background image

1

English

Contents

Safety Considerations   ....................................  1
Accessories   .....................................................  3
Precautions for Selecting a Location   ...........  3
Precautions on Installation   ............................  4
Outdoor Unit Installation Diagram   ................  4
Installation Space Requirements   ..................  5
Outdoor Unit Installation   ................................  5

1.  Installing the outdoor unit ............................................ 5
2.  Drain work (excluding RXL models) ............................ 5
3.  Flaring the pipe end ..................................................... 6

4.  Refrigerant piping ........................................................ 6
5.  Pressure test and evacuating system .......................... 7

6.  Refilling refrigerant

 ...................................................... 8

Wiring   ...............................................................  9
Facility Setting  
(cooling at low outdoor temperature)   ...........  10
Pump Down Operation   ...................................  11
Trial Operation and Testing   ...........................  12

1.  Trial operation and testing ........................................... 12
2.  Test items .................................................................... 12

Safety Considerations

Read the precautions in this manual 
carefully before operating the unit.

Read these 

Safety Considerations for Installation carefully 

before installing an air conditioner or heat pump. After completing 

the installation, make sure that the unit operates properly during 

the startup operation.

Instruct the user on how to operate and maintain the unit.

Inform users that they should store this installation manual with 

the operation manual for future reference.

Always use a licensed installer or contractor to install this product.

Improper installation can result in water or refrigerant leakage, 

electric shock, fire, or explosion. 

Meanings of 

DANGERWARNINGCAUTION, and NOTE 

Symbols:

 DANGER  ...........

Indicates an imminently hazardous 

situation which, if not avoided, will 

result in death or serious injury.

 WARNING  .........

Indicates a potentially hazardous 

situation which, if not avoided, could 

result in death or serious injury.

 CAUTION  ..........

Indicates a potentially hazardous 

situation which, if not avoided, may 

result in minor or moderate injury. 

It may also be used to alert against 

unsafe practices.

 NOTE  ................

Indicates situations that may result 

in equipment or property damage 

accidents only.

DANGER 

•  Refrigerant gas is heavier than air and replaces oxygen. 

A massive leak can lead to oxygen depletion, especially 

in basements, and an asphyxiation hazard could occur 

leading to serious injury or death.

•  Do not ground units to water pipes, gas pipes, telephone 

wires, or lightning rods as incomplete grounding can cause 

a severe shock hazard resulting in severe injury or death. 

Additionally, grounding to gas pipes could cause a gas leak 

and potential explosion causing severe injury or death.

•  If refrigerant gas leaks during installation, ventilate the 

area immediately. Refrigerant gas may produce toxic gas 

if it comes into contact with fire. Exposure to this gas could 

cause severe injury or death.

•  After completing the installation work, check that the 

refrigerant gas does not leak throughout the system.

• 

Do not install unit in an area where flammable materials 

are present due to risk of explosions that can cause 

serious injury or death.

•  Safely dispose all packing and transportation materials 

in accordance with federal/state/local laws or ordinances. 

Packing materials such as nails and other metal or 

wood parts, including plastic packing materials used for 

transportation may cause injuries or death by suffocation.

WARNING 

• 

Only qualified personnel must carry out the installation 

work. Installation must be done in accordance with this 

installation manual. Improper installation may result in 

water leakage, electric shock, or fire.

•  When installing the unit in a small room, take measures to keep 

the refrigerant concentration from exceeding allowable safety 

limits. Excessive refrigerant leaks, in the event of an accident in 

a closed ambient space, can lead to oxygen deficiency.

• 

Use only specified accessories and parts for installation 

work. Failure to use specified parts may result in water 

leakage, electric shock, fire, or the unit falling.

•  Install the air conditioner or heat pump on a foundation 

strong enough that it can withstand the weight of the unit. 

A foundation of insufficient strength may result in the unit 

falling and causing injuries.

•  Take into account strong winds, typhoons, or earthquakes 

when installing. Improper installation may result in the unit 

falling and causing accidents.

•  Make sure that a separate power supply circuit is provided 

for this unit and that all electrical work is carried out by 

qualified personnel according to local, state, and national 

regulations. An insufficient power supply capacity or 

improper electrical construction may lead to electric shock 

or fire.

The pictures in this document are for illustrative purposes only.

01_EN_3P658798-1.indd   1

2021/07/14   12:51:30

Summary of Contents for RX09RMVJU9A

Page 1: ...sh Français Español MODELS RX09RMVJU9A RX12RMVJU9A RXL09QMVJUA RXL12QMVJU9A DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel d installation Manual de instalación ...

Page 2: ...ounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant gas leaks during installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes into contact with fire Exposure to this gas could cause severe injury or death After...

Page 3: ...t be kept clean dry and tight a Clean and Dry Foreign materials including mineral oils such as SUNISO oil or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore tak...

Page 4: ...ll flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m from propane gas cylinders NOTE Cannot be installed suspended from a ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions des...

Page 5: ...led and the environment in which it is used Foot bolt hole centers 18 1 2 470 From unit s side 3 13 16 97 Footbolt hole centers 12 1 8 308 O D 3 8 inch 9 5mm Gas pipe Liquid pipe O D 1 4 inch 6 4mm 0 21oz ft 20g m Max allowable piping length 49 1 4ft 15m 65 5 8ft 20m Max allowable piping height Additional refrigerant required for refrigerant pipe exceeding 32 3 4ft 10m in length 10ft 3m Min allowa...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 150 Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to Precautions for Selecting a Location and the Outdoor Unit Installation Diagram If drain work is necessary follow the procedures in 2 Drain work excluding RX...

Page 7: ...1 0 1 5mm Clutch type Rigid type 0 059 0 079 inch 1 5 2 0mm Wing nut type Imperial type Conventional flare tool Cut exactly at right angles Remove burrs 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a result of deterioration over time To prevent gas leakage apply refrigeration oil only to the inner surface of the flare Use re...

Page 8: ... 32 inch 12 15mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid side Use separate thermal insulation pipes for gas and liquid refrigerant pipes Using finishing tape bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other piping Gas pipe Liquid pipe Gas p...

Page 9: ...valve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s flare and outdoor unit s flare and valve rods After the check is complete wipe all soapy water off 8 Disconnect the charging hoses from the service port for the gas stop valve ...

Page 10: ...e Round crimp style terminal Arrow view Flat washer Screw Round crimp style terminal Good Round crimp style terminal Flat washer Screw Wrong Flat washer Round crimp style terminal Screw A A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and fire Strip wire end to this point Excessive strip length ...

Page 11: ...exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation from the indoor unit outlet vent Cutting the jumper 6 J6 sets the...

Page 12: ...peration press For FTXR and FVX models 1 Press and at the same time 2 Press select and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press For FFQ and FDMQ models For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold t...

Page 13: ...s leaks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System is properly grounded Electrical leakage Only specified wires are used for all wiring and all wires are connected correctly No operation or burn damage Indoor or outdoor unit s air inlet or air out...

Page 14: ...Two dimensional bar code is a manufacturing code 3P658798 1 M21B105 2108 HT ...