its
original position.
1
2
3
1
2
3
1
2
3
Screws
Conduit
mounting
cover
Screws
Protection plate
Power supply
terminal block
Shape wires so
that the protection
plate and conduit
mounting plate fit
securely.
Conduit
Lock nut
Conduit
mounting
plate
L
1
L
2
Facility Setting
(cooling at low outdoor temperature)
WARNING
Make sure to turn the power OFF before performing work.
CAUTION
• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
•
Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew condensation from the indoor unit outlet vent.
• Cutting the jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
This function is designed for facilities such as equipment or computer rooms. It is never to be used in a
residence or office where people occupy the space.
Cutting the jumper 6 (J6) on the circuit board will expand the operation range down to 14°F (–10°C).
Installing an air direction adjustment grille (sold separately) will further extend the operation range to –4°F (–20°C).
In these cases, the unit will stop operating if the outdoor temperature falls below –4°F (–20°C), restarting once the
temperature rises above this level.
1) Remove the top plate of the outdoor unit. (4 screws)
2) Remove the front plate. (5 screws)
3) Cut the jumper (J6) of the PCB inside.